2016-11-14 08:51:351ST REVIEW FBC-2014 MECHANICAL, EXISTING BUILDING,
 ENERGY CONSERVATION CODES
 PERMIT #16110180
 11/14/16
  
 THE MECHANICAL PLANS DESIGNED BY SANDRA PUERTA
 ARCHITECT ARE DEFICIENT AND NOT IN COMPLIANCE WITH
 CURRENT CODES AND STANDARDS.
  
 1) PROVIDE EQUIPMENT SCHEDULES ON THE PLAN FOR THE NEW
 AND EXISTING AC SYSTEMS, AND THE VARIOUS EXHAUST FANS
 SHOWN IN THE DRAWINGS.
  
 2) PROVIDE AC COOLING AND HEATING CALCULATIONS FOR THE
 NEW AC SYSTEM- SECTION C403.2.1 FBC-14 ENERGY
 CONSERVATION.
  
 3) REFER TO SECTION 809.2 FBC-14 EXISTING BUILDING CODE
 AND PROVIDE MINIMUM VENTILATION CALCULATIONS FOR ALL
 ROOMS AND SPACES PER TABLE 403.3 FBC-14 MECHANICAL.
 PROVIDE A SCHEDULE THAT INDICATES THE REQUIRED AND
 PROVIDED CFMS OF OUTDOOR AIR, AND THE REQUIRED AND
 PROVIDED CFM'S OF EXHAUST AIR.
  
 4) PROVIDE AN AIR BALANCE CALCULATION.
  
 5) THE PROJECT IS DEFINED AS A CHANGE OF OCCUPANCY PER
 SECTION 202 FBC-14 EXISTING BUILDING CODE. REFER TO
 SECTION C101.4.4 FBC-14 ENERGY CONSERVATION AND SUBMIT
 DOCUMENTATION OF COMPLIANCE. SEE SECTION 401.2 FOR
 COMPLIANCE PATH OPTIONS.
  
 6) PROVIDE AN AIR DEVICE SCHEDULE ON THE PLAN,.
  
 7) INDICATE THE SIZES OF THE SUPPLY AND RETURN DUCTS,
 DIFFUSERS, DISTRIBUTION BOXES, AND RETURN GRILLS SHOWN
 ON THE LAYOUT DRAWING, AND SHOW CFM AMOUNTS AT EACH
 SUPPLY DIFFUSER AND RETURN GRILL.
  
 8) PROVIDE A COMPLETE DUCT LAYOUT FOR AHU-2 & AHU-3
  
 9) INDICATE HOW OUTSIDE AIR IS BEING SUPPLIED TO THE
 ROOMS AND SPACES, AND REFER TO SECTION C403.2.4.4 FOR
 SHUTOFF DAMPER REQUIREMENTS.
  
 10) REFER TO TABLE 403.3 FOOTNOTE B: AIR FROM THE DOG
 GROOMING ROOM IS NOT PERMITTED TO RECIRCULATE INTO THE
 ADJACENT RETAIL AREA.
  
 11) REFER TO TABLE 403.3 FOOTNOTE B: HOW IS AIR BEING
 RETURNED TO AHU-3? NO RETURN DUCTS OR GRILLS ARE SHOWN.
 PLEASE NOTE THAT AHU-1 MUST BE A COMPLETELY SEALED UNIT
 WITH A DUCTED RETURN BECAUSE IT SHARES THE SAME
 MECHANICAL CLOSET WITH AHU-2. THE AIR FROM THESE TWO
 SYSTEMS CANNOT COMMUNICATE.
  
 12) PROVIDE EXHAUST VENTILATION DETAILS: SHOW THE TYPES
 AND SIZES OF EXHAUST DUCTS, THE DUCT RUNS, AND THE
 TERMINATION LOCATIONS- SEE SECTION 501.2- 501.3.1.1.
  
 13) PROVIDE WIND LOAD ENGINEERING FOR INSTALLATION OF
 THE ACCU #3- SECTION 301.15.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER