2016-11-08 14:15:43CITY OF WEST PALM BEACH LOCAL AMENDMENTS TO THE FLORIDA
 BUILDING CODE (FBC) 2010 CHAPTER 1 ADMINISTRATION
  
 107.1 GENERAL ? 107.2 CONSTRUCTION DOCUMENTS ? 107.2.1
 INFORMATION ON CONSTRUCTION DOCUMENTS
  
 AS PER DAIKIN SPECIFICATIONS THE RATED CFM OUTPUT AT .1
 FRICTION LOST FOR DV24PVCC14 IS 700 CFM. MAXIMUM OUTPUT
 AT .1 FRICTION LOST IS 770 CFM. AS PER YOUR SUBMITTED
 PLANS THE FIRST FLOOR TOTAL SUPPLY OUTLET CFM OUTPUT IS
 500 CFM. AS PER YOUR SUBMITTED PLANS THE SECOND FLOOR
 TOTAL SUPPLY OUTLET CFM OUTPUT IS 575 CFM.
  
 (1) PROVIDE PROPER SUPPLY AIR OUTLET CFM DISTRIBUTION
 BALANCE AS PER RATED CFM MANUFACTURER SPECIFICATIONS.
  
 FLORIDA ENERGY CODE FBC 2014
  
 JORGE VALIDO
 WPB MECHANICAL INSPECTOR/PLANS EXAMINER