2018-04-05 16:50:35 | MECHANICAL PROVISO. |
| 4/5/18 |
| |
| REQUIRED SUBMITTALS: |
| |
| 1) WIND LOAD ENGINEERING FOR INSTALLATION OF ALL |
| EXTERIOR MECHANICAL EQUIPMENT INCLUDING AC CONDENSERS |
| AND FANS. |
| |
| 2) FLORIDA PRODUCT APPROVALS AND/OR MIAMI-DADE NOA'S |
| FOR CONDENSER ANCHORING CLIPS, EXHAUST AND OUTDOOR AIR |
| LOUVERS. |
| |
| 3) MANUFACTURER'S SPECIFICATIONS AND INSTALLATION |
| INSTRUCTIONS FOR THE GARAGE EXHAUST FANS, THE HONEYWELL |
| GAS MONITORS AND CONTROLLER, THE EXHAUST DUCT |
| FIREWRAPPING, FIRE DAMPERS, AND SMOKE DETECTORS. |
| |
| ALL SUBMITTALS SHALL BE REVIEWED AND APPROVED BY THE |
| DESIGN PROFESSIONAL OF RECORD AND BEAR SHOP DRAWING |
| APPROVAL STAMPS. |
| |
| 1) DEFERRED SUBMITTAL: 107.3.4.2 DEFERRED SUBMITTALS. |
| FOR THE PURPOSES OF THIS SECTION, DEFERRED SUBMITTALS |
| ARE DEFINED AS THOSE PORTIONS OF THE DESIGN THAT ARE |
| NOT SUBMITTED AT THE TIME OF THEAPPLICATION AND THAT |
| ARE TO BE SUBMITTED TO THE BUILDING OFFICIAL WITHIN A |
| SPECIFIED PERIOD. DEFERRAL OF ANY SUBMITTAL ITEMS SHALL |
| HAVE THE PRIOR APPROVAL OF THE BUILDING OFFICIAL. THE |
| REGISTERED DESIGN PROFESSIONAL IN RESPONSIBLE CHARGE |
| SHALL LIST THE DEFERRED SUBMITTALS ON THE CONSTRUCTION |
| DOCUMENTS FOR REVIEW BY THE BUILDING OFFICIAL. |
| DOCUMENTS FOR DEFERRED SUBMITTAL ITEMS SHALL BE |
| SUBMITTED TO THE REGISTERED DESIGN PROFESSIONAL IN |
| RESPONSIBLE CHARGE WHO SHALL REVIEW THEM AND FORWARD |
| THEM TO THE BUILDING OFFICIAL WITH A NOTATION |
| INDICATING THAT THE DEFERRED SUBMITTAL DOCUMENTS HAVE |
| BEEN REVIEWED AND FOUND TO BE IN GENERAL CONFORMANCE TO |
| THE DESIGN OF THE BUILDING. THE DEFERRED SUBMITTAL |
| ITEMS SHALL NOT BE INSTALLED UNTIL THE DEFERRED |
| SUBMITTAL DOCUMENTS HAVE BEEN APPROVED BY THE BUILDING |
| OFFICIAL. |
| 2) DEFERRED SUBMITTAL. 2017 FBC 107.3.4.1 PRODUCT |
| APPROVALS. THOSE PRODUCTS WHICH ARE REGULATED BY THE |
| DCA RULE 9N-03 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. |
| |