Plan Review Notes
Plan Review Notes For Permit 16110249
Permit Number 16110249
Review Stop B
Sequence Number 1
Notes
Date Text
2016-11-30 15:56:10BUILDING PLAN REVIEW
 W. P. B. PERMIT: 16110249 FOUNDATION/ AUGER CAST PILE/
 PILE CAPS
 ADD: 3611 S. FLAGLER DR.
 CONT: JOHN ROSSI CONSTRUCTION
 TEL: 561-659-5505
 E-MAIL: [email protected]
  
 FOUNDATION PERMIT: 2014 FLORIDA BUILDING CODE W 2014
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION 107.3.3 PHASED
 APPROVAL. THE BUILDING OFFICIAL IS AUTHORIZED TO ISSUE
 A PERMIT FOR THE CONSTRUCTION OF BEFORE THE
 CONSTRUCTION DOCUMENTS FOR THE WHOLE BUILDING OR
 STRUCTURE HAVE BEEN SUBMITTED, PROVIDED THAT ADEQUATE
 INFORMATION AND DETAILED STATEMENTS HAVE BEEN FILED
 COMPLYING WITH PERTINENT REQUIREMENTS OF THIS CODE. THE
 HOLDER OF SUCH PERMIT FOR THE FOUNDATION OR OTHER PARTS
 OF A BUILDING OR STRUCTURE SHALL PROCEED AT THE
 HOLDER?S OWN RISK WITH THE BUILDING OPERATION AND
 WITHOUT ASSURANCE THAT A PERMIT FOR THE ENTIRE
 STRUCTURE WILL BE GRANTED.
  
 1ST REVIEW
 DATE: WED. NOV. 30/2016
 ACTION: DENIED
  
 1A) TO DATE ONLY A FOUNDATION PERMIT HAS BEEN APPLIED
 FOR, THERE ARE NO DRAWINGS IN THIS SUBMITTAL INDICATING
 THE BUILDING CODE ANALYSIS FOR THE BUILDING,
 CONSTRUCTION TYPE, SQUARE FOOTAGE PER FLOOR, FLOOR
 PLANS/ ROOF PLAN, LIFE SAFETY PLANS PER FLOOR, AND
 ELEVATIONS. ADMINISTRATION 107.3.3 PHASED APPROVAL. THE
 BUILDING OFFICIAL IS AUTHORIZED TO ISSUE A PERMIT FOR
 THE CONSTRUCTION OF BEFORE THE CONSTRUCTION DOCUMENTS
 FOR THE WHOLE BUILDING OR STRUCTURE HAVE BEEN
 SUBMITTED, PROVIDED THAT ADEQUATE INFORMATION AND
 DETAILED STATEMENTS HAVE BEEN FILED COMPLYING WITH
 PERTINENT REQUIREMENTS OF THIS CODE.
  
 1B) ART IN PUBLIC PLACES. THE CITY OF WEST PALM BEACH
 ART IN PUBLIC PLACES ORDINANCE REQUIREMENT THAT APPLIES
 TO ANY REMODEL OR NEW CONSTRUCTION PROJECT FOR WHICH
 THE PERMIT APPLICATION WAS SUBMITTED AFTER 6/29/14, AND
 THE TOTAL PROJECT CONSTRUCTION COSTS ARE EQUAL TO OR
 GREATER THAN $750,000 WILL NEED TO COMPLY WITH THIS
 ORDINANCE.
 PER CITY OF WEST PALM BEACH ORDINANCE NO. 4504-14, AND
 CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE V,
 ART IN PUBLIC PLACES, SECTION 78-123(A) AND SECTION
 78-126(A), THE ART ASSESSMENT IS 1% OF THE TOTAL
 PROJECT CONSTRUCTION COST.
 PER CITY OF WEST PALM BEACH CODE OF ORDINANCES, ARTICLE
 V, ART IN PUBLIC PLACES, SECTION 78-122, RENOVATION AND
 NEW CONSTRUCTION PROJECTS ARE ASSESSED CUMULATIVELY, SO
 THE ART ASSESSMENT WILL BE APPLICABLE TO ALL FUTURE
 PROJECTS.
 FOR CONTACT INFORMATION PLEASE CONTACT:
 MS. SYBILLE WELTER ART IN PUBLIC PLACES COORDINATOR
 822-1515 E-MAIL: [email protected]
  
 2) THIS BUILDING BEING A 6 STORY BUILDING QUALIFIES AS
 A THRESHOLD BUILDING / FL S. S. 553.71(7) ?THRESHOLD
 BUILDING" MEANING ANY BUILDING WHICH IS GREATER THAN
 (3) STORIES OR 50 FT. IN HEIGHT, OR WHICH HAS AN
 ASSEMBLY OCCUPANCY CLASSIFICATION AS DENIED IN THE
 FLORIDA BUILDING CODE WHICH EXCEEDS 5,000 SQ. FT. IN
 AREA AND AN OCCUPANT CONTENT OF GREATER THAN 500
 PERSONS.
  
 2A) 109.3.6.1 THRESHOLD INSPECTION PLAN. THE ENFORCING
 AGENCY SHALL REQUIRE A (WRITTEN/ TYPED) SPECIAL
 INSPECTOR TO PERFORM STRUCTURAL INSPECTIONS ON A
 THRESHOLD BUILDING PURSUANT TO A STRUCTURAL INSPECTION
 PLAN PREPARED BY THE ENGINEER OF RECORD. THE STRUCTURAL
 INSPECTION PLAN MUST BE SUBMITTED TO THE ENFORCING
 AGENCY PRIOR TO THE ISSUANCE OF A BUILDING PERMIT FOR
 THE CONSTRUCTION OF A THRESHOLD BUILDING. THE PURPOSE
 OF THE STRUCTURAL INSPECTION PLAN IS TO PROVIDE
 SPECIFIC INSPECTION PROCEDURES AND SCHEDULES SO THAT
 THE BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE
 WITH THE PERMITTED DOCUMENTS.
  
 2B) THRESHOLD INSPECTOR: WPB AMENDMENT 109.3.6.2 W.P.B.
 CONSTRUCTION SERVICES DEPARTMENT REQUEST FOR THRESHOLD
 BUILDINGS A SPECIAL INSPECTOR AS REQUIRED BY FL S
 553.79(5) FLORIDA STATUTES TO THE MINIMUM INSPECTIONS
 REQUIRED BY THIS CODE. THE THRESHOLD INSPECTION FORMS
 ARE REQUIRED TO BE FILED OUT BY ALL PARTIES WITH
 INTEREST, NOTARIZED AND RETURNED TO THIS OFFICE, AND
 REVIEWED AND APPROVED BEFORE PERMIT ISSUANCE WILL TAKE
 PLACE.
 FORMS E-MAILED TO: [email protected] 11/30/16
 12:22 PM.
  
  
 2C) THRESHOLD BLDG., REQUIRED STATEMENT: W.P.B.
 AMENDMENT 110.3.7.4.4 ALL PLANS FOR THE BUILDING WHICH
 ARE REQUIRED TO BE SIGNED AND SEALED BY THE ARCHITECT
 OR ENGINEER OF RECORD CONTAIN A STATEMENT THAT, TO THE
 BEST OF THE ARCHITECT'S OR ENGINEER'S KNOWLEDGE, THE
 PLANS AND SPECIFICATIONS COMPLY WITH THE APPLICABLE
 FIRE-SAFETY STANDARDS AS DETERMINED BY THE LOCAL
 AUTHORITY IN ACCORDANCE WITH THIS SECTION AND 633
 FLORIDA STATUTE.
  
 2D) FOR THE SPECIAL INSPECTOR PLEASE PROVIDE A RESUME'
 OF INSPECTION EXPERIENCE ON PREVIOUS PROJECT. THE
 RESUME' MUST BE ACCOMPANIED BY ALL CERTIFICATES AS
 SPECIFIED HEREIN. THE BUILDING OFFICIAL OR HIS DESIGNEE
 WILL REVIEW THE RESUME'. AFTER THE RESUME' IS REVIEWED,
 AN INTERVIEW WILL BE SCHEDULED. UNDER NO CIRCUMSTANCES
 WILL AN INSPECTOR BE INTERVIEWED FOR WORK WITHOUT FIRST
 MEETING THE ABOVE CRITERIA.
  
 2E) THE CONTRACTOR WILL PRODUCE A JOB SUMMARY OR
 HISTORY FOR THIS TYPE OF CONSTRUCTION.
  
 2F) NOTE FOR PAPER PLANS 3 SETS OF DOCUMENTS ARE
 REQUIRED. FOR DIGITAL PLANS, AFTER PERMIT ISSUANCE,
 PLEASE E-MAIL THE PERMIT LIBRARIAN OF THE PERMIT BEING
 ISSUED, THE PERMIT LIBRARIAN WILL THEN E-MAIL YOU THE
 APPROVED AND BATCH STAMPED PLANS SO YOU MAY PRINT YOUR
 PLANS, TWO SETS OF PLANS WILL NEED TO BE PRINTED IN
 COLOR, (1) FOR THE THRESHOLD INSPECTOR, THE OTHER FOR
 THE MEP INSPECTORS OTHER PLANS YOU WISH TO PRINT MAYBE
 IN BLACK & WHITE..
 2010 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION, 110.3.7 THRESHOLD
 BUILDINGS, GUIDELINES AND POLICIES FOR PROJECTS
 CONCERNING SPECIAL INSPECTORS.
  
 2G) 110.3.7.4.3 ALL SHORING AND RESHORING PROCEDURES,
 PLANS AND DETAILS SHALL BE SUBMITTED TO THE ENFORCEMENT
 AGENCY FOR RECORDKEEPING. EACH SHORING AND RESHORING
 INSTALLATION SHALL BE SUPERVISED, INSPECTED AND
 CERTIFIED TO BE IN COMPLIANCE WITH THE SHORING
 DOCUMENTS BY THE CONTRACTOR.
  
 2H) PLEASE CALL THE CITY OF WEST PALM BEACH?S AUTOMATED
 TELEPHONE INSPECTIONS LINE (561) 805-6700) FOR ALL
 BUILDING INSPECTIONS FOR AUDITING OF JOBSITE
 INSPECTIONS WITHOUT THIS THE PERMIT EXPIRES IN 6
 MONTHS, ABANDONMENT OF JOB, NO INSPECTION ACTIVITY.
  
 2I) 109.3.6 THRESHOLD BUILDINGS, OPERATING GUIDELINES
 FOR THRESHOLD INSPECTORS #26. ASSURE THAT THE DESIGNER
 HAS REQUIRED ON THE PLANS OR SPECIFICATIONS ONE
 MATERIAL, APPROVED FOR FIRE STOPPING PENETRATIONS, FOR
 WALLS AND CEILINGS.
  
 3) THIS PROPERTY IS LOCATED IN A FLOOD ZONE. FBC
 BUILDING 1612 AND CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A5" FLOOD
 ZONE WITH THE BASE FLOOD ELEVATION OF 7.0 FT. NGVD. A
 FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED. PLEASE
 REVIEW CITY ORDINANCE FOR THE CITY REQUIREMENTS REQUIRE
 AN ADDITIONAL (1) FOOT FINISH FLOOR OF ELEVATION OR A
 MINIMUM OF 8.0 FT. NGVD. PLEASE NOTE SHEET C-1 SHOWS A
 FINISH FLOOR ELEVATION OF 8.0 FT. NGVD. WITH
 CONSTRUCTION TOLERANCES AND THE EXPECTED SETTLEMENT
 EVALUATION GIVEN IN THE SOILS REPORT SUBMITTED BY
 NUTTING ENGINEERS THE FINISH FLOOR ELEVATION NEEDS TO
 BE RE-EVALUATED. PLEASE NOTE PLANS SUBMITTED FOR PERMIT
 AFTER SEPT. 12/ 2016 WILL REQUIRE A 1.0 FOOT FREEBOARD.
 ORDINANCE NO. 4658-16, ARTICLE XVII, SECTION 94-546(2)
 NONRESIDENTIAL CONSTRUCTION.
  
 DURING THE PERMITTING OF THIS STRUCTURE THERE WILL BE
 REQUIRED (3) DIFFERENT FLOOD ZONE CERTIFICATES
 REQUIRED:
 (3.1) (CONSTRUCTION DRAWINGS)A FLOOD ZONE CERTIFICATE
 IS REQUIRED AS PART OF THE PLAN REVIEW DOCUMENTS WITH
 THE PROPOSED FINISH FLOOR HEIGHT.
 (3.2) ONCE THE FIRST FLOOR SLAB IS POURED THE 2ND
 ELEVATION CERTIFICATE IS REQUIRED.
 W. P. B. ADMINISTRATIVE CODE 110.3.1.2. IN FLOOD HAZARD
 AREAS, UPON PLACEMENT OF THE LOWEST FLOOR, INCLUDING
 BASEMENT, AND PRIOR TO FURTHER VERTICAL CONSTRUCTION,
 THE ELEVATION CERTIFICATION, REQUIRED IN SECTION
 1612.5, SHALL BE SUBMITTED TO THE BUILDING OFFICIAL.
  
 (3.3) BEFORE THE ISSUANCE OF A CERTIFICATE OF OCCUPANCY
 OR A CERTIFICATE OF COMPLETION THE 3RD FLOOD ZONE
 CERTIFICATE IS REQUIRED WITH THE HEIGHT OF ALL EXTERIOR
 ATTENDANTS.
 W. P. B. ADMIN. CODE 110.3. 6. FINAL INSPECTION. TO BE
 MADE AFTER THE BUILDING IS COMPLETED AND READY FOR
 OCCUPANCY. 6.1. LOWEST FLOOR ELEVATION. IN FLOOD HAZARD
 AREAS, AS PART OF THE FINAL INSPECTION, A FINAL
 CERTIFICATION OF THE LOWEST FLOOR ELEVATION SHALL BE
 SUBMITTED TO THE AUTHORITY HAVING JURISDICTION.
 A/C PADS OR OTHER SLABS FOR GENERATORS.
  
 FEMA NEW FORM AVAILABLE JUNE 13/2016.
 OMB NO. 1660-0008
 EXPIRATION DATE: NOV. 30/2018
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 4) SHEET S-01:
 4A) PLEASE MAKE CORRECTIONS TO WIND DESIGN CRITERIA,
 PLANS INDICATE ASCE 07-02 2004 FBC W/ 2007 SUPPLEMENTS.
 THE CURRENT STATEWIDE CODE IS 2014 FBC-B & ASCE 7-10/
 VULT 170 OR VASD 132 MPH, SEE FIGURE 1609A.
  
 4B) COMPONENTS AND CLADDING AGAIN ASCE 7-02. THE
 CURRENT STATEWIDE CODE IS 2014 FBC-B & ASCE 7-10/ VULT
 170 OR VASD 132 MPH, SEE FIGURE 1609A.
  
 4C) THE EXPOSURE IS GIVEN AS AN C EXPOSURE. PLEASE
 CORRECT TO AN D EXPOSURE. 2014 FBC-B 1609.4.2 EXPOSURE
 D. EXPOSURE D SHALL APPLY WHERE THE GROUND SURFACE
 ROUGHNESS, AS DEFINED BY SURFACE ROUGHNESS D, PREVAILS
 IN THE UPWIND DIRECTION FOR A DISTANCE OF AT LEAST
 5,000 FEET (1524 M) OR 20 TIMES THE HEIGHT OF THE
 BUILDING, WHICHEVER IS GREATER. EXPOSURE D SHALL ALSO
 APPLY WHERE THE GROUND SURFACE ROUGHNESS IMMEDIATELY
 UPWIND OF THE SITE IS B OR C, AND THE SITE IS WITHIN A
 DISTANCE OF 600 FEET (183 M) OR 20 TIMES THE BUILDING
 HEIGHT, WHICHEVER IS GREATER, FROM AN EXPOSURE D
 CONDITION AS DEFINED IN THE PREVIOUS SENTENCE. WHEN A
 VECTOR IS SENT TO THE NNE & SSE IN BOTH DIRECTIONS IT
 IS OVER 5000 FEET OF WATER AND THE SHORELINE DIRECTLY
 IN FRONT OF THE PROPERTY IN THE SAME VECTOR TO THE NNE
 & SSE IS LESS THAN 600 FEET.
  
 4D) THE MEAN ROOF HEIGHT GIVEN ON THE PLANS IS
 INDICATED AS +512 FEET. PLEASE UPDATE PLANS. 107.2.1.3
 ADDITIONAL INFORMATION IS REQUIRED.
  
 5) TO DATE WE HAVE NO COMPANY SIGNED ON TO OVERSEE THE
 AUGER CAST PILE OR TEST PILE. FBC-B 1803.4 QUALIFIED
 REPRESENTATIVE. 2014 FLORIDA BUILDING CODE W * 2010
 WEST PALM BEACH AMENDMENTS TO THE FLORIDA BUILDING
 CODE, CHAPTER 1, ADMINISTRATION SECTION 117 TESTS. THE
 BUILDING OFFICIAL MAY REQUIRE TESTS OR TEST REPORTS AS
 PROOF OF COMPLIANCE. REQUIRED TESTS ARE TO BE MADE AT
 THE EXPENSE OF THE OWNER, OR AGENT, BY AN APPROVED
 TESTING LABORATORY OR OTHER APPROVED AGENCY. PLEASE
 ALSO PROVIDE DOCUMENTATION OF WHAT SOILS ENGINEERING
 FIRM WILL BE CONTRACTED WITH FOR THE RECORDING AND
 MONITORING OF BOTH THE TEST PILE AS WELL AS THE
 PRODUCTION PILE. 2014 FBC-B 1810.3.3.1.2 LOAD TESTS.
 1810.3.3.1.4 ALLOWABLE FRICTIONAL RESISTANCE.
 1810.3.3.1.5 UPLIFT CAPACITY OF A SINGLE DEEP
 FOUNDATION (SINGLE) ELEMENT. 1810.3.3.1.6 UPLIFT
 CAPACITY OF GROUPED DEEP FOUNDATION (GROUP) ELEMENTS.
  
 6) PLEASE SHOW HOW SLOPE LIMITS WILL BE ACHIEVED. 2014
 FBC-B 3304.1.1 SLOPE LIMITS. SLOPES FOR PERMANENT FILL
 SHALL NOT BE STEEPER THAN ONE UNIT VERTICAL IN TWO
 UNITS HORIZONTAL (50-PERCENT SLOPE). CUT SLOPES FOR
 PERMANENT EXCAVATIONS SHALL NOT BE STEEPER THAN ONE
 UNIT VERTICAL IN TWO UNITS HORIZONTAL (50-PERCENT
 SLOPE). DEVIATION FROM THE FOREGOING LIMITATIONS FOR
 CUT SLOPES SHALL BE PERMITTED ONLY UPON THE
 PRESENTATION OF A SOIL INVESTIGATION REPORT ACCEPTABLE
 TO THE BUILDING OFFICIAL.
  
 7) WHEN EXCAVATING WILL THE EXCESS SOILS BE STORED ON
 SITE? 2014 FBC-B 3304.1.2 SURCHARGE. NO FILL OR OTHER
 SURCHARGE LOADS SHALL BE PLACED ADJACENT TO ANY
 BUILDING OR STRUCTURE UNLESS SUCH BUILDING OR STRUCTURE
 IS CAPABLE OF WITHSTANDING THE ADDITIONAL LOADS CAUSED
 BY THE FILL OR SURCHARGE. EXISTING FOOTINGS OR
 FOUNDATIONS WHICH CAN BE AFFECTED BY ANY EXCAVATION
 SHALL BE UNDERPINNED ADEQUATELY OR OTHERWISE PROTECTED
 AGAINST SETTLEMENT AND SHALL BE PROTECTED AGAINST LATER
 MOVEMENT.
  
 8) PLEASE PROVIDE COMPLIANCE WITH: POLLUTION PREVENTION
 PLAN. 2014 FBC-B 3307.1 PROTECTION REQUIRED. ADJOINING
 PUBLIC AND PRIVATE PROPERTY SHALL BE PROTECTED FROM
 DAMAGE DURING CONSTRUCTION, REMODELING AND DEMOLITION
 WORK. PROVISIONS SHALL BE MADE TO CONTROL WATER RUNOFF
 AND EROSION DURING CONSTRUCTION OR DEMOLITION
 ACTIVITIES. THE PERSON MAKING OR CAUSING AN EXCAVATION
 TO BE MADE SHALL PROVIDE WRITTEN NOTICE TO THE OWNERS
 OF ADJOINING BUILDINGS ADVISING THEM THAT THE
 EXCAVATION IS TO BE MADE AND THAT THE ADJOINING
 BUILDINGS SHOULD BE PROTECTED. SAID NOTIFICATION SHALL
 BE DELIVERED NOT LESS THAN 10 DAYS PRIOR TO THE
 SCHEDULED STARTING DATE OF THE EXCAVATION.
 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 109.3.10 IMPACT OF CONSTRUCTION. ALL
 CONSTRUCTION ACTIVITY REGULATED BY THIS CODE SHALL BE
 PERFORMED IN A MANNER SO AS NOT TO ADVERSELY IMPACT THE
 CONDITION OF ADJACENT PROPERTY, UNLESS SUCH ACTIVITY IS
 PERMITTED TO AFFECT SAID PROPERTY PURSUANT TO CONSENT
 BY THE APPLICABLE PROPERTY OWNER, UNDER TERMS &
 CONDITIONS AGREEABLE TO THE APPLICABLE PROPERTY OWNER.
 THIS INCLUDES BUT IS NOT LIMITED TO THE CONTROL OF
 DUST, NOISE, WATER OR DRAINAGE RUN-OFF, DEBRIS, AND THE
 STORAGE OF CONSTRUCTION MATERIALS. NEW CONSTRUCTION
 ACTIVITY SHALL NOT ADVERSELY IMPACT HISTORIC SURFACE
 WATER DRAINAGE FLOWS SERVING ADJACENT PROPERTIES, & MAY
 REQUIRE SPECIAL DRAINAGE DESIGN COMPLYING WITH
 ENGINEERING STANDARDS TO PRESERVE THE POSITIVE PATTERNS
 OF THE AFFECTED SITES. ACCORDINGLY, DEVELOPERS,
 CONTRACTORS, AND OWNERS OF ALL NEW RESIDENTIAL
 DEVELOPMENT, INCLUDING ADDITIONS, POOLS, PATIOS,
 DRIVEWAYS, DECKS, OR SIMILAR ITEMS, ON EXISTING
 PROPERTIES RESULTING IN A DECREASE IN EXCESS OF 800SQ.
 FT. OF PERMEABLE LAND AREA ON ANY PARCEL SHALL AS A
 PERMIT CONDITION, PROVIDE A PROFESSIONALLY PREPARED
 DRAINAGE PLAN CLEARLY INDICATING COMPLIANCE WITH THIS
 PARAGRAPH. UPON COMPLETION OF THE IMPROVEMENT, A
 CERTIFICATION FROM A LICENSED ENGINEER SHALL BE
 SUBMITTED TO THE INSPECTOR IN ORDER TO RECEIVE APPROVAL
 OF THE FINAL INSPECTION.
  
 9) PLEASE PROVIDE COMPLIANCE WITH: 2014 FBC-B 3303.5
 WATER ACCUMULATION. PROVISION SHALL BE MADE TO PREVENT
 THE ACCUMULATION OF WATER OR DAMAGE TO ANY FOUNDATIONS
 ON THE PREMISES OR THE ADJOINING PROPERTY.
  
 10) 2014 FBC-B 3306.9 ADJACENT TO EXCAVATIONS. EVERY
 EXCAVATION ON A SITE LOCATED 5 FEET (1524 MM) OR LESS
 FROM THE STREET LOT LINE SHALL BE ENCLOSED WITH A
 BARRIER NOT LESS THAN 6 FEET (1829 MM) HIGH. WHERE
 LOCATED MORE THAN 5 FEET (1524 MM) FROM THE STREET LOT
 LINE, A BARRIER SHALL BE ERECTED WHEN REQUIRED BY THE
 BUILDING OFFICIAL. BARRIERS SHALL BE OF ADEQUATE
 STRENGTH TO RESIST WIND PRESSURE AS SPECIFIED IN
 CHAPTER 16.
  
 11) PERIMETER FENCING UNDER A SEPARATE PERMIT. PLEASE
 PROVIDE COMPLIANCE WITH: 2014 FBC-B 3306.5 BARRIERS.
 BARRIERS SHALL BE A MINIMUM OF 8 FEET (2438 MM) IN
 HEIGHT AND SHALL BE PLACED ON THE SIDE OF THE WALKWAY
 NEAREST THE CONSTRUCTION. BARRIERS SHALL EXTEND THE
 ENTIRE LENGTH OF THE CONSTRUCTION SITE.
  
 12) 2014 FLORIDA BUILDING CODE W 2014 WEST PALM BEACH
 AMENDMENTS TO THE FLORIDA BUILDING CODE, CHAPTER 1,
 ADMINISTRATION 109.3.10.1 HURRICANE PROTECTION. IT
 SHALL BE UNLAWFUL FOR ANY PERSON TO ALLOW CONSTRUCTION
 RELATED MATERIALS EQUIPMENT AND DEBRIS TO REMAIN LOOSE
 OR OTHERWISE UNSECURED AT A CONSTRUCTION SITE FROM 24
 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED UNTIL THE
 HURRICANE WATCH OR WARNING HAS BEEN LIFTED. ALL SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS SHALL BE
 EITHER REMOVED FROM THE CONSTRUCTION SITE OR SECURED IN
 SUCH A MANNER AS TO MINIMIZE THE DANGER OF SUCH
 CONSTRUCTION MATERIALS, EQUIPMENT AND DEBRIS CAUSING
 DAMAGE TO PERSONS OR PROPERTY FROM HIGH WINDS. ANY
 PERSONS WHO FAILS TO COMPLY TO COMPLY TO REMOVE OR
 SECURE THE CONSTRUCTION MATERIALS EQUIPMENT AND DEBRIS
 WITHIN 24 HRS. AFTER A HURRICANE WATCH HAS BEEN ISSUED
 SHALL BE SUBJECT TO A FINE NOT TO EXCEED $500.00. IN
 ADDITION TO THE ABOVE, A LICENSED CONTRACTOR WHO
 VIOLATES THIS SECTION SHALL BE SUBJECT TO DISCIPLINE
 PURSUANT TO SECTION 113 OF THIS CHAPTER.
  
 13) ALL CONSTRUCTION TRAILERS (MOBILE OR MODULAR
 BUILDINGS) THAT ARE GOING TO HAVE MEETING IN THEM WILL
 BE REQUIRED TO GET A PERMIT, 102.2( E ) MOBILE OR
 MODULAR STRUCTURES USED AS TEMPORARY OFFICES, EXCEPT
 THAT THE PROVISIONS OF PART V (SECTION 553.501-553.513,
 FLORIDA STATUTES) RELATING TO ACCESSIBILITY BY PERSONS
 WITH DISABILITIES, AND PERMITS SHALL BE REQUIRED FOR
 STRUCTURAL SUPPORT AND TIE DOWN, ELECTRICAL SUPPLY, AND
 ALL UTILITY CONNECTIONS TO SUCH MOBILE OR MODULAR
 STRUCTURES.
  
 14) DEPENDING ON THE SIZE OF THE CONSTRUCTION TRAILERS,
 CLOSENESS TO BUILDINGS AND OR OTHER CONSTRUCTION
 TRAILERS THE FIRE DEPARTMENT THROUGH THE FIRE
 PREVENTION CODE MAY REQUIRE FIRE SPRINKLERS.
  
 15) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 16) WHEN RESUBMITTING PLANS PLEASE INDICATE THE
 REVISION & REMOVE ANY VOIDED SHEETS & REPLACE ANY PAGES
 AS NECESSARY. A TRANSMITTAL LETTER LISTING THE ORIGINAL
 REVIEW COMMENT NUMBER, WITH A DESCRIPTION OF THE
 REVISION MADE, IDENTIFYING THE SHEET OR SPECIFICATION
 PAGE WHERE THE CHANGES CAN BE FOUND WILL HELP TO
 EXPEDITE YOUR PERMIT. THANK YOU FOR YOUR ANTICIPATED
 COOPERATION.
  
 A THOROUGH REVIEW CANNOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
  
  
  
  