2016-12-12 11:47:56 | RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW |
| COMMENTS. |
| CODE: FBC, 5TH EDITION (2014). |
| |
| 1- THE PERSON WHO PREPARED THE LOAD CALCULATIONS IS THE |
| SAME PERSON WHO PREPARED THE ENERGY CALCULATIONS. SEE |
| BUILDING REVIEW COMMENTS FOR REQUIRED ENERGY |
| CALCULATIONS REVISIONS AND REVISE THE LOAD CALCULATIONS |
| AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS. |
| |
| 2- THE LOAD CALCULATIONS ARE CONSIDERING 12 PEOPLE AS |
| THE OCCUPANTS IN THIS SINGLE FAMILY RESIDENCE. THE |
| NUMBER OF PEOPLE LOOKS A LITTLE BIG HIGH FOR A THREE |
| BEDROOM SINGLE FAMILY RESIDENCE. THE HIGH NUMBER OF |
| PEOPLE MAY AFFECT THE SIZING OF THE EQUIPMENT. SEC. |
| R403.6.1 DOESN'T ALLOW ANY FACTORS THAT WILL AFFECT THE |
| SIZING OF THE EQUIPMENT. REVISE AS REQUIRED OR PROVIDE |
| DOCUMENTATION SHOWING WHY A HIGHER NUMBER OF PEOPLE |
| NEED TO BE CONSIDERED. |
| |
| 3- LOAD CALCULATIONS TO INCLUDE THE EQUIPMENT |
| MANUFACTURER'S AND MODEL NUMBER ALONG WITH THE SENSIBLE |
| AND TOTAL COOLING CAPACITIES AS REQUIRED BY SEC. |
| R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014). |
| NOTE: COORDINATE WITH A/C PLAN SUBMITTED. |
| |
| 4- THE TRANSFER DUCT SIZE SPECIFIED ON THE A/C PLAN FOR |
| THE MASTER BEDROOM DOESN'T COMPLY WITH THE BALANCED |
| RETURN AIR. SEC. M1602.4. ALL THE SUPPLY AIR INTO THE |
| MASTER BEDROOM NEEDS TO BE CONSIDERED, INCLUDING THE |
| BATHROOM AS REQUIRED BY EXCEPTION #3 OF SEC. M1602.4 |
| FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS |
| REQUIRED. |
| |
| 5- CONDENSER UNIT TIE-DOWN CLIP PRODUCT APPROVAL |
| SUBMITTED: PROVIDE CURRENT (2014 CODE) AND LEGIBLE |
| PRODUCT APPROVAL. |
| FAC 61G20-3.002(33). |
| |
| |