Plan Review Notes
Plan Review Notes For Permit 16110575
Permit Number 16110575
Review Stop B
Sequence Number 1
Notes
Date Text
2017-03-16 16:20:50BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110575
 ADD: 3200 N. CONGRESS / ENTRY FOUNTAIN
 CONT: HEDRICK BROTHERS
 TEL: 561-308-2954
 E-MAIL: [email protected]
  
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION
  
 1ST REVIEW
 DATE: THURS. MARCH 16/ 2017
 ACTION: DENIED
  
 1) THIS SITE HAS BEEN OR IS THE PROCESS OF BEING
 REPLATED WITH NEW STREET NAMES; THE PERMIT APPLICATION
 USED THE STREET NAME OF N. CONGRESS WHEREAS SHEET
 A-1.101 SHOWS THE STREET DIRECTLY IN FRONT OF THE
 BUILDING NAMED RESORT COURT. . CITY MUNI CODE SEC.78-6
 (1-7). THE SUBMITTED ADDRESS WILL BE REASSIGNED BY
 CONTACT:
 MICHAEL ORIO GIS SUPPORT SPECIALIST/ INFORMATION
 TECHNOLOGY
 TEL: 561-494-1040
 E-MAIL: [email protected]
  
 2) ALL SHEETS SIGNED BY THE ARCHITECT DANIELE E. ADACHE
 THE DESIGNER HAS USED AN INK STAMP FOR THE REQUIRED
 WRITTEN SIGNATURE. FL ADMIN CODE 61G16.003 ARCHITECTS.
 PLANS ARE TO BE SIGNED WITH A FULL SIGNATURE FROM THE
 ARCHITECT OF RECORD PER 481.221 WITH A MINIMUM OF FIRST
 AND LAST NAME AS SHOWN ON THE ARCHITECTS' LICENSE, FAC
 61G1-16.003
  
 3) DISCREPANCY IN PLANS. 107.2.1.3 ADDITIONAL
 INFORMATION IS REQUIRED. THE STRUCTURAL INDEX FOR THE
 TOWER INDICATE THERE ARE MISSING SHEETS, MISSING SHEETS
 ARE:
 S-2.10
 S-3.00
 S-3.01
 S-4.00
 S-5.00
  
 4) SHEET S-0.00 PROVIDES THE WIND DESIGN CRITERIA BUT
 DOES NOT PROVIDE THE PRESSURES FOR ZONES 1-3 FOR THE
 ROOF AND WALL ZONES 4 & 5 FOR THE WALLS AND OPENINGS.
 2014 FBC-B 1603.1.4(5) 5. DESIGN WIND PRESSURES TO BE
 USED FOR EXTERIOR COMPONENT AND CLADDING MATERIALS NOT
 SPECIFICALLY DESIGNED BY THE REGISTERED DESIGN
 PROFESSIONAL RESPONSIBLE FOR THE DESIGN OF THE
 STRUCTURE, PSF (KN/ M2).
 TABLE 1609.7(2) ADJUSTMENT FACTORS FOR HEIGHT &
 EXPOSURE. PROVIDE THE MEAN ROOF HEIGHT FOR THE
 BUILDING.
 1609.3.1 WIND SPEED CONVERSION VULT TO VASD.
  
 5)BUILDING PROVISO/ DEFERRED SUBMITTAL. 107.3.4.2.
 COMPONENTS & CLADDING. 2010/ 2014 FBC-B 1609.1.2
 PROTECTION OF OPENINGS, 1609.6.4.4.1 COMPONENTS &
 CLADDING. FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS,
 ADMINISTRATIVE CODE 61G20-3.005, RULE 9N-3 NOV. 01/
 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS
 (C), WALL LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES,
  
 6) FBC 107.3.4.1 PRODUCT APPROVALS. THOSE PRODUCTS
 WHICH ARE REGULATED BY THE DCA RULE 9N-03 SHALL BE
 REVIEWED AND APPROVED IN WRITING BY THE DESIGNER OF
 RECORD PRIOR TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
 FL 61G1-23.015 (2) THE ARCHITECT IS RESPONSIBLE FOR
 SUPERVISING AND REVIEWING ALL PROJECT DATA, REPORTS,
 SHOP DRAWINGS ETC..
  
 7) WHEN RESUBMITTING PLANS PLEASE INDICATE THE REVISION
 & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES AS
 NECESSARY, COLLATE AND STAPLE INTO SETS OF PLANS. A
 TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW COMMENT
 NUMBER, WITH A DESCRIPTION OF THE REVISION MADE,
 IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE THE
 CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR PERMIT.
 THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER BN, PX, CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 CONSTRUCTION SERVICES DIVISION/ DEVELOPMENT SERVICES
 DEPARTMENT
 401 CLEMATIS ST.
 WEST PALM BEACH. FL 33402
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  