2016-11-16 15:04:321ST REVIEW 2014 5TH FBC ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  
  
 1] NEC 600.5 SIGN OUTLET SHALL BE SUPPLIED BY A
 MINNIMUM DEDICATED 20 AMP BRANCH CIRCUIT, IF AN
 EXISTING CIRCUIT IS TO BE USED PLEASE ADD A NOTE ON THE
 PLANS.
  
 2] THE STATED VALUATION OF $1,000 IS TOO LOW FOR THE
 PROPOSED SIGN. THE PERMIT VALUATION AND PERMIT FEE MUST
 COMMENSURATE WITH THE VALUATION AND FEE THAT A LICENSED
 CONTRACTOR WOULD PROVIDE. PLEASE INCREASE THE VALUATION
 ACCORDINGLY AND PROVIDE AN OWNER SIGNED CONTRACT FOR
 VERIFICATION. FBC-109
  
  