2018-02-07 07:37:343RD REVIEW
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER LL
 CITY OF WEST PALM BEACH
 DEVELOPMENT SERVICES
 BUILDING DIVISION
 561-805-6711
 [email protected]
  
 GAS COMMENTS:
  
 PREVIOUS COMMENT NOT COMPLIED 3RD REQUEST SUBMIT
 CALCULATIONS FOR COMBUSTION AIR PER THE FBC-2014 FUEL
 GAS CODE SEC. 304. THE WATER HEATERS ARE THE ONLY
 DIRECT VENT GAS APPLIANCES PLEASE PROVIDE COMBUSTION
 CALC FOR KITCHEN COOKING APPLIANCES.
  
  
 WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES
 AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE
 AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW.
  