Plan Review Notes For Permit 16110543 |
Permit Number |
16110543 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-29 08:37:29 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1.THE WC IN MASTER MATH SHOULD TIE INTO THE BRANCH | | DRAIN FOR MASTER BATHROOM NOT THE STACK. PER WPB AMEND | | TO FBC 107.2.1 | | | | 2.GUEST BATH 2 IT IS REQUIRED TO HAVE A MIN OF 21" OF | | CLEARANCE IN FRONT OF THE WC TO THE TUB PLEASE SHOW OM | | THE PLAN. PER FBC RES P2705.1(5) | | | | 3. COMPLY WITH ALL OTHER TRADE COMMENTS. PER WPB AMEND | | TO FBC 107.2.1 | | |
|