Plan Review Notes
Plan Review Notes For Permit 16110161
Permit Number 16110161
Review Stop M
Sequence Number 1
Notes
Date Text
2016-12-12 11:47:56RESIDENTIAL (R3) ALTERATION, MECHANICAL REVIEW
 COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- THE PERSON WHO PREPARED THE LOAD CALCULATIONS IS THE
 SAME PERSON WHO PREPARED THE ENERGY CALCULATIONS. SEE
 BUILDING REVIEW COMMENTS FOR REQUIRED ENERGY
 CALCULATIONS REVISIONS AND REVISE THE LOAD CALCULATIONS
 AS REQUIRED. SEC. 107.2.1 CITY AMENDMENTS.
  
 2- THE LOAD CALCULATIONS ARE CONSIDERING 12 PEOPLE AS
 THE OCCUPANTS IN THIS SINGLE FAMILY RESIDENCE. THE
 NUMBER OF PEOPLE LOOKS A LITTLE BIG HIGH FOR A THREE
 BEDROOM SINGLE FAMILY RESIDENCE. THE HIGH NUMBER OF
 PEOPLE MAY AFFECT THE SIZING OF THE EQUIPMENT. SEC.
 R403.6.1 DOESN'T ALLOW ANY FACTORS THAT WILL AFFECT THE
 SIZING OF THE EQUIPMENT. REVISE AS REQUIRED OR PROVIDE
 DOCUMENTATION SHOWING WHY A HIGHER NUMBER OF PEOPLE
 NEED TO BE CONSIDERED.
  
 3- LOAD CALCULATIONS TO INCLUDE THE EQUIPMENT
 MANUFACTURER'S AND MODEL NUMBER ALONG WITH THE SENSIBLE
 AND TOTAL COOLING CAPACITIES AS REQUIRED BY SEC.
 R403.6.1 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
 NOTE: COORDINATE WITH A/C PLAN SUBMITTED.
  
 4- THE TRANSFER DUCT SIZE SPECIFIED ON THE A/C PLAN FOR
 THE MASTER BEDROOM DOESN'T COMPLY WITH THE BALANCED
 RETURN AIR. SEC. M1602.4. ALL THE SUPPLY AIR INTO THE
 MASTER BEDROOM NEEDS TO BE CONSIDERED, INCLUDING THE
 BATHROOM AS REQUIRED BY EXCEPTION #3 OF SEC. M1602.4
 FBC-RESIDENTIAL, 5TH EDITION (2014). REVISE AS
 REQUIRED.
  
 5- CONDENSER UNIT TIE-DOWN CLIP PRODUCT APPROVAL
 SUBMITTED: PROVIDE CURRENT (2014 CODE) AND LEGIBLE
 PRODUCT APPROVAL.
 FAC 61G20-3.002(33).
  
  