2017-02-22 12:36:19 | 5TH REVIEW FBC-2014 MECHANICAL |
| PERMIT #16110180 |
| 1/22/17 |
| |
| 1) 4TH REQUEST FOR EXHAUST VENTILATION CALCULATIONS: |
| THE REQUESTED EXHAUST VENTILATION CALCULATIONS FOR THE |
| DOG AREA AND THE OVERNIGHT DOG PLAY AREA HAVE NOT BEEN |
| PROVIDED AS REQUIRED BY TABLE 403.3. CALCULATIONS BASED |
| ON THE SCALE SHOWN ON THE PLAN INDICATE 666 CFMS OF |
| EXHAUST REQUIRED FOR THE DOG AREA AND 683 CFMS FOR THE |
| OVERNIGHT DOG PLAY AREA. THE EF-1 FANS AT 110 CFMS |
| CAPACITY ARE ONLY PROVIDING 220 CFMS OF EXHAUST AT EACH |
| OF THESE ROOMS INDICATING INCREASED VENTILATION MUST BE |
| PROVIDED- SEE TABLE 403.3. |
| |
| 2) 4TH REQUEST FOR COMPLETE EXHAUST SYSTEM DRAWINGS: |
| THE REQUESTED DETAILS FOR THE EXHAUST SYSTEMS IN THE |
| DOG AREA AND OVERNIGHT DOG PLAY AREA HAVE NOT BEEN |
| PROVIDED. |
| |
| 2) PLEASE LABEL THE NEW EXHAUST AND SUPPLY FANS IN THE |
| INDOOR DOG PLAY AREA AND PROVIDE EQUIPMENT SCHEDULES. |
| |
| 3) REFER TO TABLE 403.3 AND PROVIDE AN O/A CALCULATION |
| FOR THE INDOOR PLAY AREA AND SHOW HOW O/A WILL BE |
| PROVIDED TO THE AREAS. CORRECT THE NOTE IN THE AIR |
| BALANCE CALCULATION THAT STATES "NO FRESH AIR THRU |
| AHU'S". |
| |
| 4) INDICATE THE SIZES OF THE MAIN DUCT TRUNKS |
| DISTRIBUTING AIR FROM AHU'S 3, 4 & 5. |
| |
| 5) THE PLAN APPEARS TO SHOW INADEQUATE AIR DISTRIBUTION |
| WILL BE PROVIDED TO THE BREATHING ZONES IN THE INDOOR |
| DOG PLAY AREA BASED ON THE DUCT LAYOUT PLAN PROVIDED. |
| |
| 6) A PRODUCT DATA SHEET FOR BROAN EXHAUST FANS HAS BEEN |
| SUBMITTED WITH MODEL NUMBERS THAT DON'T MATCH THE MODEL |
| NUMBERS ON THE EQUIPMENT SCHEDULES SHOWN ON THE PLANS- |
| PLEASE CORRECT ONE OR THE OTHER. |
| |
| 7) A PRODUCT DATA SHEET HAS BEEN SUBMITTED FOR A |
| SHUTTER FAN BUT NO LOCATION, DETAILS, OR SCHEDULE FOR |
| THE FAN ARE PROVIDED ON THE PLANS. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |