Plan Review Notes
Plan Review Notes For Permit 16110061
Permit Number 16110061
Review Stop B
Sequence Number 4
Notes
Date Text
2018-04-07 13:52:41****PROVISOS****
 REVISED 4/13/18
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 A. PRODUCT APPROVALS ARE DEFERRED SUBMITTALS. ALL
 PRODUCT APPROVALS, DELEGATED ENGINEERING, AND OTHER
 SUBMITTALS REQUIRED BY THE INSPECTOR ARE TO BE
 SUBMITTED AND REVIEWED BY OUR DEPARTMENT PRIOR TO
 INSTALLATION. ALL SUBMITTALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL TO THE BUILDING
 DIVISION, FBC B 1609.
  
 B. A SEPARATE ROOF PERMIT IS REQUIRED. THE ROOF PRODUCT
 APPROVAL INDICATING THE ASSEMBLY PROPOSED AND
 ENGINEERING, IF APPLICABLE, IS TO BE SUBMITTED. THE
 ROOF PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL. ROOF PERMIT REQUIRED PRIOR
 TO ROOF WORK COMMENCEMENT.
  
 C. MOVEABLE (NONFIXED) SEATING WAS NOT REVIEWED.
  
 D. REPLAT REQUIRED PRIOR TO CO. A COPY OF THE RECORDED
 REPLAT IS TO BE PROVIDED VIA EMAIL.
  
 E. RESTRICTIVE COVENANT REQUIRED PRIOR TO C.O. A COPY
 OF THE RECORDED DOCUMENT IS TO BE PROVIDED VIA EMAIL.
 (RECEIVED ON 4/13/18)
  
 F. SEPARATE PERMITS ARE REQUIRED; ONLY BUILDING,
 MECHANICAL, ELECTRICAL, PLUMBING ARE INCLUDED IN THIS
 REVIEW. SEPARATE PERMITS, FEES AND PLANS ARE REQUIRED
 FOR FIRE ALARM, FIRE SPRINKLER, FIRE UNDERGROUND LINE,
 PARKING LOT, GAS, LOW VOLTAGE, LANDSCAPING, AND OTHER
 SUCH ITEMS.
  
 G. THIS PROJECT HAS A SEPARATE ENGINEERING PERMIT;
 THERE MAY BE CONFLICTS BETWEEN THESE CIVIL SHEETS AND
 THE ISSUED ENGINEERING PERMIT. ISSUED AT CONTRACTOR'S
 RISK. APPLICANT IS TO REVISE ANY SHIEETS WHICH AFFECT
 BUILDING OR FIRE CODE COMPLIANCE.
  
 H. DIGITAL SIGNATURE FOR HOLLOWCORE SHOP DRAWINGS IS
 NOT ACCEPTABLE TO FBPE . PLEASE PROVIDE A PAPER SIGNED
 AND SEALED ORIGINAL TO ADDRESS. THIS MUST BE DONE PRIOR
 TO INSTALLATION.