2016-11-07 11:57:46 | PERMIT #16110180 | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | FAIL COMMENTS: | | | | 1) SHEET A-4: YOU SHOW A TRAVEL DISTANCE OF 94 FEET. | | THIS IS A NON-SPRINKLERED BUILDING. PER NFPA 150: | | 8.1.2.4* EXIT TRAVEL DISTANCES. | | 8.1.2.4.1 IN ANIMAL HOUSING FACILITIES NOT SPRINKLERED | | IN ACCORDANCE WITH SECTION 9.2, EXIT TRAVEL DISTANCE | | SHALL NOT EXCEED 75 FT (23 M) FROM ANY POINT IN THE | | FACILITY. | | | | 2) PLEASE INDICATE WHAT CATEGORY OF ANIMALS WILL BE | | HOUSED IN THIS FACILITY. (CATEGORY A, CATEGORY B, OR | | BOTH). | | PLEASE SEE NFPA 150: 9.8 SPECIAL REQUIREMENTS FOR | | CATEGORY A ANIMALS. | | | | 3) SHEET A-4: NOTE INDICATES THAT ONLY ONE (1) FIRE | | EXTINGUISHER WILL BE PROVIDED. FIRE EXTINGUISHERS WILL | | NEED TO BE PROVIDED PER NFPA 1, NFPA 101, AND NFPA 150. | | | | 4) SHEET A-4: LIFE SAFETY GENERAL NOTES INDICATE THAT | | EGRESS REQUIREMENTS ARE IN COMPLIANCE WITH NFPA 101, | | CHAPTERS 7 AND 12. PLEASE REVIEW NFPA 150 FOR | | ADDITIONAL EGRESS REQUIREMENTS, IF ANY, AS NEEDED FOR | | ANIMAL CATEGORY (A AND/OR B) AND ANIMAL HOUSING CLASS | | (CLASS 1, 2, OR 3). | | | | 5) ADDITIONAL COMMENTS MAY BE NEEDED UPON REVIEW OF | | RESUBMITTAL. | | | | | | SUE ELLEN CALDERON | | ASSISTANT FIRE MARSHAL | | OFFICE OF THE FIRE MARSHAL | | WEST PALM BEACH FIRE RESCUE | | [email protected] | | (561) 644-7326 | | | | | | |
|