2016-11-29 15:47:13 | 2ND REVIEW: FBC 2014 5TH ED. RESIDENTIAL, EXISTING |
| BUILDING |
| |
| REVIEW FOR RE-ISSUANCE OF PERMIT NUMBER 03120384 FOR |
| RE-ROOFING OF WORK THAT WAS PERFORMED IN 2004. THE JOB |
| WAS ORIGINALLY APPLIED FOR ON 12/05/2003 AND IS |
| DOCUMENTED WITH INSPECTION HISTORY AS FOLLOWS: |
| 01/23/2004 FAILED SHEATHING BUT NOTED AS IN PROGRESS |
| WITH NO ADDITIONAL NOTES, 01/26/2004 PASSED ROOF METAL |
| TIN TAG, 07/01/2004 FAILED FINAL WITH NO NOTES AND |
| CODED NOT READY. THE WORK DESCRIPTION IS: REPLACE ROOF |
| WITH EXISTING IDENTICAL TILE. THERE IS NO UNDERLAYMENT |
| SYSTEM SPECIFIED. THERE IS NO BUILT UP OR OTHER ROOFING |
| PRODUCT SPECIFIED. SHEET 1 OF 6 FOR MIAMI DADE NOA |
| 02-1211.08 ROOF TILE IS IN THE RECORD. NO TILE |
| ATTACHMENT IS SPECIFIED. |
| |
| THE INSPECTION HISTORY IS INCOMPLETE. THE OWNER HAS |
| ENGAGED A LICENSED ROOFING CONTRACTOR. THE CONTRACTOR |
| AND OWNER MUST ENGAGE A LICENSED ENGINEER OR ROOFING |
| CONSULTANT TO PERFORM AN INVESTIGATION AND/OR TESTS TO |
| ASSURE ALL THE REQUIREMENT OF THE PERMIT WERE |
| SATISFACTORILY COMPLETED AND/OR SPECIFY ADDITIONAL WORK |
| WHICH MAY BE NECESSARY. PURSUANT TO FBC 110.3.9.1 AND |
| FBC 117, A WRITTEN REPORT WITH PHOTOGRAPHIC EVIDENCE IS |
| REQUIRED. SUCH REPORT SHALL INCLUDE BUT NOT BE LIMITED |
| TO CERTIFYING THE FOLLOWING INSPECTIONS. |
| |
| ROOF SHEATHING RE-NAILING |
| UNDERLAYMENT AND UNDERLAYMENT FASTENER SPACING |
| INCLUDING ALL METAL, FLASHING, AND DRIP EDGE |
| INSTALLATION IS ON RECORD AS NOTED ABOVE. |
| BUILT UP OR OTHER SECONDARY ROOFING SYSTEM INSTALLATION |
| ROOFING TILE INSTALLATION AND FASTENING METHOD. |
| THE REMAINING USEFUL LIFE OF THE ROOF COVERING SHALL BE |
| ESTIMATED AND DOCUMENTED IN THE REPORT. |
| |
| FBC 110.3.9.1 AFFIDAVIT FOR INSPECTION. WITH SPECIFIC |
| PRIOR APPROVAL OF, AND IN A FORMAT ACCEPTABLE TO THE |
| BUILDING OFFICIAL, AN AFFIDAVIT FOR CERTIFICATION OF |
| INSPECTION MAY BE ACCEPTED FROM THE PERMIT QUALIFIER; |
| WHEN ACCOMPANIED BY EXTENSIVE PHOTOGRAPHIC EVIDENCE OF |
| SUFFICIENT DETAIL TO DEMONSTRATE CODE COMPLIANCE. |
| |
| FBC 117 - THE BUILDING OFFICIAL MAY REQUIRE TESTS OR |
| TEST REPORTS AS PROOF OF COMPLIANCE. REQUIRED TESTS ARE |
| TO BE MADE AT THE EXPENSE OF THE OWNER, OR AGENT, BY AN |
| APPROVED TESTING LABORATORY OR OTHER APPROVED AGENCY. |
| |
| DEPENDING ON THE ACCEPTABILITY OF THE REPORT AND |
| INSPECTION AFFIDAVIT, THE MATTER MAY BE RESOLVED |
| WITHOUT FURTHER NEED TO SCHEDULE ANY INSPECTION. PLEASE |
| COORDINATE WITH ME DIRECTLY UPON FURTHER SUBMITTAL. |
| |
| ALTERNATIVELY, A RE-SUBMITTAL MAY BE ACCEPTED UNDER |
| THIS PERMIT RECORD FOR A NEW ROOFING SYSTEM. ADDITIONAL |
| REVIEW AND FEES WILL APPLY. |
| |
| IN THE EVENT THE ABOVE CANNOT BE ACCOMPLISHED, THE |
| ORIGINAL PERMIT WILL REMAIN EXPIRED. |
| |
| STEVEN KENNEDY, CBO |
| CHIEF PLANS EXAMINER |