2017-07-07 11:30:41 | 2ND REVIEW FBC-2014 MECHANICAL , ENERGY CONSERVATION |
| CODES. |
| WEST PALM BEACH AMENDMENTS TO THE FBC. |
| PERMIT #16110061 |
| 7/7/17 |
| |
| PLAN REVIEW RESULTS: DENIED. |
| |
| 1) SHEETS M0.1 & M1.1: REFER TO COMMENT #3 FROM THE 1ST |
| REVIEW AND SECTION 404.2 MINIMUM VENTILATION FOR |
| PARKING GARAGES. PLEASE PROVIDE EXHAUST CACULATIONS |
| BASED ON A MINIMUM AIRFLOW RATE OF 0.05 CFMS PER SQ. |
| FT. AND A MAXIMUM CAPABILITY OF 0.75 CFMS PER SQ. FT. |
| PLACE A NOTE THAT THE SYSTEM WILL OPERATE CONTINUOUSLY |
| NOT BELOW THE MINIMUM AIRFLOW RATE. |
| |
| 2) M1.1, DETAIL 2: PLEASE PROVIDE A WRITTEN NARRATIVE |
| TO ACCOMPANY AND CLARIFY THE GAS MONITORING CONTROL |
| SEQUENCE OF OPERATION. |
| |
| 3) M1.1: REFER TO COMMENT #9 FROM THE 1ST REVIEW AND |
| SECTIONS 502.4 & 502.8. AS PREVIOUSLY REQUESTED |
| INDICATE WHERE THE GOLF CART BATTERIES WILL BE STORED |
| AND CHARGED AND PROVIDE CONTINOUS VENTILATION THAT WILL |
| LIMIT THE CONCENTRATION OF HYDROGEN TO 1.0 PERCENT OF |
| THE TOTAL VOLUME OF THE ROOM- SECTION 502.4.1. A) THE |
| SUBMITTED DOCUMENT FROM "CLUB CAR" APPEARS TO BE JUST |
| ONE PAGE OF A MULTI-PAGE DOCUMENT. PLEASE PROVIDE A |
| COMPLETE SUBMITTAL WITH A REVIEW AND APPROVAL STAMP BY |
| THE ENGINEER OF RECORD. B) THE FLOOR PLAN SHOWS ONLY |
| TWO GAS SENSORS FOR THE ENTIRE AREA: PROVIDE |
| MANUFACTURER'S SPECIFICATIONS TO VERIFY THE SPACINGS |
| ARE ADEQUATE, AND NOTE THAT A SENSOR WILL BE REQUIRED |
| IN THE BATTERY STORAGE ROOM. C) PLEASE PLACE A NOTE ON |
| THE PLANS PURSUANT TO TABLE 403.3 FOOTNOTE B THAT NO |
| EXHAUST AIR FROM THE PARKING GARAGE WILL BE |
| RECIRCULATED TO OCCUPIED SPACES VIA AHU-1. |
| |
| 4) M1.1, M1.2, & M2.1- DETAIL 12: PROVIDE DUCT SMOKE |
| DETECTORS IN THE RETURN AIR SYSTEMS OF AHU'S 1, 2, & 3- |
| SECTION 606.2.1. PROVIDE SYMBOLS TO SHOW THE |
| INSTALLATION LOCATIONS. |
| |
| 5) M1.2 & M1.3 & M1.3: NO REFERENCE TO THE MUA FAN(S) |
| FOR THE HOODS ARE SHOWN ON THE MECHANICAL FLOOR PLANS |
| AND NO EQUIPMENT SCHEDULES HAVE BEEN PROVIDED, OR FAN |
| LOCATIONS SHOWN. |
| |
| 6) M1.2: THE 2X2' ACCESS PANEL FOR AHU-2 APPEARS TWO |
| SMALL TO BE ABLE TO REMOVE AND REPLACE AHU-2, AND NO |
| PANEL LOCATIONS ARE SHOWN FOR VAV BOXES AND FANS THAT |
| ARE LOCATED ABOVE HARD CEILINGS- PLEASE SEE CODED NOTE |
| #1 ON THE PLAN, AND SECTION 306.1 AND SHOW ALL PROPOSED |
| PANEL LOCATIONS AND DIMENSIONS. |
| |
| 7) M1.1: PROVIDE THE CLEARANCE DISTANCE MEASUREMENT |
| BETWEEN EXHAUST FANS EF-3A & 3B AND THE 24X12 O/A |
| LOUVER. THE LOCATIONS DO NOT APPEAR TO BE IN COMPLIANCE |
| WITH EITHER 401.4 OR 506.3.13.3. |
| |
| 8) M2.1 : PROVIDE THE WIND DESIGN CRITERIA USED TO |
| ESTABLISH THE TIE DOWN DESIGN FOR THE CONDENSERS, AND |
| SUBMIT A FL. PRODUCT APPROVAL OR MIAMI-DADE NOA FOR THE |
| CLIP. PLEASE NOTE ALL SUBMITTALS SHALL BEAR THE SHOP |
| DRAWING APPROVAL STAMP FROM THE EOR. |
| |
| 9) PLEASE PROVIDE A MECHANICAL ROOF PLAN SHOWING THE |
| LOCATIONS OF OF EQUIPMENT, AND ALL MECHANICAL OR |
| GRAVITY O/A INTAKE OPENINGS AND EXHAUST OUTLETS. |
| |