2017-02-17 07:43:49 | 4TH REVIEW FBC-2014 MECHANICAL |
| PERMIT #16110180 |
| 2/17/17 |
| |
| NO CORRECTIONS TO THE PLANS OR RESPONSES TO THE 3RD |
| REVIEW COMMENTS HAVE BEEN PROVIDED. I HAVE COPIED THE |
| COMMENTS BELOW FOR REVIEW- PLEASE COMPLY. |
| |
| 1) 3RD REQUEST FOR EXHAUST VENTILATION CALCULATIONS FOR |
| ALL SYSTEMS- TABLE 403.3 |
| |
| 2) 3RD REQUEST TO PROVIDE COMPLETE EXHAUST SYSTEM |
| DRAWINGS INCLUDING THE INDOOR DOG PLAY ROOMS. THE |
| DRAWINGS AND DETAILS SHALL INCLUDE THE EXHAUST DUCT |
| TYPES AND SIZES, DUCT RUNS AND TERMINATION LOCATIONS. |
| PLEASE NOTE THAT ENGINEERING DETAILS FOR INSTALLATION |
| OF ANY ROOFTOP FANS OR TERMINATION CAPS WILL BE |
| REQUIRED. |
| |
| 3) 2ND REQUEST FOR THE ARCHITECT OF RECORD TO PROVIDE |
| SHOP DRAWING APPROVAL OF THE AC CALCULATIONS. |
| |
| 4) 2ND REQUEST FOR THE ENERGY COMPLIANCE CHECKLIST TO |
| BE FILLED OUT. |
| |
| 5) 3RD REQUEST FOR COMPLETE AIR BALANCE CALCULATIONS. |
| PLEASE NOTE THE CALCULATION M-1 DOES NOT INCLUDE THE |
| O/A AIR SUPPLIED BY AHU-3 AND THE REQUIRED EXHAUST |
| SYSTEMS IN THE INDOOR DOG AREAS. |
| |
| 6) PROVIDE THE DUCT LAYOUT PLAN FOR AHU-3. |
| |
| 7) THE CU TIE DOWN DETAIL IS INCOMPLETE. PLEASE PROVIDE |
| THE GAUGE OF THE STEEL STRAP OR MANUFACTURER'S |
| SPECIFICATIONS, AND HOW THE CLIP WILL BE FASTENED TO |
| THE CONDENSER JACKET. |
| |
| 8) 2ND REQUEST TO SHOW THE LOCATION OF THE DS DETECTORS |
| IN THE RETURN AIR SYSTEMS OF THE AHU'S. |
| |
| 9) PLEASE CLARFY WHAT TYPE OF AUTOMATIC O/A DAMPERS ARE |
| PROPOSED FOR AHU'S 1 & 2. ARE THESE MOTORIZED DAMPERS? |
| IF SO, PLEASE SEE SECTION C402.4.5.2 FBC-14 ENERGY |
| CONSERVSATION AND PROVIDE MANUFACTURER'S |
| SPECIFICATIONS. |
| |
| 10) REFER TO SECTION 401.4 AND PROVIDE THE REQUIRED |
| CLEARANCE DISTANCE MEASUREMENTS FOR THE O/A INTAKES TO |
| EXHAUST OUTLETS OR OTHER CONTAMINANT SOURCES, AND |
| VEHICULAR DRIVE AREAS SUCH AS DRIVEWAYS AND PARKING |
| LOTS |
| |
| 11) INDICATE HOW THE O/A OPENINGS WILL BE PROTECTED IN |
| COMPLIANCE WITH SECTION 401.5. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |