2016-11-09 08:08:161ST REVIEW FBC-2014 MECHANICAL
 PERMIT #16110097
 11/9/16
  
 1) SHEET M-1: PLEASE IDENTIFY ALL THE ROOMS AND SPACES
 ON THE PLAN- SECTION 107.2.1 WPB AMENDMENTS TO THE FBC.
  
 2) M-1: PROVIDE THE MAKES AND MODELS AND COOLING AND
 HEATING CAPACITIES OF THE EXISTING AC SYSTEMS.
  
 3) M-1: CORRECT NOTE #2 INDICATING 1152 SF TO SQUARE
 INCHES.
  
 4) REFER TO SECTION 602.1: PLENUMS SHALL BE LIMITED TO
 ONE FIRE AREA. PROVIDE A DUCTED RETURN TO AC-2 FROM THE
 WEST TENANT SPACE.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 561-805-6719