Plan Review Notes For Permit 16110180 |
Permit Number |
16110180 |
|
Review Stop |
B |
Sequence Number |
3 |
|
Notes |
Date |
Text |
2017-01-26 17:58:08 | ****CORRECTIONS**** | | | | SAMANTHA HILL | | BUILDING PLANS EXAMINER | | [email protected] | | 561-805-6724 | | | | FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) | | FBC B = FBC BUILDING | | FBC EB = FBC EXISTING BUILDING | | FBC A = FBC ACCESSIBILITY | | FBC EC = FBC ENERGY CONSERVATION | | | | TWO COMMENTS REMAINING FROM PREVIOUS LIST (NOTE THAT A | | PROVISO WILL BE CONSIDERED; CONTACT S.KENNEDY IF I AM | | UNAVAILABLE): | | | | 3. INCORRECT OCCUPANT LOAD FOR MERCANTILE, SEE FBC B | | TABLE 1004.1.2. | | | | THIS WAS CHANGED FROM 100 TO 60. SEE THE TABLE - GRADE | | FLOOR REQUIRES 30 SF PER PERSON. REVISE PLAN | | ACCORDINGLY. | | | | 14. OFFICE DOOR LACKS MANEUVERING CLEARANCE, PULL SIDE, | | FBC ACCESSIBILITY 404.2.4.1. | | | | THIS WAS ADDRESSED BY SHOWING CLEAR FLOOR SPACE ON THE | | OPPOSITE SIDE. PLEASE REFER TO DIAGRAMS, 18" PULL SIDE | | REQUIRED, REVISE PLAN ACCORDINGLY. | | | | THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISOS: | | | | A. FBC 1006.1, MEANS OF EGRESS ILLUMINATION IS REQUIRED | | IN THE EXIT DISCHARGE; TO BE VERIFIED AT INSPECTION. | | | | B. PRODUCT APPROVALS TO BE SUBMITTED AS A REVISION | | PRIOR TO INSTALLATION | | |
|