Plan Review Notes
Plan Review Notes For Permit 16110161
Permit Number 16110161
Review Stop B
Sequence Number 1
Notes
Date Text
2016-12-09 07:34:11RESIDENTIAL (R3) ALTERATION, BUILDING REVIEW COMMENTS.
 CODE: FBC, 5TH EDITION (2014).
  
 1- PLANS SUBMITTED ARE REFERENCING THE 2010 FBC. THE
 CURRENT CODE IS THE FBC 5TH EDITION (2014). REVISE
 INFORMATION ON SHEET A-1 AND A-3. CHAPTER 553 F.S.
  
 2- ACCORDING TO SEC. R301.2.1.4 OF FBC 5TH EDITION
 (2014) THIS BUILDING IS LOCATED IN EXPOSURE "C" NOT
 "B". REVISE INFORMATION ON SHEET A-1 AND A3 AS
 REQUIRED.
  
 3- SHEET A-2: WINDOWS SPECIFIED FOR BEDROOM LOCATED
 ADJACENT TO THE GARAGE DON'T FIT ON THE OPENING SIZE
 SPECIFIED ON PLANS. REVISE AS REQUIRED. SEC. 107.2.1
 CITY AMENDMENTS.
  
 4- CLARIFY IF PROPOSED ENTRY DOOR IS "INSWING" OR
 "OUTSWING". SHEET A-2 SHOWS "INSWING" ENTRY DOOR, WHILE
 SHEET S-1 SHOWS "OUTSWING" ENTRY DOOR. NOTE: TYPE OF
 SWING IS IMPORTANT FOR PROPER PRODUCT APPROVAL L
 REVIEW. SEC. 107.2.1 CITY AMENDMENTS.
  
 NOTE:
 DESIGNER OF RECORD TO COORDINATE WITH PERSON PREPARING
 THE ENERGY CALCULATIONS TO AVOID CONFLICTS/DELAYS.
 DESIGNER OF RECORD TO PROVIDE ALL THE DETAILS AND
 SPECIFICATIONS REQUIRED BASED ON THE INFORMATION
 SPECIFIED ON THE ENERGY CALCULATIONS SUBMITTED.
  
 5- REVISE ENERGY CALCULATIONS SUBMITTED;
 A) PROVIDE COMPLETE INFORMATION ON TOP OF FORM
 INCLUDING OWNER'S NAME, BUILDER'S NAME, PERMIT OFFICE
 AND JURISDICTION. CLARIFY WHY THE PROJECT NAME IS 2416
 S. OLIVE AVE, WHILE THE STREET ADDRESS IS 2417 S. OLIVE
 AVE. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH
 EDITION (2014).
  
 B) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW THE EXISTING HOUSE COMPLIES WITH THE R-2 INSULATION
 ON THE SLAB ON GRADE EDGE INSULATION SPECIFIED ON ITEM
 #8. SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 C) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW THE EXISTING HOUSE COMPLIES WITH THE R-8 CONCRETE
 BLOCK EXTERIOR INSULATION SPECIFIED ON ITEM #9. SEC.
 R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 D) PROVIDE COMPLETE DETAILS AND SPECIFICATIONS SHOWING
 HOW THE EXISTING HOUSE COMPLIES WITH THE R-38 CEILING
 INSULATION SPECIFIED ON ITEM #10. SEC. R405.4.3
 FBC-ENERGY CONSERVATION, 5TH EDITION (2014).
  
 E) COOLING AND HEATING INFORMATION SHOWN ON ITEMS #12
 AND #13 DON'T MATCH EQUIPMENT SIZING CALCULATIONS
 SUBMITTED. REVISE AS REQUIRED, INCLUDING THE SEER. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 F) REVISE TYPE OF HOT WATER SYSTEM SPECIFIED ON ITEM
 #14. PLANS SUBMITTED DON'T SPECIFY ELECTRIC SYSTEM.
 SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 G) CEILING FANS CREDIT IS TAKEN ON ITEM #15. SPECIFY ON
 PLANS SIZE AND LOCATION OF CEILING FANS AS REQUIRED BY
 SEC. R405.7.6 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 H) OWNER /AGENT TO CERTIFY AND DATE BOTTOM OF FORM AS
 REQUIRED BY SEC. R103.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 I) NUMBER OF OCCUPANTS SPECIFIED UNDER "SPACES" ON PAGE
 2 OF 4 DOESN'T MATCH NUMBER OF OCCUPANTS SHOWN ON THE
 EQUIPMENT SIZING CALCULATIONS SUBMITTED. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 J) TYPE OF ROOF SPECIFIED UNDER "ROOF" ON PAGE 2 OF 4
 DOESN'T MATCH TYPE OF ROOF SHOWN ON PLANS. REVISE AS
 REQUIRED. SEC. R101.5.1.1.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 K) ACCORDING TO SEC. R806.2 FBC-RESIDENTIAL, THE
 REQUIRED ATTIC VENTILATION RATIO IS 1/150. ATTIC
 INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC
 VENTILATION RATIO. PROVIDE COMPLETE DETAILS AND
 SPECIFICATIONS SHOWING HOW THE EXISTING HOUSE COMPLIES
 WITH THE 1/300 RATIO. SEE SEC. R806.2 FBC-RESIDENTIAL
 FOR THE REQUIREMENTS REQUIRED TO MEET THIS VENT RATIO
 AND PROVIDE THE REQUIRED DOCUMENTATION.
  
 L) REVISE THE WINDOWS/DOORS OVERHANG SEPARATION
 SPECIFIED ON SHEET 3 OF 4 TO MATCH PLANS. SEC.
 R101.5.1.1.2 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 M) DOORS INFORMATION ON PAGE 3 OF 4 SPECIFIES INSULATED
 DOORS. TYPE OF DOORS DON'T MATCH TYPE OF DOORS
 SPECIFIED ON PLANS AND PRODUCT APPROVALS SUBMITTED.
 DOOR WITH GLAZING NEEDS TO BE SPECIFIED ON WINDOWS AREA
 AS REQUIRED BY SEC. R405.5.3.3 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 N) BUILDER TO COMPLETE THE EPL DISPLAY CARD AS REQUIRED
 BY SEC. R405.4.3 FBC-ENERGY CONSERVATION, 5TH EDITION
 (2014).
  
 NOTE:
 LABEL FOR WINDOWS AND DOORS SHOWING THE U-FACTOR AND
 SHGC FACTOR SPECIFIED ON THE ENERGY CALCULATIONS WILL
 BE REQUIRED WHEN THE ENERGY CALCULATIONS ARE NOT USING
 THE PROGRAM DEFAULT FACTORS.
  
 6-CEILING FANS CREDIT IS TAKEN ON ITEM #15. DESIGNER OF
 RECORD TO SPECIFY ON PLANS SIZE AND LOCATION OF CEILING
 FANS AS REQUIRED BY SEC. 103.2 FBC-ENERGY CONSERVATION,
 5TH EDITION (2014).
  
 7- ACCORDING TO SEC. R806.2 FBC-RESIDENTIAL, THE
 REQUIRED ATTIC VENTILATION RATIO IS 1/150. ATTIC
 INFORMATION ON PAGE 2 OF 4 SPECIFIES 1/300 ATTIC
 VENTILATION RATIO. DESIGNER OF RECORD TO PROVIDE
 COMPLETE DETAILS AND SPECIFICATIONS SHOWING HOW THE
 EXISTING HOUSE COMPLIES WITH THE 1/300 RATIO AS
 REQUIRED BY SEC. R806.2 FBC-RESIDENTIAL.
  
 8- PROVIDE PRODUCT APPROVAL (2 COPIES) AS REQUIRED BY
 FAC 61G20-3.002(33) FOR "INSWING" ENTRY DOOR AS SHOWN
 ON PLANS.
  