2016-11-27 05:27:201) SUBMIT A SANITARY AND WATER RISER FOR BOTH BREAK
 ROOM SINKS. THE PLUMBING SHEET SHOWS THE DISCHARGE LINE
 FROM THE SUMP TANK BUT WHERE ARE THE LINES FROM THE TWO
 SINKS THAT ARE DISCHARGING INTO THE TANK? SHOW THE SIZE
 OF EACH LINE FROM THE FIXTURES INTO THE TANK.WPB AMEND.
 TO FBC SEC. 107.3.5.3.
 2) THE SANITARY CONNNECTION FROM THE SUMP TANK TO THE
 EXISTING BUILDING DRAINAGE SYSTEM SHALL COMPLY WITH
 2014 FBC-PLUMBING SEC.712.3.5.
  
  