2017-01-06 09:52:522ND ELECTRICAL PLAN REVIEW
  
 APPLICABLE CODES IN EFFECT:
 FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011 NEC
 COMMENTS NOT ADDRESSED FROM INITIAL REVIEW:
  
 5. SHOW CIRCUIT DESIGNATION FOR ALL NEW LIGHTING AND
 POWER OUTLETS AND EQUIPMENT. SHOW WHAT PANEL THEY
 ORIGINATE FROM TO VERIFY LOAD CALCULATION DO NOT
 EXCEEDED AMPS PER SIZE OF MAINS.
 6. SHOW DESIGN COMPLIANCE PER FBC ENERGY CONSERVATION
 CODE. A GENERAL NOTE WILL NOT SUFFICE, SHOW SYMBOLS OF
 AUTOMATIC CONTROL LIGHTING AND LIGHTING DENSITIES FOR
 AREAS.
  
 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  