2017-02-07 13:30:08 | 3200 NORTH CONGRESS AVENUE - CLUBHOUSE |
| PERMIT #16110061 & 17010998 (TWO DIFFERENT PERMITS FOR |
| SAME STRUCTURE?) |
| REVIEW COMMENTS - FIRE DEPARTMENT |
| |
| |
| GENERAL: PER NFPA 241 SECTION 8.7.2.3, WHERE |
| UNDERGROUND WATER MAINS AND HYDRANTS ARE TO BE |
| PROVIDED, THEY SHALL BE INSTALLED, COMPLETED, AND IN |
| SERVICE PRIOR TO VERTICAL CONSTRUCTION WORK OR |
| ACCUMULATION OF COMBUSTIBLE MATERIALS. PER SECTION |
| 18.3.4.1 (NFPA 1), FIRE HYDRANTS SHALL BE PROVIDED WITH |
| CLEARANCES OF 7'-6" TO THE FRONT AND SIDES AND 4'-0" TO |
| THE BACKSIDE OF THE STEAMER CAP. |
| |
| GENERAL: A SUB PERMIT (UG FIRELINE) IS NEEDED TO |
| INSTALL FIRE MAINS AND FIRE HYDRANTS. |
| |
| GENERAL: PER NFPA 241 SECTION 4.2.2: DETACHMENT BETWEEN |
| TEMPORARY STRUCTURES, ADEQUATE TEMPORARY FIXED FIRE |
| PROTECTION SYSTEMS, AND PORTABLE EQUIPMENT SHALL BE |
| PROVIDED AS REQUIRED BY THE AUTHORITY HAVING |
| JURISDICTION.TEMPORARY CONSTRUCTION TRAILERS OR MODULAR |
| BUILDINGS WILL REQUIRE A PERMIT AND COMPLIANCE WITH THE |
| FOLLOWING: |
| PER NFPA 241- STANDARD FOR SAFEGUARDING CONSTRUCTION, |
| ALTERATION, AND DEMOLITION OPERATIONS, SECTION 4.2: |
| TEMPORARY OFFICES, TRAILERS, AND OTHER FACILITIES OF |
| COMBUSTIBLE CONSTRUCTION OR HOUSING COMBUSTIBLE |
| CONTENTS SHALL BE SEPARATED FROM ADJACENT BUILDINGS, |
| TRAILERS OR STRUCTURES IN ACCORDANCE WITH TABLE 4.2.1. |
| PER TABLE 4.2.1: |
| 1) 20 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 30 FEET |
| 2) 30 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 35 FEET |
| 3) 40 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 40 FEET |
| 4) 50 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 45 FEET |
| 5) 60 FEET EXPOSED LENGTH SHALL BE SEPARATED FROM |
| ADJACENT STRUCTURES BY AT LEAST 50 FEET |
| 6) GREATER THAN 60 FEET EXPOSED LENGTH SHALL BE |
| SEPARATED FROM ADJACENT STRUCTURES BY AT LEAST 60 FEET |
| **A 75 PERCENT REDUCTION IN SEPARATION DISTANCES SHALL |
| BE PERMITTED TO BE APPLIED, PROVIDED AUTOMATIC |
| SPRINKLER PROTECTION IS USED IN THE EXPOSING STRUCTURE. |
| |
| GENERAL: PROVIDE DRAWING NOTE INDICATING ALL |
| CONSTRUCTION WORK SHALL CONFORM TO THE REQUIREMENTS OF |
| NFPA 241. TRASH AND CONSTRUCTION DEBRIS SHALL BE |
| REMOVED FROM THE SITE DAILY. SMOKING SHALL BE |
| PROHIBITED EXCEPT IN DESIGNATED EXTERIOR AREAS. ALL |
| OTHER DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| SMOKING" SIGNS POSTED. WHERE SMOKING IS PERMITTED, SAFE |
| RECEPTACLES FOR SMOKING MATERIALS SHALL BE PROVIDED. |
| |
| GENERAL: PROVIDE AN EXTERIOR KEY SAFE TO ALLOW |
| EMERGENCY RESPONDERS NON-FORCIBLE ENTRY INTO THE |
| BUILDING DURING NON-BUSINESS HOURS. A KEY SAFE CAN BE |
| ORDERED FROM WWW.KNOXBOX.COM. |
| |
| GENERAL: STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| REFLECTIVE COLOR AND BEAR THE APPROPRIATE LETTER R/F/RF |
| DESIGNATION PER FLORIDA STATUTE 633.027 AND FLORIDA |
| ADMINISTRATIVE CODE 69A-60.0081. |
| |
| CIVIL: SUBMIT OFFICIAL CIVIL DRAWINGS SHOWING ALL FIRE |
| DEPARTMENT ACCESS ROADS, FIRE MAINS, AND FIRE HYDRANTS. |
| CIVIL PLANS INDICATE FOR REFERENCE ONLY. MOST OF THE |
| SAME CIVIL PLANS ARE SUBMITTED MULTIPLE TIMES; AND |
| DRAWING SET IS NOT A COMPLETE CIVIL SET. |
| |
| SITE: PER SECTION 18.2.3.4.1.1 (NFPA 1), FIRE |
| DEPARTMENT ACCESS ROADS SHALL HAVE A SURFACE DESIGNED |
| TO ACCOMMODATE FIRE APPARATUS WEIGHING AT LEAST 38 |
| TONS. ACCESS ROADS SHALL HAVE AN UNOBSTRUCTED WIDTH OF |
| NOT LESS THAN 20 FEET AND AN UNOBSTRUCTED VERTICAL |
| CLEARANCE OF NOT LESS THAN 13 FEET 6 INCHES. |
| |
| SITE: PER SECTION 18.2.3.5.3 (NFPA 1), FIRE LANES SHALL |
| BE MARKED WITH FREESTANDING SIGNS READING, "FIRE LANE - |
| NO PARKING BY ORDER OF THE FIRE DEPARTMENT." SIGNS |
| SHALL BE 12" X 18" WITH A WHITE BACKGROUND AND RED |
| LETTERS AND SHALL BE A MAXIMUM OF SEVEN FEET IN HEIGHT |
| TO THE BOTTOM OF THE SIGN. SIGNS SHALL BE WITHIN SIGHT |
| OF THE TRAFFIC FLOW AND BE SPACED A MAXIMUM OF 60 FEET |
| APART. |
| |
| CIVIL: PER NFPA 1 SECTION18.2.3.2.1 A FIRE DEPARTMENT |
| ACCESS ROAD SHALL EXTEND TO WITHIN 50 FEET OF AT LEAST |
| ONE EXTERIOR DOOR THAT CAN BE OPENED FROM THE OUTSIDE |
| AND THAT PROVIDES ACCESS TO THE INTERIOR OF THE |
| BUILDING. THE CURRENT DRIVE AISLE NEAR THE CLUBHOUSE IS |
| NOT AN APPROVED FIRE LANE BECAUSE IT DOES NOT HAVE A |
| MINIMUM CLEAR WIDTH OF 20 FEET AND CANNOT RELIABLY |
| REMAIN UNOBSTRUCTED FROM GOLF CARTS, VEHICLES, ETC AT |
| ALL TIMES AS IS SHOWN IN SHEET A204.ADDITIONALLY THE |
| PORTE COCHIERE MAY IMPEDE FIRE RESCUE OPERATIONS. |
| |
| CIVIL: COULD NOT LOCATE A FIRE HYDRANT NEAR THE |
| CLUBHOUSE. |
| |
| SHEET A003: BASEMENT STAIR AND KITCHEN OCCUPANTS |
| INDICATE AN EXIT DISCHARGE THROUGH THE DELIVERY AND |
| DUMPSTER AREA. |
| |
| SHEET A003: EGRESS DOOR NEAR THE ADA RAMP IS OBSTRUCTED |
| BY TABLE AND CHAIRS. |
| |
| GENERAL: PROVIDE A KITCHEN EQUIPMENT SCHEDULE. |
| |
| GENERAL: PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT |
| DOORS WITH EXIT SIGNS. |
| |
| GENERAL: FOR ASSEMBLY OCCUPANCIES WITH AN OCCUPANT LOAD |
| OF 100 OR MORE PERSONS (50 PERSONS PER THE FLORIDA |
| BUILDING CODE), PANIC HARDWARE SHALL BE PROVIDED ON |
| DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR |
| LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE |
| PANIC HARDWARE. AS A SUBSTITUTE FOR PANIC HARDWARE, THE |
| MAIN ENTRANCE (ONLY) IS PERMITTED TO HAVE AN INTERIOR |
| KEYED DOOR LOCK (AND NO LATCH) WITH A READILY VISIBLE |
| SIGN STATING THIS DOOR TO REMAIN UNLOCKED WHEN THE |
| BUILDING IS OCCUPIED. SIGN LETTERS SHALL BE AT LEAST 1 |
| INCH IN HEIGHT. KEYED LOCK TO BE EQUIPPED WITH AN |
| "OPEN/LOCKED" INDICATOR WINDOW (SUCH AS ADAMS RITE 4089 |
| OR SIMILAR). A THUMB TURN STYLE LOCK IS NOT PERMITTED |
| TO BE SUBSTITUTED FOR A KEYED LOCK.SHEET |
| A THOROUGH AND COMPLETE PLAN REVIEW CANNOT BE COMPLETED |
| AT THIS TIME DUE TO LACK OF INFORMATION SUBMITTED ON |
| THE PLANS. ADDITIONAL PLAN REVIEW COMMENTS MAY BE |
| GENERATED DURING PLAN RESUBMISSION. |
| |
| SHEET FP-1.1: THE ENTIRE BASEMENT IS STORAGE; PROTECT |
| ENTIRE SPACE AS ORDINARY HAZARD. |
| |
| SHEET FP-1.2: PROTECT MERCANTILE PRO SHOP #113 AS |
| ORDINARY HAZARD. |
| |
| SHEET E-1.2: DOES NOT APPEAR TO BE ANY EXTERIOR |
| EMERGENCY LIGHTING ON EAST SIDE OF BUILDING AND ADA |
| RAMP AREA. |
| |
| SHEET E-2.2: PER SECTION 12.3.4.3.3, PROVIDE |
| SPEAKER/STROBE NOTIFICATION APPLIANCES AS ASSEMBLY |
| OCCUPANCIES WITH AN OCCUPANT LOAD EXCEEDING 300 |
| OCCUPANTS SHALL RECEIVE FIRE ALARM NOTIFICATION BY |
| VISIBLE SIGNALS AND VOICE ANNOUNCEMENTS. PROVIDE A |
| PRE-RECORDED FIRE ALARM EVACUATION MESSAGE NOTIFYING |
| OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN THE |
| BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE |
| BUILDING IMMEDIATELY. DO NOT USE THE ELEVATOR. |
| |
| SHEET E-2.2: NO NOTIFICATION APPLIANCES PROVIDED IN ALL |
| RESTROOMS, CHANGING ROOMS OR SHOWER SPACES. |
| |
| SHEET M-1.2 & M-1.3: KITCHEN EXHAUST FANS ARE |
| TERMINATING AT AN OUTSIDE WALL IN LIEU OF ROOFTOP |
| TERMINATION. THE FANS ARE LOCATED WITHIN 10 FEET OF THE |
| COMBUSTIBLE ROOF WHICH IS NOT PERMITTED BY NFPA 96 |
| SECTION 7.8.3. |
| |
| NOTE: REVIEW AND APPROVAL BY THE AHJ SHALL NOT RELIEVE |
| THE OWNER, CONTRACTOR, ETC. OF THE RESPONSIBILITY OF |
| COMPLIANCE WITH CODE (NFPA 1, SECTION 1.14.4).FBC |
| SECTION 105.4.1 PERMIT INTENT: A PERMIT ISSUED SHALL BE |
| CONSTRUED TO BE A LICENSE TO PROCEED WITH THE WORK AND |
| NOT AS AUTHORITY TO VIOLATE, CANCEL, ALTER OR SET ASIDE |
| ANY OF THE PROVISIONS OF THE TECHNICAL CODES, NOR SHALL |
| ISSUANCE OF A PERMIT PREVENT THE BUILDING OFFICIAL FROM |
| THEREAFTER REQUIRING A CORRECTION OF ERRORS IN PLANS, |
| CONSTRUCTION OR VIOLATIONS OF THIS CODE. |
| |