Plan Review Notes For Permit 16110061 |
Permit Number |
16110061 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2017-07-07 11:09:44 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | GAS COMMENTS: | | | | PREVIOUS COMMENT NOT COMPLIED 2ND REQUEST5. SUBMIT | | CALCULATIONS FOR COMBUSTION AIR PER THE FBC-2014 FUEL | | GAS CODE SEC. 304. THE WATER HEATERS ARE THE ONLY | | DIRECT VENT GAS APPLIANCES PLEASE PROVIDE COMBUSTION | | CALC FOR KITCHEN COOKING APPLIANCES. | | | | NEW COMMENTS: | | | | 1. THE NOTE ON THE GAS RISER 11/2" G(GWH-2/399) IS THIS | | INDICATING 2 GWH AT 399 CFH THE PLAN ONLY SHOWS ONE | | PLEASE CLARIFY. PER WPB AMEND TO FBC 107.2.1 | | | | 2. SHOW ALL PIPING FOR GWH ON RISER WITH SIZE AND | | LENGTH. PER WPB AMEND TO FBC 107.2.1 | | | | 3. PLEASE SHOW METER ON RISER. PER WPB AMEND TO FBC | | 107.2.1 | | | | 4. SHOW ANSUL VALVE ON RISER. PER WPB AMEND TO FBC | | 107.2.1 | | | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | |
|