Plan Review Notes
Plan Review Notes For Permit 16110061
Permit Number 16110061
Review Stop B
Sequence Number 2
Notes
Date Text
2017-06-30 07:15:43****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 STRUCTURE PERMIT IS TO BE ISSUED PRIOR TO ISSUANCE OF
 THIS PERMIT. IF STRUCTURE PERMIT IS NOT ISSUED, VALUE
 IS TO BE ADJUSTED.
  
 1-15. OK
  
 16. FROM PREVIOUS LIST: REVISE PLAN TO SHOW COMPLIANCE
 WITH FBC B 705, TABLES 602, 705.8. DISTANCE TO ASSUMED
 PROPERTY LINE OR PROPERTY LINE NOT CLEAR, COMPLIANCE
 NOT CLEAR. PROVIDE A SITE PLAN, OR REVISE THE SITE
 PLAN, TO INCLUDE THE PROPERTY LINES, ASSUMED PROPERTY
 LINES, AND DIMENSIONS OF THIS BUILDING TO THE PROPERTY
 LINES, DIMENSION OF ADJACENT BUILDING (OR FUTURE
 ADJACENT BUILDING) TO THE ASSUMED PROPERTY LINE OR
 PROPERTY LINE.
  
 2ND REVIEW, A004, A SITE PLAN SHOWING POD LINES WAS
 PROVIDED. THE EAST DISTANCE TO PROPERTY LINE IS SHOWN
 AS 14'2 1/8", BUT THIS IS SHOWN TO A POINT WHICH IS NOT
 WORST CASE. THE NORTHEAST CORNER OF THE BUILDING
 APPEARS TO TOUCH THE PROPERTY LINE ON AN ANGLE. THE
 OVERHAND APPEARS TO EXTEND OVER THE POD BOUNDARY LINE.
 THE NORTH SIDE OF THE BUILDING APPEARS TO SHOW A
 TRELLIS WHICH EXTENS TO "PBA #4 BOUNDARY LINE".
  
 REVISE AND SHOW COMPLIANCE WITH FBC B 705, TABLES 602,
 705.8, 705.2 (PROJECTIONS).
  
 REVISE PLAN TO CLARIFY, WHAT IS "POD BOUNDARY LINE"? IS
 THIS PROPERTY UNDERGOING A REPLAT? IS THIS THE PROPOSED
 PROPERTY LINE? IF THIS IS NOT THE PROPOSED NEW PROPERTY
 LINE (AFTER REPLAT), REVISE PLAN TO SHOW PROPOSED NEW
 PROPERTY LINES (AFTER REPLAT).
  
 FEEL FREE TO CONTACT ME TO DISCUSS RESOLUTIONS TO BE
 APPROVED PRIOR TO RESUBMITTAL.
  
 17-27. OK
  
 28. FBC A 226, 902, DINING SURFACES, REVISE PLAN TO
 SHOW COMPLIANCE.
  
 2ND REVIEW, BANYAN GRILL DOES NOT APPEAR TO HAVE AN
 ACCESSIBLE SECTION. PLEASE EXPLAIN RATIONALE.
  
 29-49. OK
  
 THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISOS:
  
 A. PRODUCT APPROVALS NOT SUBMMITTED. ALL PRODUCT
 APPROVALS ARE TO BE SUBMITTED AND REVIEWED PRIOR TO
 INSTALLATION. PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 B. A SEPARATE ROOF PERMIT IS REQUIRED. THE ROOF PRODUCT
 APPROVAL INDICATING THE ASSEMBLY PROPOSED AND
 ENGINEERING, IF APPLICABLE, IS TO BE SUBMITTED. THE
 ROOF PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL. ROOF PERMIT REQUIRED PRIOR
 TO ROOF WORK COMMENCEMENT.
  
 C.PROVIDE A DETAIL FOR THE HORIZONTAL 1 HOUR ASSEMBLY,
 EITHER TESTED ASSEMBLY OR CALCULATED, FBC B 703.2.
 REVISE PLAN TO INCLUDE DAMPERS REQUIRED, OR REVISE PLAN
 TO INCLUDE EXCEPTION.
  
  