Plan Review Notes
Plan Review Notes For Permit 16110061
Permit Number 16110061
Review Stop M
Sequence Number 3
Notes
Date Text
2018-02-09 14:01:563RD REVIEW FBC-2014 MECHANICAL , ENERGY CONSERVATION
 CODES.
 WEST PALM BEACH AMENDMENTS TO THE FBC.
 PERMIT #16110061
 7/7/17
  
 PLAN REVIEW RESULTS: DENIED.
  
 1) THE VENTILATION SYSTEM IN THE GOLF CART PARKING
 GARAGE WHERE THE BATTERIES ARE CHARGED IS STILL IN
 QUESTION. THE SUBMITTAL FROM CLUB CAR AND THE REVISED
 PLAN ARE NOT CLEARLY INDICATING THAT THE SYSTEM WILL
 PROVIDE CONTINUOUS VENTILATION THAT WILL LIMIT THE
 CONCENTRATION OF HYDROGEN TO 1.0 PERCENT OF THE VOLUME
 OF THE ROOM- SECTION 502.4.1. PROVIDE FURTHER EVIDENCE
 AND CALCULATIONS
  
 ACCORDINGLY. PLEASE NOTE THAT THE SENSORS SHALL ALSO BE
 CAPABLE OF DETECTING NO2 IN CONJUNCTION WITH CO2 PER
 SECTION 404.1 (2).
  
 2) REFER TO SECTIONS 510.6.1 & 510.6.2: THE FIRE
 DAMPERS IN THE GARAGE EXHAUST DUCTS ARE PROHIBITED, AND
 THE DUCTS SHALL BE ENCLOSED IN FIRE-RESISTANT SHAFT
 CONSTRUCTION WHERE THEY PENETRATE THE FLOOR/CEILING
 SASSEMBLY, ASCEND UP THROUGH THE 1ST FLOOR AND ATTIC
 SPACE TO TERMINATION ABOVE THE ROOF.
  
  
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT
 CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE
 PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND
 KEEP THEM WITH THE SUBMITTALS.
  
 CHRISTOPHER L. COLE
 MECHANICAL PLANS EXAMINER
 401 CLEMATIS STREET
 WEST PALM BEACH FL 33401
 561-805-6719
 [email protected]
  