2017-07-03 13:17:21FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH ED
 NFPA 70 2011 EDITION
  
 JAKE LEAHY
 ELECTRICAL PLANS EXAMINER II
 561-805-6713
 [email protected]
  
 PAGE E-2-1
 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL (B) OTHER THAN DWELLING UNITS
  
 (8) GARAGES, SERVICE BAYS, AND SIMILAR AREAS
  
  
 PAGE E-3-1
 210.8 GROUND-FAULT CIRCUIT-INTERRUPTER PROTECTION
 FOR PERSONNEL (B) OTHER THAN DWELLING UNITS
 ALL 125-VOLT, SINGLE-PHASE 15- AND 20-AMPERE
 RECEPTACLES
 INSTALLED IN THE LOCATIONS SPECIFIED IN 210.8(B)(1)
 THROUGH
 (8) SHALL HAVE GROUND-FAULT CIRCUITINTERRUPTER
 PROTECTION FOR PERSONNEL.
  
 (2) KITCHENS
  
  
 PAGE E-41
  
 RISER SHOWS 800A GENERATOR SET WITH 620A OF WIRE
  
 PAGE E-6-1
  
 LOAD CALCULATION SHOWS PERCENTAGES USED FOR LOAD CALC
 LIKE 110%, 121% ?
 HVAC LOAD OF 5.7 ? THERE IS OTHERS SHOWN HOW IS 5.7 THE
 LOAD FOR ACS?