2016-11-28 13:12:48JOB PERMIT NUMBER: 16110543 (REVISION)
 JOB ADDRESS: 336 MARLBOROUGH RD
 WEST PALM BEACH FLORIDA
 DATE: NOVEMBER 28, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] EVERY SEPARATE BUILDING OR AN ADDITION TO AN
 EXISTING BUILDING FOR WHICH A PERMIT FOR NEW
 CONSTRUCTION IS ISSUED AND HAVING A FOSSIL-FUEL-BURNING
 HEATER OR APPLIANCE, A FIREPLACE, AN ATTACHED GARAGE,
 OR OTHER FEATURE, FIXTURE, OR ELEMENT THAT EMITS CARBON
 MONOXIDE AS BYPRODUCT OF COMBUSTION SHALL HAVE AN
 OPERATIONAL CARBON MONOXIDE ALARM INSTALLED WITHIN 10
 FEET (3048 MM) OF EACH ROOM USED FOR SLEEPING PURPOSES.
 FBC-R 315.1
  
 2] SHOW A SMOKE ALARM IN THE FIRST FLOOR LOWER LEVEL
 STAIRWAY LANDING PER FBC-R 314.3
  
 3] BREAKFAST ROOM MISSING A RECEPTACLE IN SHORT WALL
 SPACE SECTION BY THE 1ST FLOOR DOUBLE DOOR PER FBC-R
 SECTION E3902.2.2 (2' WALL SPACE).
  
 4] PROVIDE RECEPTACLE & LIGHTING OUTLETS IN BEDROOM 1 &
 2 IN ACCORDANCE WITH FBC-R SECTIONS E3901.2.1 & E3903.2
  
 5] PROVIDE AN ELECTRICAL RISER DIAGRAM, INCLUDE
 GROUNDING & CONDUIT DETAIL. FBC-107
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  