Plan Review Notes
Plan Review Notes For Permit 16110418
Permit Number 16110418
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2016-12-02 12:26:35501 FERN STREET SUITE C OR #102
 TRACKING #16110418
 PERMIT #16070199
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PLANS INDICATE THE WORK IS BEING PERFORMED IN SUITE
 #102; HOWEVER, THE ORIGINAL PERMIT APPLICATION
 (16070199) INDICATES THE WORK IS BEING PERFORMED IN
 SUITE C. THE ORIGINAL PERMIT APPLICATION NEEDS TO BE
 CORRECTED IF SUITE C IS NO LONGER IN THE SCOPE OF WORK.
  
 THE RESPONSE LETTER INDICATES THE JOB SCOPE OF WORK WAS
 REDUCED FROM 45 SPRINKLERS TO 14; HOWEVER, NO REVISED
 PLANS FOR SUITE C HAVE BEEN SUBMITTED INDICATING THESE
 45 HEADS ARE NOT BEING INSTALLED/MODIFIED.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE