Plan Review Notes For Permit 16110097 |
Permit Number |
16110097 |
|
Review Stop |
E |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-01-12 17:06:03 | PROVISO 2014 5TH FBC ED. NEC 2011 | | MARIO VALDES | | ELECTRICAL PLAN EXAMINER | | 561-805-6713 | | [email protected] | | | | | | 1] APPLY ARC-FLASH HAZARD WARNING LABEL TO ELECTRICAL | | EQUIPMENT LIKELY TO BE WORKED ON WHILE ENERGIZED PER | | NEC 110.16. | | | | 2] PULL BOX SHALL BE SIZED IN ACCORDANCE WITH NEC | | 314.28. | | |
|