Plan Review Notes
Plan Review Notes For Permit 16110061
Permit Number 16110061
Review Stop B
Sequence Number 3
Notes
Date Text
2018-02-05 08:55:19****CORRECTIONS****
 REVISED 2/21/18
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. SEE COMMENTS FROM PREVIOUS LISTS, ITEM #16: REVISE
 PLAN TO SHOW COMPLIANCE WITH FBC B 705, TABLES 602,
 705.8.
  
 3RD REVIEW, SHEET A004 WAS PRELIMINARILY REVIEWED AND
 AGREED UPON IN A MEETING - A RESTRICTIVE COVENANT IS TO
 BE FILED TO LIMIT CONSTRUCTION ON THE ADJACENT LOT.
  
 PLEASE PROVIDE TIMELINE FOR THE RECORDING OF THE
 RESTRICTIVE COVENANT AND THE REPLAT. SEE ALSO NEW
 COMMENT #2.
  
 2. A004 DOES NOT MATCH A005 AND OTHER SHEETS. SHEET
 A005 AND OTHER PAGES (SUCH AS A201) DEPICT THE CORNER
 OF THE ROOF OVERHANG EXTENDING OVER THE ADJACENT
 PROPERTY. ALTHOUGH A RESTRICTIVE COVENANT ADDRESSING
 THE PROPOSED NONCOMPLIANT CONDITION AT THIS LOCATION, I
 DO NOT RECALL EXTENSION OVER THE PROPERTY LINE. AS THE
 TWO PLANS CONFLICT, CLARIFY WHAT IS PROPOSED.
  
 2/21/18 PER BUILDING OFFICIAL, OK FOR OVERHANG TO
 ENCROACH PROPERTY LINE INTO THE AREA COVERED BY THE
 RESTRICTIVE COVENANT.
  
 3. SOME OF THE STRUCTURAL PAGES HAVE A DIGITAL
 SIGNATURE WHICH DO NOT COMPLY WITH FAC61G15-23 (STATES
 THE DOCUMENT WAS SIGNED BY "DOCUSIGN" RATHER THAN
 C.TIEDGE,PE. THIS HAS BEEN DISCUSSED WITH ENGINEER AND
 SENT TO FBPE TO ANSWER HER QUESTIONS. FOR THE STRUCTURE
 PERMIT, ENGINEER HAD ADDRESSED THE ISSUE BY UTILIZING A
 DIGITAL SEAL FROM A DIFFERENT VENDOR.
  
 SHEETS WHICH NEED A NEW DIGITAL SIGNATURE (SIGNED BY
 "DOCUSIGN" RATHER THAN ENGINEER): S001, S002, S003,
 S200, S302, S303, S304, S305
  
 S201, S300 (MESSAGE: SIGNED AND ALL SIGNATURES ARE
 VALID, BUT WITH UNSIGNED CHANGES AFTER THE LAST
 SIGNATURE),
  
 NEW COMMENTS:
  
 4. HOLLOWCORE SHOP DRAWINGS ARE NOT SIGNED AND SEALED
 AND ARE NOT REVIEWED BY SEOR, FAC61G15-30.005. THIS WAS
 ALSO NOT SUBMITTED WITH THE STRUCTURE PERMIT. WHAT IS
 THE PROPOSED INSTALLATION DATE? ALL DELEGATED
 ENGINEERING IS TO BE SUBMITTED, REVIEWED, AND APPROVED
 PRIOR TO INSTALLATION. THIS MAY BE A PROVISO ITEM UPON
 REQUEST, REQUIRED PRIOR TO INSTALLATION, IF THERE IS
 ADEQUATE TIME TO DO SO (ALLOW AT LEAST 30 DAYS AFTER
 PERMIT ISSUANCE BEFORE SETTING OF MECHANICAL EQUIPMENT
 FOR SUBMITTAL AND REVIEW OF REQUIRED DOCUMENTS).
  
 5. MECHANICAL EQUIPMENT ANCHOR INFORMATION WAS
 PROVIDED. THIS WAS NOT REVIEWED BY DOR, AND DOES NOT
 INDICATE THE METHOD OF FASTENING PROPOSED, FBC B 1609,
 FBC 107. AS A STRUCTURE PERMIT HAS ALREADY BEEN ISSUED,
 PROVIDE PROPOSED INSTALLATION DATE. THIS MAY BE A
 PROVISO ITEM UPON REQUEST, REQUIRED PRIOR TO
 INSTALLATION, IF THERE IS ADEQUATE TIME TO DO SO (ALLOW
 AT LEAST 30 DAYS AFTER PERMIT ISSUANCE BEFORE SETTING
 OF MECHANICAL EQUIPMENT FOR SUBMITTAL AND REVIEW OF
 REQUIRED DOCUMENTS).
  
 6. A202, A203, BLUE DOTS WERE ADDED TO THE PLAN. THIS
 APPEARS TO BE RELATED TO PLUMBING. CLARIFY WHY THIS
 INFORMATION WAS ADED TO THE PLAN FOR THIS REVIEW; THIS
 INFORMATION IS NOT TYPICALLY SHOWN ON THIS PAGE. EITHER
 REMOVE OR PROVIDE A LEGEND. ADDITIONAL REVIEW BY
 PLUMBING MAY BE REQUIRED, FBC 107. CHECK ALL PAGES.
  
 7. NA
  
 8. THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING
 PROVISOS:
  
 A. PRODUCT APPROVALS WERE NOT SUBMMITTED. ALL PRODUCT
 APPROVALS ARE TO BE SUBMITTED AND REVIEWED PRIOR TO
 INSTALLATION. PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTALM, FBC B 1609.
  
 B. A SEPARATE ROOF PERMIT IS REQUIRED. THE ROOF PRODUCT
 APPROVAL INDICATING THE ASSEMBLY PROPOSED AND
 ENGINEERING, IF APPLICABLE, IS TO BE SUBMITTED. THE
 ROOF PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL. ROOF PERMIT REQUIRED PRIOR
 TO ROOF WORK COMMENCEMENT.
  
 C. MOVEABLE (NONFIXED) SEATING WAS NOT REVIEWED.
  
 D. REPLAT REQUIRED PRIOR TO CO. A COPY OF THE RECORDED
 REPLAT IS TO BE PROVIDED VIA EMAIL.
  
 E. RESTRICTIVE COVENANT REQUIRED PRIOR TO C.O. A COPY
 OF THE RECORDED DOCUMENT IS TO BE PROVIDED VIA EMAIL.
  
 F. SEPARATE PERMITS ARE REQUIRED; ONLY BUILDING,
 MECHANICAL, ELECTRICAL, PLUMBING ARE INCLUDED IN THIS
 REVIEW. SEPARATE PERMITS, FEES AND PLANS ARE REQUIRED
 FOR FIRE ALARM, FIRE SPRINKLER, FIRE UNDERGROUND LINE,
 PARKING LOT, GAS, LOW VOLTAGE, LANDSCAPING, AND OTHER
 SUCH ITEMS.
  
 G. THIS PROJECT HAS A SEPARATE ENGINEERING PERMIT;
 THERE MAY BE CONFLICTS BETWEEN THESE CIVIL SHEETS AND
 THE ISSUED ENGINEERING PERMIT. ISSUED AT CONTRACTOR'S
 RISK. APPLICANT IS TO REVISE ANY SHIEETS WHICH AFFECT
 BUILDING OR FIRE CODE COMPLIANCE.
  
  
  
  