2016-11-09 16:16:25JOB PERMIT NUMBER: 16100893
 JOB ADDRESS: 2417 SOUTH OLIVE AVE
 WEST PALM BEACH FLORIDA 33401
 DATE: NOVEMBER 9, 2016
  ELECTRICAL PLAN REVIEW COMMENTS
  
 THE PLANS HAVE BEEN REVIEWED FOR COMPLIANCE WITH NEC
 2011, (NATIONAL ELECTRICAL CODE) AND FBC 2014, (FLORIDA
 BUILDING CODE) AS WELL AS THE CITY OF WEST PALM BEACH
 AMENDMENTS. SEE BELOW A LIST OF ITEMS NOTED.
  
 1] PROVIDE A RISER DIAGRAM WITH SERVICE FEEDER WIRE
 SIZE, CONDUIT DETAIL INCLUDING RACEWAY TYPE & SIZE,
 GROUNDING DETAIL WITH ELECTRODE CONDUCTOR SIZE. FBC-
 107.3.5.3
  
 2] SHOW A GFCI OUTDOOR RECEPTACLE OUTLET FOR THE W/H
 IGNITION.
  
 3] GARAGE DOOR MOTOR RECEPTACLE OUTLET REQUIRES GFCI
 PROTECTION PER FBC-R SEC E3902.2.
  
 4] CARBON MONOXIDE ALARM REQUIRED WITHIN 10' OF
 SLEEPING ROOMS DUE TO THE ATTACHED GARAGE PER FBC-R SEC
 315.1
  
 5] CLARIFY SMOKE ALARM LOCATED IN THE KITCHEN TO BE
 LISTED FOR THE USE FOR INSTALLATION NEAR COOKING
 APPLIANCES & EQUIPPED WITH A SILENCING MEANS FEATURE IN
 ACCORDANCE WITH NFPA 29.8.3.4 .
  
 PLEASE REVISE YOUR DRAWINGS TO REFLECT THE ABOVE
 MENTIONED ITEMS. WHEN RESUBMITTING, FOR A QUICKER
 RETURN ON YOUR RE-SUBMITTAL, PROVIDE A RESPONSE LETTER
 (NARRATIVE) ADDRESSING EACH ITEM. CLOUDING THE CHANGES
 WILL BE GREATLY APPRECIATED. IF YOU HAVE FURTHER
 QUESTIONS, PLEASE DON'T HESITATE TO CONTACT ME
 DIRECTLY.
  
 1ST REVIEW FBC 2014 5TH ED. NEC 2011
 MARIO VALDES
 ELECTRICAL PLAN EXAMINER
 561-805-6713
 [email protected]
  