Plan Review Notes For Permit 16110180
Permit Number 16110180
Review Stop P
Sequence Number 2
Notes
Date Text
2017-01-12 14:25:162ND REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 PLUMBING COMMENTS:
  
 1. SHOW HEIGHT OF ACCESSIBLE SINK IN BREAK ROOM TO
 COMPLY WITH FBC ACC 606.3 - 306
  
 2. SANITARY RISER DIAGRAM DOES NOT COMPLY WITH THE
 CODE. PER WPB AMEND TO FBC 107.2.1
  
 A) THE MOP SINK IS NOT VENTED. FBC PL 901.2.1
 B) ACCESSIBLE SINK IN BREAK ROOM IS NOT VENTED. FBC PL
 901.2.1
 C) DOG TUBS NOT VENTED. FBC PL 901.2.1
 D) WASHING MACHINE IS NOT VENTED. FBC PL 901.2.1
 E) THE WATER FOUNTAIN IS NOT SHOWN ON RISER DIAGRAM.
 PER WPB AMEND TO FBC 107.2.1
 F)DRAIN LINE FOR WASHING MACHINE SHALL BE A MIN OF 3".
 PER FBC PL 406.2
 G) EXISTING WASHER IS NOT SHOWN ON DEMO PLAN PLEASE
 CLARIFY. PER WPB AMEND TO FBC 107.2.1
 H) THE BUILDING DRAIN SERVING THE WASHING MACHINE, DOG
 TUBS, BREAKROOM SINKS AND MOP SINK SHALL CONNECT DOWN
 STREAM OF BATHROOM GROUP IT CAN'T CONNECT BETWEEN THE
 TOILET AND LAV. FBC PL 912.1
  
 3. THE WATER RISER DIAGRAM IS UNCLEAR PLEASE ENLARGE
 AND MAKE IT CLEAR TO READ. PER WPB AMEND TO FBC 107
 107.2.1.4
  