Plan Review Notes For Permit 16110517 |
Permit Number |
16110517 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-16 16:29:32 | REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | PASSED WITH THE FOLLOWING PROVISO | | | | 1] FOR INSTALLATIONS CONSISTING OF NOT MORE THAN TWO | | 2-WIRE BRANCH CIRCUITS, THE SERVICE DISCONNECTING MEANS | | SHALL HAVE A RATING OF NOT LESS THAN 30 AMPERES. NEC | | 230.79(B) |
|