Date |
Text |
2018-02-09 14:01:56 | 3RD REVIEW FBC-2014 MECHANICAL , ENERGY CONSERVATION |
| CODES. |
| WEST PALM BEACH AMENDMENTS TO THE FBC. |
| PERMIT #16110061 |
| 7/7/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) THE VENTILATION SYSTEM IN THE GOLF CART PARKING |
| GARAGE WHERE THE BATTERIES ARE CHARGED IS STILL IN |
| QUESTION. THE SUBMITTAL FROM CLUB CAR AND THE REVISED |
| PLAN ARE NOT CLEARLY INDICATING THAT THE SYSTEM WILL |
| PROVIDE CONTINUOUS VENTILATION THAT WILL LIMIT THE |
| CONCENTRATION OF HYDROGEN TO 1.0 PERCENT OF THE VOLUME |
| OF THE ROOM- SECTION 502.4.1. PROVIDE FURTHER EVIDENCE |
| AND CALCULATIONS |
| |
| ACCORDINGLY. PLEASE NOTE THAT THE SENSORS SHALL ALSO BE |
| CAPABLE OF DETECTING NO2 IN CONJUNCTION WITH CO2 PER |
| SECTION 404.1 (2). |
| |
| 2) REFER TO SECTIONS 510.6.1 & 510.6.2: THE FIRE |
| DAMPERS IN THE GARAGE EXHAUST DUCTS ARE PROHIBITED, AND |
| THE DUCTS SHALL BE ENCLOSED IN FIRE-RESISTANT SHAFT |
| CONSTRUCTION WHERE THEY PENETRATE THE FLOOR/CEILING |
| SASSEMBLY, ASCEND UP THROUGH THE 1ST FLOOR AND ATTIC |
| SPACE TO TERMINATION ABOVE THE ROOF. |
| |
| |
| WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE |
| LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY |
| RE-SUBMITTAL FORM. ADDITIONALLY, PLEASE INSERT |
| CORRECTED PLAN SHEETS INTO THE SETS, REMOVE THE |
| PREVIOUSLY REVIEWED SHEETS AND MARK VOID ON THEM, AND |
| KEEP THEM WITH THE SUBMITTALS. |
| |