Plan Review Notes
Plan Review Notes For Permit 16110138
Permit Number 16110138
Review Stop M
Sequence Number 1
Notes
Date Text
2016-11-08 10:50:101ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110138
 11/8/16
  
 1) PLEASE PROVIDE A COVER SHEET AND PLAN INDEX FOR THE
 PROPOSED PROJECT- SECTION 107.1 WPB AMENDMENTS TO THE
 FBC.
  
 2) DESIGN CRITERIA: PROVIDE A LIST OF CODES AND
 STANDARDS USED IN THE DESIGN OF THE PROJECT- SECTION
 107.1.
  
 3) SYSTEM COMMISSIONING IS REQUIRED FOR THE NEW COOLING
 TOWERS AND OUTSIDE AIR UNITS IN COMPLIANCE WITH SECTION
 C408.2 FBC-14 ENERGY CONSERVATION. PLEASE PROVIDE ON
 THE PLAN OR IN DOCUMENT FORM AN OUTLINE OF THE
 COMMISSIONING PLAN AND PROCEDURES AS INDICATED IN
 SECTION C408.2.1.
  
 4) INDICATE THE TYPE AND THICKNESS OF WATER PIPING
 INSULATION, AND SUBMIT SPECS FOR BOTH THE PVC PIPING
 AND THE INSULATION.
  
 5) PROVIDE A BACKFLOW PREVENTER FOR THE 1" MAKE UP
 WATER PIPE- SECTION 608.1 FBC-14 PLUMBING.
  
 6) CLARIFY IF THE NEW MARLEY COOLING TOWERS HAVE FM
 APPROVAL- SUBMIT MANUFACTURER'S SPECIFICATIONS.
  
 7) PROVIDE STRUCTURAL DETAILS FOR INSTALLATION OF
 SERVICE PLATFORMS AND LADDERS- SECTION 306.1.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719
 [email protected]
  