2016-12-28 09:14:142ND REVIEW FBC-2014 MECHANICAL
 PERMIT #16110097
 12/28/16
  
 1) PROVIDE THE DIMENSIONS OF THE RETURN AIR GRILLS AT
 THE MECHANICAL ROOM- 601.5
  
 2) SHOW THE LOCATION(S) OF THE REQUIRED SMOKE
 DETECTOR(S) IN THE MECHANICAL ROOM- SECTION 606.2.2
  
 3) SHOW THE LOCATION OF THE O/A DUCT.
  