2017-03-10 15:21:421) THE ARCHITECTURAL PLANS CONTAIN COPIES OF THE
 REQUIRED SIGNATURE AND SEAL AND DO NOT COMPLY WITH
 F.A.C. RULE 61G1- 16.001, 61G1-16.003.
 2) SHT. F-2 - THE HOSE BIBB SHALL BE EQUIPPED WITH A
 SHUTOFF VALVE AND A VACUUM BREAKER. 2014 FBC SEC.606.2,
 608.15.4.
 3) INDICATE ON THE PLANS WHERE THE FLOOR DRAIN IN THE
 PUMP ROOM DISCHARGES. THE FLOOR DRAIN SHALL DISCHARGE
 TO THE SANITARY AND BE EQUIPPED WITH A TRAP PRIMER.2014
 FBC SEC.1002.4. SUBMNIT SANITARY RISER DIAGRAM AND ALSO
 A WATER RISER DIAGRAM FOR ANY AND ALL DOMESTIC WATER
 PIPING AND SANITARY DRAIN PIPING FOR THIS PROJECT. WPB
 AMEND. TO FBC SEC. 107.2.1.
 4) SHT. F-3 - THE FEATURE PUMP CURVE TEXT INDICATES A 6
 INCH SUCTION AND A 5 INCH DISCHARGE FOR THE MARLOW
 SERIES 530 SC 5-9 FEATURE DISCHARGE PUMP BUT THE PLAN
 VIEW ON SHT. F-2 AND SHT. F-4 SHOWS AN 8 INCH DISCHARGE
 AND SUCTION. CLARIFY.
 5) SUBMIT MANUF. SPECIFICATION SHEETS FOR THE AQUASTAR
 CHANNEL DRAIN. WPB AMEND. TO 2014 FBC SEC. 107.2.1.
 6) THE AUTO FILL SHALL BE EQUIPPED WITH AN APPROVED
 BACKFLOW PREVENTION DEVICE. 2014 FBC- PLUMBING, SEC.
 608.13, 608.15.
 7) SHT. F-4 - PLACE A NOTE / DETAILS ON THE PLANS AS TO
 HOW THE PIPE SUPPORTS WILL BE SECURED TO THE SUBSTRATE
 AND THE SPACING OF SAID SUPPORTS. WPB AMEND. TO FBC
 SEC. 107.2.1.
 8) SUBMIT FILTRATION RATES / CALCULATIONS FOR THE
 SYSTEM.
  