Plan Review Notes For Permit 16110097 |
Permit Number |
16110097 |
|
Review Stop |
M |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2016-12-28 09:14:14 | 2ND REVIEW FBC-2014 MECHANICAL | | PERMIT #16110097 | | 12/28/16 | | | | 1) PROVIDE THE DIMENSIONS OF THE RETURN AIR GRILLS AT | | THE MECHANICAL ROOM- 601.5 | | | | 2) SHOW THE LOCATION(S) OF THE REQUIRED SMOKE | | DETECTOR(S) IN THE MECHANICAL ROOM- SECTION 606.2.2 | | | | 3) SHOW THE LOCATION OF THE O/A DUCT. | | | | CHRISTOPHER L. COLE | | MECHANICAL PLANS EXAMINER | | 561-805-6719 | | [email protected] | | |
|