2016-11-14 11:29:141ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110230
 11/14/16
  
 1) THE 18X18" RETURN GRILL IS UNDERSIZED PER SECTION
 601.5- 600 SQ. INCHES REQUIRED.
  
 2) REFER TO SECTION C403.2.7.2 FBC-14 ENERGY
 CONSERVATION: THE MECHANICAL CLOSET SHALL BE CONSIDERED
 A "PLENUM CHAMBER" AND MUST BE CONSTRUCTED IN
 ACCORDANCE WITH SECTION 602.1. PLEASE VERIFY
 COMPLIANCE.
  
 3) THE BMP CLIP SUBMITTAL HAS A COPIED ENGINEER'S
 SIGNATURE AND SEAL WHICH IS NOT ACCEPTABLE PER SECTION
 61G15-23.002 FLORIDA ADMINISTRATIVE CODE. PROVIDE SITE
 SPECIFIC WIND LOAD ENGINEERING DESIGNED BY A FL.
 LICENSED ENGINEER- SEE SECTION 301.15 FBC-14
 MECHANICAL, AND SECTION 1609 FBC-14 BUILDING.
  