Plan Review Notes For Permit 16110543 |
Permit Number |
16110543 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-01-10 18:40:57 | CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA | | BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION | | | | 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1 | | INFORMATION ON CONSTRUCTION DOCUMENTS | | | | (1) PROVIDE MECHANICAL PLANS SHOWING HVAC FOR ENTIRE | | HOME. PROVIDE MAIN DUCT SIZES, BRANCH SIZES, GRILL | | SIZES, CFM QUANTITIES. DIFFERENTIATE EXISTING AND NEW | | DUCT WORK. | | (2) PROVIDE BALANCE RETURN FROM ALL BEDROOMS | | (3) PROVIDE EXHAUST FROM ALL BATHROOMS | | | | FLORIDA ENERGY CODE FBC 2014 | | | | (4) FORMS R405-2014 REQUIRES SIGNATURE AT OWNER /AGENT. | | (5) HEAT LOAD CALCULATIONS MUST HAVE NAME AND SIGNATURE | | OF PREPARED BY. | | (6) PROVIDE AHRI SHEET | | | | JORGE VALIDO | | WPB MECHANICAL INSPECTOR/PLANS EXAMINER | | [email protected] | | 561-805-6716 | | |
|