2016-11-12 16:21:01 | INITIAL ELECTRICAL PLAN REVIEW |
| |
| APPLICABLE CODES IN EFFECT: |
| FLORIDA EXISTING BUILDING CODE 2014 5TH EDITION |
| FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH |
| EDITION |
| NFPA 70- 2011 NEC |
| COMMENTS: |
| 1. PLEASE PROVIDE AN ACCURATE ONE-LINE RISER THAT |
| EXISTING AS CONDUCTORS SIZE AT 1/0 IS UNDERSIZED FOR A |
| 200A MAIN. FBC 107.3.5 |
| 2. DELETE RESIDENTIAL CODE NOTES FROM THE ELECTRICAL |
| NOTES, ONLY PROVIDE WHAT IS APPLICABLE FOR THIS |
| PROJECT. FBC 107.3.5 |
| 3. CLARIFY HEX NOTES TO FLOOR PLAN. NOT SHOWN. |
| 4. SHOW A COMPLETE PANEL BOARD SCHEDULE NOT JUST |
| ADDITIONAL AS SHOWN. THERE ARE NEW POWER AND LIGHTING |
| OUTLETS SHOWN. NEW EXHAUST FANS, NEW A/H AND A/C MUST |
| BE ACCOUNTED FOR. |
| 5. SHOW CIRCUIT DESIGNATION FOR ALL NEW LIGHTING AND |
| POWER OUTLETS AND EQUIPMENT. SHOW WHAT PANEL THEY |
| ORIGINATE FROM TO VERIFY LOAD CALCULATION DO NOT |
| EXCEEDED AMPS PER SIZE OF MAINS. |
| 6. SHOW DESIGN COMPLIANCE PER FBC ENERGY CONSERVATION |
| CODE. A GENERAL NOTE WILL NOT SUFFICE, SHOW SYMBOLS OF |
| AUTOMATIC CONTROL LIGHTING AND LIGHTING DENSITIES FOR |
| AREAS. |
| 7. NEW A/C EQUIPMENT MUST PROVIDE A W/P GFCI RECEPTACLE |
| WITHIN 25FT OF UNIT FOR SERVICE. NEC 210.63. SHOW A |
| DISCONNECT FOR A/C UNIT AND A/H UNIT INSIDE. |
| 8. LABEL ON FLOOR PLAN WHAT IS NEW OR EXISTING FOR A |
| COMPLETE REVIEW. |
| 9. EM LIGHTING TO BE PROVIDED TO NEW BATHROOM AREA. |
| 10. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM |
| TO INDICATE NEC 110.24- AVAILABLE FAULT CURRENT- FIELD |
| MARKINGS; SEE VERBIAGE IN CODE. |
| 11. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL |
| FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS |
| REGARDING THIS PROJECT. |
| |
| |