Plan Review Notes
Plan Review Notes For Permit 16110461
Permit Number 16110461
Review Stop B
Sequence Number 3
Notes
Date Text
2016-12-27 08:37:41****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 COMMENTS FROM PREVIOUS LISTS; NOTE THAT SPEC SHEETS ARE
 NOT ACCEPTABLE. TEST REPORTS ARE REQUIRED. NOTE THAT
 ALL THREE REQUIREMENTS COME FROM THE INTERNATIONAL
 BUILDING CODE, SO ARE REQUIREMENTS APPLICABLE IN ANY
 JURISDICTION WHICH HAS ADOPTED THE I-CODES.
  
 THE STC AND IIC TESTS PROVIDED INCLUDE A SUSPENDED
 GYPSUM CEILING IN THE TESTED ASSEMBLY. AS THIS IS NOT
 THE CONDITION FOR THE PROPOSED INSTALLATION, A TEST
 REPORT WITHOUT THE SUSPENDED GYPSUM CEILING ASSEMBLY IS
 REQUIRED.
  
 1. FBC 1207.2, FLOOR/CEILING ASSEMBLIES SEPARATING
 DWELLING UNITS FROM EACH OTHER OR FROM PUBLIC OR
 SERVICE AREAS SHALL HAVE A SOUND TRANSMISSION CLASS
 (STC) OF NOT LESS THAN 50 (45 IF FIELD TESTED) FOR AIR
 BORNE NOISE WHEN TESTED IN ACCORDANCE WITH ASTM E 90.
 IF A SUSPENDED CEILING WAS USED AS A PART OF THE TEST,
 PROVIDE INFORMATION AS TO HOW IT HAS BEEN DETERMINED
 THAT THIS CONDITION CURRENTLY EXISTS AND HOW IT CAN BE
 GUARANTEED THAT THE CONDITIONS IN THE UNIT BELOW WILL
 NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 2. FBC 1207.3, FLOOR/CEILING ASSEMBLIES BETWEEN
 DWELLING UNITS OR BETWEEN A DWELLING UNIT AND A PUBLIC
 OR SERVICE AREA WITHIN THE STRUCTURE SHALL HAVE AN
 IMPACT INSULATION CLASS (IIC) RATING OF NOT LESS THAN
 50 (45 IF FIELD TESTED) WHEN TESTED IN ACCORDANCE WITH
 ASTM E 492. IF A SUSPENDED CEILING WAS USED AS A PART
 OF THE TEST, PROVIDE INFORMATION AS TO HOW IT HAS BEEN
 DETERMINED THAT THIS CONDITION CURRENTLY EXISTS AND HOW
 IT CAN BE GUARANTEED THAT THE CONDITIONS IN THE UNIT
 BELOW WILL NOT BE ALTERED.
  
 PLEASE PROVIDE A COPY OF THE TEST REPORT.
  
 3. FBC 603.1, ALLOWABLE MATERIALS IN NON COMBUSTIBLE
 BUILDINGS, SEE ITEM 2, EXCEPTION 2, ACOUSTICAL
 INSULATION INSTALLED BETWEEN A FINISHED FLOOR AND SOLID
 DECKING WITHOUT INTERVENING AIRSPACE SHALL BE ALLOWED
 TO HAVE A FLAME SPREAD INDEX OF NOT MORE THAN 200.
  
 SEE 803.1.1, PROVIDE TEST DATA IN ACCORDANCE WITH ASTM
 E 84 OR UL 723.
  


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved