2017-03-01 16:42:48 | 1ST REVIEW | | | | GEORGE JOHNSON | | PLUMBING PLANS EXAMINER LL | | CITY OF WEST PALM BEACH | | DEVELOPMENT SERVICES | | BUILDING DIVISION | | 561-805-6711 | | [email protected] | | | | PLUMBING COMMENTS: | | | | 1. SHT. P-3-3 PLEASE SEPARATE THE ISOMETRIC DRAWINGS , | | THE BASEMENT FROM THE 1ST FLOOR AND THE GREASE ALL | | SEPARATE OR EXPANDED SO THAT THE DIFFERENT LAYERS ARE | | NOT ON TOP OF EACH OTHER. PER WPB AMEND TO FBC 107.2.1 | | | | 2. TRAP PRIMERS ARE REQUIRED ON ALL FLOOR DRAINS SHOW | | TRAP PRIMERS ON THE ISOMETRIC DRAWING OR PUT A NOTE ON | | THE PLAN. PER FBC PL 1002.4 AND WPB AMEND TO FBC | | 107.2.1 | | | | 3. PROVIDE ISOMETRIC DRAWINGS FOR THE STORM SHOWING THE | | GRADE OF THE PIPE AND THE SQFT BEING DRAINED BY EACH | | DRAIN. WPB AMEND TO FBC 107.3.5.1.3(13) | | | | 3. A DRAIN PAN IS REQUIRED FOR WATER HEATER NOT SHOWN | | ON DETAIL SHT P-4-3. PER FBC PL 504.7 | | | | WHEN RESUBMITTING PLANS, REMOVE AND REPLACE ANY PAGES | | AS NECESSARY. A NARRATIVE LISTING THE ORIGINAL REVIEW | | COMMENT NUMBER WITH A DESCRIPTION OF THE CHANGES MADE | | AND IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE | | THE CHANGE CAN BE FOUND WILL HELP EXPEDITE THE REVIEW. | | |
|