2016-11-10 13:01:25 | 501 FERN STREET SUITE C OR #102 | | TRACKING #16110418 | | PERMIT #16070199 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | THE PERMIT APPLICATION INDICATES A PLAN REVISION; | | HOWEVER, NO INCREASE IN PERMIT VALUE HAS BEEN PROVIDED | | SUPPORTING THE ADDITION OF 14 NEW SPRINKLERS. | | | | THE ORIGINAL SPRINKLER PERMIT (13110269) HAD A SCOPE OF | | WORK FOR 45 SPRINKLERS. THE REVISED PLANS SHOW AN | | ADDITIONAL 14 SPRINKLERS, PUSHING THE TOTAL SPRINKLERS | | TO MORE THAN 50. PLANS ARE REQUIRED TO BE SIGNED AND | | SEALED BY A PROFESSIONAL ENGINEER PER STATE STATUTE. | | | | THE PLANS INDICATE THE WORK IS BEING PERFORMED IN SUITE | | C; HOWEVER, THE MASTER PERMIT (16071099) INDICATES THIS | | IS SUITE 102. | | | | PLAN INFORMATION IS INACCURATE. PLANS INDICATE THE 2007 | | EDITION OF NFPA 13 AND INDICATE A SCOPE OF WORK IN THE | | SPRINKLER SCHEDULE AS 36 NEW SPRINKLERS. | | | | WESLEY JOLIN | | ASSISTANT FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | |
|