Plan Review Notes For Permit 16110138 |
Permit Number |
16110138 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2016-11-08 10:50:10 | 1ST REVIEW FBC-2014 MECHANICAL | | PERMIT #16110138 | | 11/8/16 | | | | 1) PLEASE PROVIDE A COVER SHEET AND PLAN INDEX FOR THE | | PROPOSED PROJECT- SECTION 107.1 WPB AMENDMENTS TO THE | | FBC. | | | | 2) DESIGN CRITERIA: PROVIDE A LIST OF CODES AND | | STANDARDS USED IN THE DESIGN OF THE PROJECT- SECTION | | 107.1. | | | | 3) SYSTEM COMMISSIONING IS REQUIRED FOR THE NEW COOLING | | TOWERS AND OUTSIDE AIR UNITS IN COMPLIANCE WITH SECTION | | C408.2 FBC-14 ENERGY CONSERVATION. PLEASE PROVIDE ON | | THE PLAN OR IN DOCUMENT FORM AN OUTLINE OF THE | | COMMISSIONING PLAN AND PROCEDURES AS INDICATED IN | | SECTION C408.2.1. | | | | 4) INDICATE THE TYPE AND THICKNESS OF WATER PIPING | | INSULATION, AND SUBMIT SPECS FOR BOTH THE PVC PIPING | | AND THE INSULATION. | | | | 5) PROVIDE A BACKFLOW PREVENTER FOR THE 1" MAKE UP | | WATER PIPE- SECTION 608.1 FBC-14 PLUMBING. | | | | 6) CLARIFY IF THE NEW MARLEY COOLING TOWERS HAVE FM | | APPROVAL- SUBMIT MANUFACTURER'S SPECIFICATIONS. | | | | 7) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF | | SERVICE PLATFORMS AND LADDERS- SECTION 306.1. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|