Plan Review Notes For Permit 16110526 |
Permit Number |
16110526 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-14 11:41:37 | RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS. | | CODE: FBC 5TH EDITION (2014). | | | | RAS 117 CALCULATIONS SUBMITTED. | | 1- ACCORDING TO SEC. 8.1 OF RAS 117 "THE MINIMUM | | FASTENER SEPARATION SHALL NOT BE LESS THAN 4 IN. O.C.". | | CALCULATIONS SUBMITTED SHOW 2 ROWS OF NAILS ON THE SIDE | | LAP FOR THE CORNER AREAS. THE SIDE LAP IS 4", THEREFORE | | TWO ROWS OF NAILS WILL BE LESS THAN 4 IN. O.C. REVISE | | AS REQUIRED. | | | | 2- CALCULATIONS ARE NOT CLEAR. CLARIFY WHY THE NUMBER | | OF NAILS IS HIGHER FOR THE PERIMETER AREA THAN FOR THE | | CORNER AREA. SEC. 107.2.1 CITY AMENDMENTS. | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CONTACT | | JULIO GOMEZ | | COMMERCIAL COMBINATION PLANS EXAMINER | | DEVELOPMENT SERVICES DEPARTMENT | | (561)805-6712 | | [email protected] |
|