Plan Review Notes
Plan Review Notes For Permit 16110418
Permit Number 16110418
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2016-11-10 13:01:25501 FERN STREET SUITE C OR #102
 TRACKING #16110418
 PERMIT #16070199
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 THE PERMIT APPLICATION INDICATES A PLAN REVISION;
 HOWEVER, NO INCREASE IN PERMIT VALUE HAS BEEN PROVIDED
 SUPPORTING THE ADDITION OF 14 NEW SPRINKLERS.
  
 THE ORIGINAL SPRINKLER PERMIT (13110269) HAD A SCOPE OF
 WORK FOR 45 SPRINKLERS. THE REVISED PLANS SHOW AN
 ADDITIONAL 14 SPRINKLERS, PUSHING THE TOTAL SPRINKLERS
 TO MORE THAN 50. PLANS ARE REQUIRED TO BE SIGNED AND
 SEALED BY A PROFESSIONAL ENGINEER PER STATE STATUTE.
  
 THE PLANS INDICATE THE WORK IS BEING PERFORMED IN SUITE
 C; HOWEVER, THE MASTER PERMIT (16071099) INDICATES THIS
 IS SUITE 102.
  
 PLAN INFORMATION IS INACCURATE. PLANS INDICATE THE 2007
 EDITION OF NFPA 13 AND INDICATE A SCOPE OF WORK IN THE
 SPRINKLER SCHEDULE AS 36 NEW SPRINKLERS.
  
 WESLEY JOLIN
 ASSISTANT FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE