2017-01-28 06:09:501) THE BREAK ROOM SINK SHALL COMPLY WITH THE 2014
 FBC-ACCESS. SECS.212, 606 AND 305. SHOW THE HEIGHT OF
 THE TOP OF THE COUNTERTOP/SINK FROM THE FINISH FLOOR.
 2) THE WALL FINISH IN THE NEW TOILET ROMM SHALL COMPLY
 WITH 2014 FBC SEC. 1210. SHT.THE FINISH SCHEDULE ON
 SHT.A-2 SHOWS THE WALLS AS PAINT. CLARIFY.
 3) THE SANITARY RISER DOES NOT COMPLY WITH THE
 FBC-PLUMBING CODE.
 A) THE WASHING MACHINE SHALL BE INSTALLED ON A MINIMUM
 3 INCH STACK. FPC SEC.406.2.
 B) THE DOG TUBS ARE NOT VENTED. FPC 901.2.1.
 C) THE DISHWASHER SHALL DRAIN INDIRECTLY PER FPC
 SEC.802.1.6.
 D) THE DRINKING FOUNTAIN IS NOT VENTED. FPC 901.2.1.
 4) SHT. A-1 ( DEMO PLAN) IS MISSING. IT IS LISTED ON
 THE COVER PAGE. CLARIFY.
 5) HOT WATER IS REQUIRED TO THE WASHING MACHINE. FPC
 SEC.607.1.
 6) THE ENTIRE WATER SYSTEM ( HOT & COLD ) IS SIZED IN
 1/2 INCH PIPE. REFER TO FPC SEC.604.3.
  
 TIM LARGE
 CHIEF PLUMBING INSPECTOR
 PLUMBING PLAN REVIEW