2016-11-28 13:12:48 | JOB PERMIT NUMBER: 16110543 (REVISION) |
| JOB ADDRESS: 336 MARLBOROUGH RD |
| WEST PALM BEACH FLORIDA |
| DATE: NOVEMBER 28, 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| |
| 1] EVERY SEPARATE BUILDING OR AN ADDITION TO AN |
| EXISTING BUILDING FOR WHICH A PERMIT FOR NEW |
| CONSTRUCTION IS ISSUED AND HAVING A FOSSIL-FUEL-BURNING |
| HEATER OR APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE, |
| OR OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON |
| MONOXIDE AS BYPRODUCT OF COMBUSTION SHALL HAVE AN |
| OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10 |
| FEET (3048 MM) OF EACH ROOM USED FOR SLEEPING PURPOSES. |
| FBC-R 315.1 |
| |
| 2] SHOW A SMOKE ALARM IN THE FIRST FLOOR LOWER LEVEL |
| STAIRWAY LANDING PER FBC-R 314.3 |
| |
| 3] BREAKFAST ROOM MISSING A RECEPTACLE IN SHORT WALL |
| SPACE SECTION BY THE 1ST FLOOR DOUBLE DOOR PER FBC-R |
| SECTION E3902.2.2 (2' WALL SPACE). |
| |
| 4] PROVIDE RECEPTACLE & LIGHTING OUTLETS IN BEDROOM 1 & |
| 2 IN ACCORDANCE WITH FBC-R SECTIONS E3901.2.1 & E3903.2 |
| |
| 5] PROVIDE AN ELECTRICAL RISER DIAGRAM, INCLUDE |
| GROUNDING & CONDUIT DETAIL. FBC-107 |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| DIRECTLY. |
| |
| 1ST REVIEW FBC 2014 5TH ED. NEC 2011 |