Plan Review Notes For Permit 16110282 |
Permit Number |
16110282 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-17 12:51:18 | 1ST REVIEW 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] ARCHITECT MUST DATE, SIGN & SEAL AS REQUIRED FOR THE | | PERSON RESPONSIBLE FOR THE DRAWING. FAC 61G1-16.001 | | | | 2] PROVIDE AN ELECTRICAL SCOPE OF WORK & APPLICABLE | | CODES ON THE DRAWING IN ACCORDANCE WITH WPB CITY | | AMENDMENTS FBC 107.2.1 | | | | 3] SHOW AN ELECTRICAL DETAIL OF ANY EXTENSION FOR THE | | COLUMN LIGHT FIXTURES, INCLUDE WIRE & CONDUIT SIZES. | | FBC 107.3.5.3 |
|