2016-11-09 16:16:25 | JOB PERMIT NUMBER: 16100893 |
| JOB ADDRESS: 2417 SOUTH OLIVE AVE |
| WEST PALM BEACH FLORIDA 33401 |
| DATE: NOVEMBER 9, 2016 |
| ELECTRICAL PLAN REVIEW COMMENTS |
| |
| THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC |
| 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA |
| BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH |
| AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED. |
| |
| 1] PROVIDE A RISER DIAGRAM WITH SERVICE FEEDER WIRE |
| SIZE, CONDUIT DETAIL INCLUDING RACEWAY TYPE & SIZE, |
| GROUNDING DETAIL WITH ELECTRODE CONDUCTOR SIZE. FBC- |
| 107.3.5.3 |
| |
| 2] SHOW A GFCI OUTDOOR RECEPTACLE OUTLET FOR THE W/H |
| IGNITION. |
| |
| 3] GARAGE DOOR MOTOR RECEPTACLE OUTLET REQUIRES GFCI |
| PROTECTION PER FBC-R SEC E3902.2. |
| |
| 4] CARBON MONOXIDE ALARM REQUIRED WITHIN 10' OF |
| SLEEPING ROOMS DUE TO THE ATTACHED GARAGE PER FBC-R SEC |
| 315.1 |
| |
| 5] CLARIFY SMOKE ALARM LOCATED IN THE KITCHEN TO BE |
| LISTED FOR THE USE FOR INSTALLATION NEAR COOKING |
| APPLIANCES & EQUIPPED WITH A SILENCING MEANS FEATURE IN |
| ACCORDANCE WITH NFPA 29.8.3.4 . |
| |
| PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE |
| MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER |
| RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER |
| (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES |
| WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER |
| QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME |
| DIRECTLY. |
| |