2017-02-14 11:17:29APPLICABLE CODES IN EFFECT:
 FLORIDA BUILDING CODE 2014 5TH EDITION
 FLORIDA BUILDING CODE ENERGY CONSERVATION 2014 5TH
 EDITION
 NFPA 70- 2011
 COMMENTS:
  
 1. GENERAL NOTES TO CONSTRUCTION DOCUMENTS: PLEASE
 PROVIDE A BLOCK NOTE INDICATING THE REQUIRED SEPARATE
 PERMITS AND DATA SPECIFICATION SHEET SUBMITTALS FOR ALL
 LOW VOLTAGE SYSTEMS TO INCLUDE BUT NOT LIMITED TO FIRE
 ALARM, CCTV, PHONE AND DATA, WIRELESS SYSTEMS, CARD
 READERS, GENERATOR, KITCHEN HOODS ETC. A NOTE WILL
 SUFFICE.
 2. ADD A GENERAL NOTE TO PROVIDE PER FBC EC 405.7.4-
 COMPLETION DOCUMENTS PER CODE SECTION. FBC EC 405.7.3-
 VOLTAGE DROP
 3. PROVIDE GENERAL NOTES TO ELECTRICAL RISER DIAGRAM TO
 INDICATE NEC 110.16. ARC FLASH WARNING SIGNS AND NEC
 110.24- AVAILABLE FAULT CURRENT- FIELD MARKINGS; SEE
 VERBIAGE IN CODE.
 4. PROVIDE THE AVAILABLE FAULT CURRENT AT THE UTILITY
 TRANSFORMER. FBC 107.3.5
 5. PER FBC EC 405.7- A MINIMUM OF 50% OF ALL 125V, 15
 AND 20AMP RECEPTACLES SHALL BE AUTOMATICALLY CONTROLLED
 WHERE INSTALLED IN PRIVATE OR OPEN OFFICES AND COMPUTER
 CLASSROOMS. THIS INCLUDES MODULAR PARTITIONS TOO. SHOW
 COMPLIANCE ACCORDINGLY.
 6. PROVIDE A NOTE TO INDICATE COMPLIANCE WITH FBC EC
 405.2 AUTOMATIC LIGHTING CONTROL AND LIGHTING DENSITIES
 PER CODE SECTION.
 7. PLEASE ADDRESS BUILDING, FIRE AND MECHANICAL
 COMMENTS RELATED TO ELECTRICAL.
 8. PROVIDE A NOTE ON PLANS TO INDICATE NEC 300.5
 REQUIREMENTS FOR ALL UNDERGROUND RACEWAYS.
 9. PROVIDE 1/2" DETAIL OF MAIN ELECTRICAL ROOM( WHERE
 MDP IS LOCATED) TO VERIFY CLEARANCE. FBC 107.3.5
 10. PROVIDE GFCI PROTECTION FOR ALL RECEPTACLES IN THE
 BASEMENT AREA AND MAINTENANCE SECTION PER NEC 210.8B
 (6)INDOOR WET LOCATION (8) SIMILAR AREAS WHERE
 ELECTRICAL DIAGNOSTIC EQUIPMENT, ELECTRICAL HAND TOOLS
 ARE TO BE USED.- THAT WILL INCLUDE ALL 125V SINGLE
 PHASE 15 OR 20A RECEPTACLES.
 11. PLEASE NOTE THAT THE SEPARATE GENERATOR PERMIT
 REQUIRED WILL NEED TO PROVIDE A SELECTED LOAD
 ARRANGEMENT BASED ON CUSTOMER SELECTED LOADS. MANUAL
 TRANSFER SELECTED. NEC 702.4.B1. ALSO SIGNAGE IS TO BE
 PROVIDED PER NEC 702.7A. A NOTE WILL SUFFICE
 12. COMMENTS MAY FOLLOW UPON RE-REVIEW. PLEASE FEEL
 FREE TO CONTACT ME SHOULD YOU HAVE ANY QUESTIONS
 REGARDING THIS PROJECT.
  
  
 VALENTINO PEREZ
 ELECTRICAL PLANS EXAMINER II
 561-805-6717
 [email protected]
  
  
  
  
  