Plan Review Notes
Plan Review Notes For Permit 16110061
Permit Number 16110061
Review Stop P
Sequence Number 2
Notes
Date Text
2017-07-07 11:39:161ST REVIEW: FBC 2014 5TH EDITION
  
 PLUMBING COMMENTS:
  
 1. SHT P.3.3 THE TRAP FOR THE MOP SINK IS SHOWN ON THE
 SANITARY LINE IT SHALL BE ON THE GREASE RISER PLEASE
 CLARIFY. PER FBC PL 1003.3.1
  
 2. WHAT DOES FBO STAND FOR ON THE FLOOR TROUGH AND
 MOPSINK LOCATED ON THE GREASE RISER. PER WPB AMEND TO
 FBC 107.2.1
  
 3. SHT. P.0.2 UNDER THR PLUMBING SPECIFICATIONS 1.02
 HAS THE WRONG CODE YEAR WE ARE UNDER THE 2014 5TH
 EDITION PLEAS CLARIFY. PER WPB AMEND TO FBC 107.2.1
  
 4. SHT P.3.1 WATER RISER PLEASE IDENTIFY HOT WATER
 RETURN PIPING. PER WPB AMEND TO FBC 107.2.1
  
 5. SHT. P.1.1 IS LABELED AS BASEMENT LEVEL BUT THE PLAN
 SHOWS THE MAIN FLOOR ALSO MAKES IT VERY DIFFICULT TO
 DISCERN THE PLUMBING THE DIFFERENT LEVELS PLEASE
 SEPARATE. PER WPB AMEND TO FBC 107.2.1
  
 PLEASE NOTE THAT SUBMITTAL OF ADDITIONAL AND/OR REVISED
 MATERIALS MAY RESULT IN NEW PLAN REVIEW COMMENTS.
 WHEN RESUBMITTING, IT IS HELPFUL TO PROVIDE A RESPONSE
 LETTER ADDRESSING EACH ITEM ALONG WITH THE CITY
 RE-SUBMITTAL FORM. PLEASE, ADDITIONALLY, INSERT
 CORRECTED PAGES INTO TO SUBMITTAL AND REMOVE OR VOID
 THE PREVIOUSLY REVIEWED SHEETS.
  
 GEORGE JOHNSON
 PLUMBING PLANS EXAMINER
 CITY OF WEST PALM BEACH
  561-805-6711
 [email protected]
  