2016-11-14 11:41:37RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 CODE: FBC 5TH EDITION (2014).
  
 RAS 117 CALCULATIONS SUBMITTED.
 1- ACCORDING TO SEC. 8.1 OF RAS 117 "THE MINIMUM
 FASTENER SEPARATION SHALL NOT BE LESS THAN 4 IN. O.C.".
 CALCULATIONS SUBMITTED SHOW 2 ROWS OF NAILS ON THE SIDE
 LAP FOR THE CORNER AREAS. THE SIDE LAP IS 4", THEREFORE
 TWO ROWS OF NAILS WILL BE LESS THAN 4 IN. O.C. REVISE
 AS REQUIRED.
  
 2- CALCULATIONS ARE NOT CLEAR. CLARIFY WHY THE NUMBER
 OF NAILS IS HIGHER FOR THE PERIMETER AREA THAN FOR THE
 CORNER AREA. SEC. 107.2.1 CITY AMENDMENTS.
  