2017-01-09 19:11:24RESIDENTIAL (R3) ALTERATION, SECOND MECHANICAL REVIEW
 CHECKLIST.
 CODE: FBC, 5TH EDITION (2014).
  
 1- THE LOAD CALCULATIONS ARE CONSIDERING 7 PEOPLE AS
 THE OCCUPANTS IN THIS SINGLE FAMILY RESIDENCE. NUMBER
 OF PEOPLE DOESN'T MATCH NUMBER OF PEOPLE SPECIFIED ON
 THE ENERGY CALCULATIONS. ALSO, CLARIFY WHY THE
 CALCULATIONS ARE CONSIDERING 2 PEOPLE IN THE DINING
 AREA?. THE NUMBER OF PEOPLE MAY AFFECT THE SIZING OF
 THE EQUIPMENT. SEC. R403.6.1 FBC-ENERGY CONSERVATION
 DOESN'T ALLOW ANY FACTORS THAT WILL AFFECT THE SIZING
 OF THE EQUIPMENT. REVISE AS REQUIRED. (REPEAT COMMENT).
  
 2- THE TRANSFER DUCT SIZE SPECIFIED ON THE A/C PLAN FOR
 THE MASTER BEDROOM DOESN'T COMPLY WITH THE BALANCED
 RETURN AIR. SEC. M1602.4. ALL THE SUPPLY AIR INTO THE
 MASTER BEDROOM NEEDS TO BE CONSIDERED, INCLUDING THE
 BATHROOM AS REQUIRED BY EXCEPTION #3 OF SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED. (REPEAT COMMENT).
  
  