Plan Review Notes
Plan Review Notes For Permit 16110180
Permit Number 16110180
Review Stop B
Sequence Number 3
Notes
Date Text
2017-01-26 17:58:08****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 TWO COMMENTS REMAINING FROM PREVIOUS LIST (NOTE THAT A
 PROVISO WILL BE CONSIDERED; CONTACT S.KENNEDY IF I AM
 UNAVAILABLE):
  
 3. INCORRECT OCCUPANT LOAD FOR MERCANTILE, SEE FBC B
 TABLE 1004.1.2.
  
 THIS WAS CHANGED FROM 100 TO 60. SEE THE TABLE - GRADE
 FLOOR REQUIRES 30 SF PER PERSON. REVISE PLAN
 ACCORDINGLY.
  
 14. OFFICE DOOR LACKS MANEUVERING CLEARANCE, PULL SIDE,
 FBC ACCESSIBILITY 404.2.4.1.
  
 THIS WAS ADDRESSED BY SHOWING CLEAR FLOOR SPACE ON THE
 OPPOSITE SIDE. PLEASE REFER TO DIAGRAMS, 18" PULL SIDE
 REQUIRED, REVISE PLAN ACCORDINGLY.
  
 THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISOS:
  
 A. FBC 1006.1, MEANS OF EGRESS ILLUMINATION IS REQUIRED
 IN THE EXIT DISCHARGE; TO BE VERIFIED AT INSPECTION.
  
 B. PRODUCT APPROVALS TO BE SUBMITTED AS A REVISION
 PRIOR TO INSTALLATION
  