2017-02-03 10:35:57 | 1ST REVIEW FBC-2014 MECHANICAL |
| PERMIT #16110061 |
| 2/3/17 |
| |
| 1) THE SUMMARY AC COOLING AND HEATING CALCULATIONS |
| SHALL BEAR AN ELECTRONIC SIGNATURE AND SEAL BY THE |
| ENGINEER OF RECORD- SECTION C403.2.1 EXCEPTION FBC-14 |
| ENERGY CONSERVATION, AND SECTION 61G15-23.005 FLORIDA |
| ADMINISTRATIVE CODE. |
| |
| 2) THE ENERGYGAUGE COMPLIANCE SUBMITTAL MUST BEAR THE |
| CERTIFICATION SIGNATURES OF THE DESIGN PROFESSIONALS |
| AND THE OWNER/AGENT ON PAGE 3, AND MUST BE |
| ELECTRONICALLY SIGNED AND SEALED PER SECTION |
| 61G15-23.005 FAC. |
| |
| 3) PROVIDE EXHAUST VENTILATION CALULATIONS FOR THE |
| PARKING GARAGE, THE LOCKER ROOMS AND BATHROOMS, AND THE |
| KITCHEN PER TABLE 403.3. A) INDICATE HOW MAKEUP AIR IS |
| BEING PROVIDED FOR THE GARAGE AND LOCKER ROOM EXHAUST |
| SYSTEMS. B) PROVIDE AIR BALANCE CALCULATIONS FOR BOTH |
| FLOORS THAT INCLUDE ALL EXHAUST SYSTEMS. |
| |
| 4) ADVISORY: SEPARATE PERMITS AND PLANS ARE REQUIRED |
| FOR THE KITCHEN EXHAUST SYSTEM, THE KITCHEN HOOD FIRE |
| SUPPRESSION, AND THE WALK-IN COOLER/FREEZER. PLEASE |
| PLACE A NOTE ON THE PLANS ACCORDINGLY. PLEASE NOTE THE |
| FOLLOWING: A) THE HOOD EXHAUST FAN OUTLETS TERMINATING |
| AT THE EXTERIOR WALL SHALL BE IN COMPLIANCE WITH |
| 506.3.13.2. B) THE FANS MUST BE ANCHORED TO THE |
| BUILDING TO WITHSTAND THE DESIGN WINDLOADS AND |
| PRESSURES, AND INSTALLED IN A MANNER TO PREVENT WATER |
| INTRUSION. |
| |
| 5) THE AC EQUIPMENT SCHEDULE ON M-3.1 INDICATES THAT AN |
| ERV IS REQUIRED FOR AHU-1: REFER TO TABLE C403.2.6 AND |
| SECTION C403.2.6 FBC-14 ENERGY CONSERVATION. |
| |
| 6) M-3.1: PROVIDE AN EQUIPMENT SCHEDULE FOR THE VAV |
| BOXES. |
| |
| 7) M-3.1: PROVIDE CONTROL SEQUENCES FOR ALL EXHAUST |
| SYSTEMS. |
| |
| 8) M-1.1: LABEL THE AIR HANDLER, IDENTIFY AND LABEL THE |
| SUPPLY DIFFUSERS AND RETURN GRILLS. |
| |
| 9) M-1.1: PROVIDE VENTILATION FOR THE BAG STORAGE, |
| STORAGE, AND MAINTENANCE ROOMS- TABLE 403.3. PLEASE SEE |
| SECTION 502 AND ALL APPLICABLE SUB-SECTIONS AND PROVIDE |
| EXHAUST VENTILATION WHERE REQUIRED FOR ALL FUEL, OR |
| BATTERY STORAGE ROOMS OR AREAS. PLEASE NOTE THAT A |
| DETAILED LIST OF ALL HAZARDOUS MATERIALS AND THEIR |
| QUANTITIES MAY BE REQUIRED PER SECTION414.1.3 FBC-14 |
| BUILDING. |
| |
| 10) M-1.1 & M-1.2: FIRE DAMPERS ARE REQUIRED WHERE THE |
| 32X20, 22X14, AND 3" DUCTS PENETRATE THE FLOOR/CEILING |
| ASSEMBLY- SECTION 607.6.2. |
| |
| 11) M-1.1 & M-1.2: THE PLANS ARE INDICATING AIR FROM |
| THE GROUND FLOOR GARAGE WILL BE RECIRCULATED INTO THE |
| OCCUPIED AREAS ON THE FIRST FLOOR WHICH IS PROHIBITED |
| BY FOOTNOTE B, TABLE 403.3. |
| |
| 12) M-1.1: PROVIDE THE EXHAUST OUTLET CLEARANCE |
| DISTANCES AS OUTLINED IN SECTION 501.3.1. |
| |
| 13) M.1-1: CORRECT THE DUCT HEIGHT NOTE TO INDICATE |
| MINIMUM 7'0" CLEARANCE FROM FINISHED GARAGE FLOOR TO |
| BOTTOM OF THE DUCT- SECTION 406.4.1 FBC-14 BUILDING. |
| |
| 14) M-1.2: THE PLAN DOES NOT APPEAR TO SHOW ANY EXHAUST |
| VENTILATION FOR THE MEN'S AND WOMEN'S LOCKER ROOMS |
| WHICH IS REQUIRED BY TABLE 403.3. PLEASE SEE FOOTNOTE G |
| AS IT APPEARS RECIRCULATION FROM THOSE AREAS IS |
| EXCEEDING THE ALLOWABLE MAXIMUM. |
| |
| 15) M-1.2: THE PLAN APPEARS TO SHOW TWO L4 DIFFUSERS IN |
| THE RECEPTION ROOM CONNECTED TO TWO B RETURN GRILLS IN |
| THE GOLF-PRO OFFICE. |
| |
| 16) M-1.2: PROVIDE ALL FLEX DUCT SIZES. |
| |
| 17) M-1.2: INDICATE HOW ACCESS WILL BE PROVIDED FOR |
| MAINTENANCE AND REPLACEMENT OF AHU'S 2 & 3- SECTION |
| 306.1. |
| |
| 18) M-1.2: PROVIDE ENGINEERED DETAILS FOR TIE DOWN OF |
| THE AC CONDENSER UNITS- SECTION 301.15. |
| |
| 19) SUBMIT TWO COPIES OF A VALID FL.PRODUCT APPROVAL |
| AND/OR MIAMI-DADE NOA FOR THE LOUVERS- RULE 9N-B FAC. |
| |
| 20) A COMPLETE REVIEW OF THE PROPOSED PROJECT CANNOT BE |
| PERFORMED AT THIS TIME DUE TO A LACK OF INFORMATION. IN |
| ORDER TO EXPEDITE THE SECOND REVIEW PLEASE PROVIDED A |
| DETAILED NARRATIVE THAT ITEMIZES ALL CORRECTIONS MADE |
| TO THE PLANS. PLEASE NOTE ADDITIONAL COMMENTS MAY |
| FOLLOW THIS INITIAL REVIEW. |
| |
| CHRISTOPHER L. COLE |
| MECHANICAL PLANS EXAMINER |
| 561-805-6719 |