Plan Review Notes For Permit 16110180 |
Permit Number |
16110180 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-01-06 09:52:52 | 2ND ELECTRICAL PLAN REVIEW | | | | APPLICABLE CODES IN EFFECT: | | FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION | | FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH | | EDITION | | NFPA 70- 2011 NEC | | COMMENTS NOT ADDRESSED FROM INITIAL REVIEW: | | | | 5. SHOW CIRCUIT DESIGNATION FOR ALL NEW LIGHTING AND | | POWER OUTLETS AND EQUIPMENT. SHOW WHAT PANEL THEY | | ORIGINATE FROM TO VERIFY LOAD CALCULATION DO NOT | | EXCEEDED AMPS PER SIZE OF MAINS. | | 6. SHOW DESIGN COMPLIANCE PER FBC ENERGY CONSERVATION | | CODE. A GENERAL NOTE WILL NOT SUFFICE, SHOW SYMBOLS OF | | AUTOMATIC CONTROL LIGHTING AND LIGHTING DENSITIES FOR | | AREAS. | | | | 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL | | FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS | | REGARDING THIS PROJECT. | | | | | | VALENTINO PEREZ | | ELECTRICAL PLANS EXAMINER II | | 561-805-6717 | | [email protected] | | | | | | | | | | | | |
|