2017-06-30 07:15:43 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| STRUCTURE PERMIT IS TO BE ISSUED PRIOR TO ISSUANCE OF |
| THIS PERMIT. IF STRUCTURE PERMIT IS NOT ISSUED, VALUE |
| IS TO BE ADJUSTED. |
| |
| 1-15. OK |
| |
| 16. FROM PREVIOUS LIST: REVISE PLAN TO SHOW COMPLIANCE |
| WITH FBC B 705, TABLES 602, 705.8. DISTANCE TO ASSUMED |
| PROPERTY LINE OR PROPERTY LINE NOT CLEAR, COMPLIANCE |
| NOT CLEAR. PROVIDE A SITE PLAN, OR REVISE THE SITE |
| PLAN, TO INCLUDE THE PROPERTY LINES, ASSUMED PROPERTY |
| LINES, AND DIMENSIONS OF THIS BUILDING TO THE PROPERTY |
| LINES, DIMENSION OF ADJACENT BUILDING (OR FUTURE |
| ADJACENT BUILDING) TO THE ASSUMED PROPERTY LINE OR |
| PROPERTY LINE. |
| |
| 2ND REVIEW, A004, A SITE PLAN SHOWING POD LINES WAS |
| PROVIDED. THE EAST DISTANCE TO PROPERTY LINE IS SHOWN |
| AS 14'2 1/8", BUT THIS IS SHOWN TO A POINT WHICH IS NOT |
| WORST CASE. THE NORTHEAST CORNER OF THE BUILDING |
| APPEARS TO TOUCH THE PROPERTY LINE ON AN ANGLE. THE |
| OVERHAND APPEARS TO EXTEND OVER THE POD BOUNDARY LINE. |
| THE NORTH SIDE OF THE BUILDING APPEARS TO SHOW A |
| TRELLIS WHICH EXTENS TO "PBA #4 BOUNDARY LINE". |
| |
| REVISE AND SHOW COMPLIANCE WITH FBC B 705, TABLES 602, |
| 705.8, 705.2 (PROJECTIONS). |
| |
| REVISE PLAN TO CLARIFY, WHAT IS "POD BOUNDARY LINE"? IS |
| THIS PROPERTY UNDERGOING A REPLAT? IS THIS THE PROPOSED |
| PROPERTY LINE? IF THIS IS NOT THE PROPOSED NEW PROPERTY |
| LINE (AFTER REPLAT), REVISE PLAN TO SHOW PROPOSED NEW |
| PROPERTY LINES (AFTER REPLAT). |
| |
| FEEL FREE TO CONTACT ME TO DISCUSS RESOLUTIONS TO BE |
| APPROVED PRIOR TO RESUBMITTAL. |
| |
| 17-27. OK |
| |
| 28. FBC A 226, 902, DINING SURFACES, REVISE PLAN TO |
| SHOW COMPLIANCE. |
| |
| 2ND REVIEW, BANYAN GRILL DOES NOT APPEAR TO HAVE AN |
| ACCESSIBLE SECTION. PLEASE EXPLAIN RATIONALE. |
| |
| 29-49. OK |
| |
| THIS PERMIT WILL BE ISSUED WITH THE FOLLOWING PROVISOS: |
| |
| A. PRODUCT APPROVALS NOT SUBMMITTED. ALL PRODUCT |
| APPROVALS ARE TO BE SUBMITTED AND REVIEWED PRIOR TO |
| INSTALLATION. PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL. |
| |
| B. A SEPARATE ROOF PERMIT IS REQUIRED. THE ROOF PRODUCT |
| APPROVAL INDICATING THE ASSEMBLY PROPOSED AND |
| ENGINEERING, IF APPLICABLE, IS TO BE SUBMITTED. THE |
| ROOF PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL. ROOF PERMIT REQUIRED PRIOR |
| TO ROOF WORK COMMENCEMENT. |
| |
| C.PROVIDE A DETAIL FOR THE HORIZONTAL 1 HOUR ASSEMBLY, |
| EITHER TESTED ASSEMBLY OR CALCULATED, FBC B 703.2. |
| REVISE PLAN TO INCLUDE DAMPERS REQUIRED, OR REVISE PLAN |
| TO INCLUDE EXCEPTION. |
| |
| |