2016-11-29 12:43:25 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. THIS APPEARS TO BE A CHANGE OF OCCUPANCY. REVISE |
| PLAN TO SHOW COMPLIANCE WITH FBC EXISTING BUILDING |
| CHAPTER 10. |
| |
| 2. OCCUPANT LOAD FOR A SMALL PORTION OF THE BUILDING |
| HAS BEEN DETERMINED. PROVIDE OCCUPANT LOAD FOR THE |
| REMAINDER OF THE BUILDING (6,885 SF). SEE FBC 1004.1.2, |
| PROPOSE AN OCCUPANT LOAD WHICH MOST CLOSELY RESEMBLES |
| THE USE OF THE SPACE. |
| |
| 3. OCCUPANT LOAD WAS PROVIDED USING 100 SF PER PERSON, |
| BUT IT APPEARS THAT A PORTION OF THIS AREA SHOULD USE |
| MERCANTILE, SEE FBC TABLE 1004.1.2. |
| |
| 3. REVISE PLAN TO CLARIFY: |
| IN THE TABLE ASCE7 10: |
| OCCUPANCY TYPE IIIB, CLARIFY |
| BUILDING CLASSIFICATION IIIB; CLARIFY |
| |
| TYPE OF CONSTRUCTION; SEE FBC CHAPTER 6. PLAN STATES |
| UNPROTECTED (NOT SPRNKLERED). THIS IS NOT A BUILDING |
| TYPE. |
| |
| 4. FBC 1006.1, MEANS OF EGRESS ILLUMINATION IS REQUIRED |
| IN THE EXIT DISCHARGE. NO LIGHTING IS SHOWN IN THE |
| OUTDOOR AREA WHICH IS A PART OF THE EXIT DISCHARGE. |
| |
| 5. FLORIDA STATE OR LOCAL PRODUCT APPROVALS REQUIRED |
| FOR COMPONENTS AND CLADDING, FBC 1609. |
| |
| 6. FBC 1011.1, THE EXIT DISCHARGE WHICH GOES THROUGH |
| THE OUTDOOR FENCED PLAY AREAS IS NOT READILY APPARENT. |
| IT APPEARS THAT EXIT SIGNS ARE REQUIRED IN THIS AREA, |
| REVISE PLAN. |
| |
| 7. REVISE PLAN TO SHOW EXIT DISCHARGE (PATH OF EXIT TO |
| THE PUBLIC WAY), FOR THE REAR EXIT, INCLUDING THE MEANS |
| OF EGRESS ILLUMINATION FBC 1008. |
| |
| 8. A2 HAS CONFLICATING NOTES REGARDING DOOR HARDWARE. |
| ONE STATES THAT DOORS SHOULD HAVE PANIC DEVICES, |
| ANOTHER SPECS LEVERS, FBC 107. |
| |
| 9. SEE PLUMBING COMMENTS REGARDING ACCESSIBLITY; ALL |
| ARE APPLICABLE FOR BUILDING REVIEW. |
| |
| 10. A4 HAS A FIRE ALARM LEGEND, FIRE ALARM FIXTURES NOT |
| SHOWN, FBC 107. |
| |
| 11. PROVIDE A DETAIL FOR THE CHECK OUT COUNTER, FBC |
| ACCESSIBILITY 904. |
| |
| 12. REVISE PLAN TO SHOW COMPLIANCE WITH ACCESSIBLE |
| ROUTE, FBC ACCESSIBILITY 202.4, 206.2. INFORMATION |
| REGARDING THE ENTRY DOOR AND PARKING LOCATION WAS NOT |
| PROVIDED; DOES THE ROUTE COMPLY WITH FBC A 303? |
| |
| 13. SEE IMPACT FEE REVIEW. |
| |