Date |
Text |
2017-03-10 15:05:25 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL |
| BUILDING PLANS EXAMINER |
| [email protected] |
| 561-805-6724 |
| |
| FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014) |
| FBC B = FBC BUILDING |
| FBC EB = FBC EXISTING BUILDING |
| FBC A = FBC ACCESSIBILITY |
| FBC EC = FBC ENERGY CONSERVATION |
| |
| 1. FBC 1007, FBC A 207, REVISE PLAN TO STATE WHICH |
| METHOD OF COMPLIANCE IS ELECTED (IBC 2000 OR IBC 2003). |
| |
| 2. CIRCULATION PATH NOT CLEAR, FBC A 206.3; IN |
| PARTICULAR, COMMUNICATION BETWEEN GARAGE AND CLUBHOUSE |
| FLOORS. PROVIDE INFORMATION REGARDING THE USE OF THE |
| SPACES AND HOW OCCUPANTS, BOTH EMPLOYEES AND GUESTS, |
| ACCESS THE SPACES. IT IS RECOMMENDED TO SEND THIS |
| INFORMATION VIA EMAIL PRIOR TO RESUBMITTAL IN ORDER TO |
| PROVIDE A COMPLETE REVIEW. |
| |
| PLAN SHOWS A STAIR WHICH APPEARS TO BE AN EMPLOYEE |
| STAIR AS IT IS LOCATED IN EMPLOYEE AREAS |
| (DELIVERY/DUMPSTER AREA ON 1ST FLOOR, MAINTENANCE AREA |
| ON BASEMENT LEVEL). ACCESSIBLE ROUTE, VERTICAL |
| ACCESSIBILITY NOT CLEAR BETWEEN LEVELS. IT IS NOT CLEAR |
| UNDER WHICH EXEPTION VERTICAL ACCESSIBLITY IS NOT |
| PROVIDED. USE OF THE GARAGE AREA AND THE NEED FOR |
| EMPLOYEES (OR OTHER OCCUPANTS) TO TRAVEL FROM ONE FLOOR |
| TO THE OTHER IS NOT CLEAR. |
| |
| 3. A101, CLARIFY USE OF GOLF CART PARKING FACILITY. WHO |
| WILL USE THIS AREA, EMPLOYEES ONLY OR VISITORS? WILL |
| GOLF CARTS BE RENTED? WILL CARS BE SELF PARKED OR |
| PARKED BY EMPLOYEES? A MAINTENANCE AREA IS SHOWN; IS |
| THIS FOR FACILITY OWNED CARTS OR PRIVATELY OWNED CARTS? |
| IS THIS GARAGE PARKING (RESIDENTS OR OTHERS SELF PARK |
| THEIR CARTS), OR IS THIS STORAGE (FACILITY OWNED CARTS |
| BROUGHT OUTSIDE AS NEEDED BY EMPLOYEES)? FBC A |
| 206.2.15, 1006. THE ACCESSIBLE ROUTE REQUIRED IS NOT |
| CLEAR. REVISE PLAN TO ADDRESS ACCESSIBILITY ISSUES. |
| |
| 4. EXIT FROM KITCHEN ROOM 100, SHEET A003, THE EXIT |
| DISCHARGE IS NOT CLEAR. THE EXIT OPENS INTO THE |
| DELIVERY & DUMPSTER AREA #130, AND A GATE WHICH |
| COMPLIES WITH FBC B1008.1.2 IS NOT PROVIDED; SEE ALSO |
| 1008.1.1 (4 FT MAX), 1008.2 (GATES TO MEET SAME |
| REQUIREMENTS AS DOORS), 1003.1 (REQUIREMENTS APPLICABLE |
| TO EXIT DISCHARGE). EXIT DISCHARGE IS TO BE CONTINUOUS |
| TO THE PUBLIC WAY, 1027.5. |
| |
| 5. A003, FBC B 1014.2, REVISE PLAN TO EXPLAIN RATIONALE |
| OF EXITING THROUGH A DUMPSTER AREA, ESPECIALLY FROM THE |
| BASEMENT. IT APPEARS THAT EXITING THROUGH A HIGHER |
| HAZARD AREA IS PROPOSED. IF EXIT STRATEGY IS NOT |
| REVISED, THIS IS TO BE APPROVED VIA EMAIL BY FIRE AND |
| BUILDING PRIOR TO RESUBMITTAL. |
| |
| 6. A003, ACCESSIBLE ROUTE NOT CLEAR FOR COVERED OUTDOOR |
| DINING FROM RAMP. THE ROUTE IS BLOCKED BY TABLES, |
| REVISE OR CLARIFY. |
| |
| 7. A101 SHOWS A 4" ELEVATION CHANGE AT THE DOOR TO THE |
| STAIR. FBC A 403.4, 303.2, FBC B 1008.1.5, IT IS NOT |
| CLEAR UNDER WHICH EXCEPTION THIS IS PERMITTED. REVISE |
| PLAN TO INCLUDE APPLICABLE EXCEPTION, OR REVISE PLAN TO |
| COMPLY WITH THESE CODE SECTIONS. VERIFY THAT THERE ARE |
| NO OTHER CHANGES IN ELEVATION IN THE MEANS OF EGRESS, |
| WITH THE EXCEPTION OF STAIRS AND RAMPS. |
| |
| 8. A101 AT THE BASE OF THE STAIR AT DUMPSTER AREA, |
| THERE APPEARS TO BE A DRAIN. REVISE PLAN TO SHOW |
| COMPLIANCE WITH FBC A 302.3 (GRATES), 403.3 (SLOPE). |
| |
| 9. A213, THE RAMP DETAIL, TOP LANDING AT DOOR, DOOR |
| DOES NOT APPEAR TO HAVE THE 18" MANEUVERING CLEARANCE |
| REQUIRED, REVISE, FBC A 404.2.4.1. |
| |
| 10. A003, REVISE OCCUPANT LOAD TO ROUND UP (CANNOT HAVE |
| A FRACTION OF AN OCCUPANT), FBC B TABLE 1004.1.2. |
| |
| 11. A001 BUILDING DATA, A/C SPACE IS 7673, BUT A003 |
| OCCUPANCY LOAD SCHEDULE APPEARS TO SHOW A TOTAL SF AREA |
| UNDER AIR OF 6895, REVISE PLAN TO CLARIFY DISCREPANCY. |
| OUTDOOR AREAS, OCCUPANCY LOAD SCHEDULE ALSO APPEAR TO |
| HAVE A DISCREPANCY. REVISE TO CLARIFY, SUBTOTALS |
| SUGGESTED. |
| |
| 12. A003, REVISE PLAN TO CLARIFY PURPOSE OF COVERED |
| GOLF TERRACE 126, AND CLARIFY USE OF 100 SF PER PERSON |
| FOR THIS AREA WHICH APPEARS TO BE AN AREA WHERE |
| OCCUPANTS MAY CONGREGATE. 100 SF PER PERSON IS USED FOR |
| OFFICE SPACE WHICH HAS FURNISHINGS; THIS AREA APPEARS |
| TO BE OPEN. |
| |
| 13. A003 IS LACKING MANY DOORS, FBC 107. REVISE PLAN TO |
| BE CONSISTENT WITH PROPOSED CONSTRUCTION. FOR INSTANCE, |
| NO DOORS LEADING FROM BANYAN GRILLE TO COVERED OUTDOOR |
| DINING. DOORS ARE SHOWN ON OTHER SHEETS. |
| |
| 14. A SHEETS SPECIFY ELEVATIONS IN NAVD88. CIVIL SHEETS |
| UTILIZE NGVD29 VERTICAL DATUM (SEE MASTER PLAN SHEET 2 |
| WHICH REFERENCES SFWMD BASIN CRITERIA IN NGVD29, COVER |
| SHEET WHICH INCLUDES A NOTE THAT ALL ELEVATIONS ARE |
| NGVD29). BOTH A SHEETS AND CIVILS SPEC FINISHED FLOOR |
| AT 27.50. CLARIFY VERTICAL DATUM; BOTH ARE TO USE THE |
| SAME OR TO INCLUDE CONVERSIONS (NOT A CONVERSION |
| FACTOR). NOTE THAT THE CITY STANDARD IS NGVD29 UNTIL |
| NEW FIRMS ARE ADOPTED. IT IS RECOMMENDED THAT ALL |
| ELEVATIONS BE PROVIDED IN NGVD29. |
| |
| THE VERTICAL DATUM DISCREPANCY RESULTS IN A CONFLICT OF |
| APPROXIMATELY 1.55 FEET. REVISE ELEVATIONS TO BE |
| CONSISTENT AND VERIFY ELEVATIONS ON OTHER BUILDINGS FOR |
| THIS PROJECT AS THIS MAY AFFECT (AMONG OTHER THINGS) |
| ACCESSIBILITY AND UTILITIES. |
| |
| 15. PROVIDE A COPY OF THE SURVEY FOR THIS PARCEL, FBC |
| 107, FBC TABLE 602, 705.8. |
| |
| 16. REVISE PLAN TO SHOW COMPLIANCE WITH FBC B 705, |
| TABLES 602, 705.8. DISTANCE TO ASSUMED PROPERTY LINE OR |
| PROPERTY LINE NOT CLEAR, COMPLIANCE NOT CLEAR. PROVIDE |
| A SITE PLAN, OR REVISE THE SITE PLAN, TO INCLUDE THE |
| PROPERTY LINES, ASSUMED PROPERTY LINES, AND DIMENSIONS |
| OF THIS BUILDING TO THE PROPERTY LINES, DIMENSION OF |
| ADJACENT BUILDING (OR FUTURE ADJACENT BUILDING) TO THE |
| ASSUMED PROPERTY LINE OR PROPERTY LINE. |
| |
| 17. A201 SHOWS TWO ARROWS IN THE HALL AT THE BATHROOMS |
| WEST OF THE WOMENS LOCKER, REVISE TO CLARIFY WHAT THE |
| GRAPHIC DEPICTS. |
| |
| 18. A003 AND OTHER SHEETS, REVISE PLAN TO SHOW |
| MANEUVERING CLEARANCE, PULL SIDE, FOR BOTH DOORS AT |
| MENS VESTIBULE 116 (MINIMUM 18"), FBC A 404.2.4.1. |
| |
| 19. SHOE DROP 119, FBC B 1008.1.1, THE ENTRY TO THE |
| SPACE IS SHOWN AS 2'6", MINIMUM 32" REQUIRED, REVISE. |
| CHECK ALL. |
| |
| 20. THE RESTAURANT BAR AREA INCLUDES TABLES AND CHAIRS |
| WHICH APPEAR TO RESTRICT THE ACCESSIBLE ROUTE, FBC A |
| CHAPTER 4. REVISE TO CLARIFY REQUIREMENTS AND DESIGN |
| INTENT. |
| |
| 22. A701, FBC 1008.1.10, PANIC DEVICES OR FIRE EXIT |
| HARDWARE IS REQUIRED ON ALL DOORS AND GATES IN THE |
| MEANS OF EGRESS SERVING ASSEMBLY OCCUPANCY WITH AN |
| OCCUPANT LOAD OVER 50. THE DOOR LOCKSET GROUPS DOES NOT |
| INCLUDE PANIC DEVICES OR FIRE EXIT HARDWARE. REVISE THE |
| INTERIOR DOOR SCHEDULE, EXTERIOR DOOR SCHEDULE, |
| EXTERIOR WINDOW SCHEDULE, ANY OTHER APPLICABLE AREAS. |
| |
| IF THERE ARE ANY GATES IN THE MEANS OF EGRESS, REVISE |
| PLAN TO INCLUDE THE GATE INFORMATION. |
| |
| 23. I WAS UNABLE TO LOCATE SOME OF THE DOORS TYPES IN |
| THE SCHEDULE (SUCH AS TYPE P AND TYPE Q). THE DOORS DO |
| NOT APPEAR TO COMPLY WITH THE REQUIREMENTS FOR THIS |
| OCCUPANCY. REMOVE (OR X OUT) DOORS WHICH ARE NOT FOR |
| THIS PROJECT. IF THEY ARE TO BE INCLUDED, PLEASE DIRECT |
| TO THE LOCATION. |
| |
| 24. A801, TOILET, THE TOP OF THE SEAT IS TO BE A MAX OF |
| 19"; THE DETAIL APPEARS TO DEPICT THE LOWER PART OF THE |
| TANK, ABOVE THE LID. REVISE DETAIL TO CLEARLY SHOW THAT |
| THE SEAT IS TO BE A MAX OF 19", FBC A 604.4. |
| |
| 25. A802 ADA NOTES INCLUDE AN OLD CODE REFERENCE (FBC |
| 11-4.13.9), REVISE TO REMOVE. |
| |
| 26. WOMENS 107 ADA, SEE FBC A 604.8.1.6 AND 604.8.1.7 |
| AND ADVISORY, DOOR IS TO BE DIAGONAL TO THE WATER |
| CLOSET. |
| |
| 27. LOCKER ROOMS, CHANGING ROOMS, SEE FBC A 803. REVISE |
| PLAN TO SHOW COMPLIANCE WITH ALL REQUIREMENTS. |
| |
| HTTPS://WWW.ACCESS-BOARD.GOV/GUIDELINES-AND-STANDARDS/R |
| ECREATION-FACILITIES/GUIDES/SPORTS-FACILITIES/DRESSING, |
| -FITTING,-OR-LOCKER-ROOMS |
| |
| 28. FBC A 226, 902, DINING SURFACES, REVISE PLAN TO |
| SHOW COMPLIANCE. |
| |
| 29. RECEPTION AREA A201, OTHER SERVICE OR CHECK OUT |
| AREAS (FOR EXAMPLE, SHOE DROP, PRO SHOP) PROVIDE A |
| DETAIL FOR THE SERVICE (OR CHECK OUT) COUNTERS, FBC A |
| 227, 904. |
| |
| 30. PROVIDE A DETAIL FOR THE HORIZONTAL 1 HOUR |
| ASSEMBLY, EITHER TESTED ASSEMBLY OR CALCULATED, FBC B |
| 703.2. REVISE PLAN TO INCLUDE DAMPERS REQUIRED, OR |
| REVISE PLAN TO INCLUDE EXCEPTION. |
| |
| 31. A ROOF HATCH IS SHOWN ON A904, BUT I WAS UNABLE TO |
| LOCATE THIS ITEM ON THE ENERGY CALC INPUT DATA REPORT, |
| EITHER INCLUDE OR ADVISE AS TO WHERE THIS CAN BE FOUND, |
| FBC 107. IF A ROOF HATCH IS NOT PROPOSED FOR THIS |
| PROJECT, REMOVE OR X OUT DETAIL. |
| |
| 32. DETAIL 9-A904, STRUCTURAL INFORMATION NOT INCLUDED. |
| EITHER REVISE TO INCLUDE OR, IF NOT LOCATED ELSEWHERE |
| ON THE PLAN, THIS WILL BE A PROVISO ITEM - SUBJECT TO |
| INSPECTOR'S DISCRETION, A REVISION MAY BE REQUIRED |
| PRIOR TO INSTALLATION. |
| |
| 33. S004 NOMINAL C&C WIND PRESSURES STATE THE PORTE |
| COCHERE IS OPEN, SEE DEFINITION, DOES NOT APPEAR TO |
| MEET THE CRITERIA FOR AN OPEN BUILDING, SEE ASCE7-10 |
| 26.1.2.2 DEFINITION OF OPEN BUILDING IS A BUILDING WITH |
| EACH WALL AT LEAST 80% OPEN. THE PORTE COCHERE IS A |
| PORTION OF A BUILDING, ONE WALL ENCLOSED. IF ENGINEER |
| DISAGREES, PUT RATIONALE IN WRITING AND SEND VIA EMAIL |
| FOR CONSIDERATION PRIOR TO RESUBMITTAL. |
| |
| 34. S102, WOOD CONNECTOR SCHEDULE, MARK 5 SPECS LGT, 1 |
| 3/4" TITENS. SEE CATALOG, SEVERAL DIFFERENT LGT, REVISE |
| TO SPECIFY WHICH CONNECTOR. IF LGT 2 IS PROPOSED, THE |
| FASTENER SPECIFIED ON THE PLAN IS NOT THE SAME AS THE |
| ONE SPECIFIED IN THE SIMPSON CATALOG (1 3/4" TITEN |
| RATHER THAN 2 1/4" TITEN 2). REVISE OR PROVIDE |
| CALCULATIONS OR OTHER DOCUMENTATION TO SUPPORT USE OF A |
| SMALLER FASTENER. CHECK ALL. |
| |
| 35. FS471, THE A SHEETS HAVE A TITLE BLOCK FOR RANDALL |
| STOFFT AS ARCHITECT, BUT THE DIGITAL SIGNATURE IS FOR |
| DON DURANTE. EITHER REVISE THE TITLE BLOCK AND SEAL TO |
| SHOW DON DURANTE AS ARCHITECT, OR HAVE THE SHEETS |
| SIGNED AND SEALED BY RANDALL STOFFT. IF THIS IS AN |
| ERROR IN THE DIGITAL SIGNATURE, PLEASE CONTACT THE |
| ISSUER. ISSUER HAS CONFIRMED THAT THIS IS NOT CORRECT; |
| THE "SIGNED BY" NAME IS TO MATCH THE NAME OF THE |
| INDIVIDUAL SIGNING. |
| |
| 36. THE SEAL FOR RANDALL STOFFT IS NOT CONSISTENT WITH |
| THE DESCRIPTION OF SEAL FAC 61G1-16.002. EITHER REVISE |
| OR ADVISE VIA EMAIL THAT ARCHITECT OBJECTS TO THE |
| COMMENT. AN EMAIL WILL THEN BE SENT TO FLORIDA BOARD OF |
| ARCHITECTS TO DETERMINE WHETHER OR NOT THE SEAL ON THE |
| PLAN IS ACCEPTABLE. |
| |
| IF ARCHITECT OBJECTS TO EITHER COMMENT, PLEASE CONTACT |
| ME. IT APPEARS THAT ALL A SHEETS NEED TO BE RESUBMITTED |
| WITH A CORRECTED SEAL IMAGE AND CORRECT SIGNATURE & |
| SEAL. TO AVOID PERMIT ISSUANCE DELAYS, PLEASE DO NOT |
| RESUBMIT WITHOUT THESE TWO ITEMS CORRECTED UNLESS WE |
| HAVE DISCUSSED THIS IN ADVANCE. |
| |
| 37. CIVIL SHEETS ARE REQUIRED, SEE FIRE COMMENTS. |
| DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR |
| PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED |
| ORIGINALS, FS471. IF THIS DESIGN PROFESSIONAL DOES NOT |
| HAVE A DIGITAL OR ELECTRONIC SIGNATURE, PLEASE CONTACT |
| ME REGARDING ALTERNATE METHODS OF SUBMITTAL. |
| |
| 38. ENERGY INPUT REPORT HAS THE FOLLOWING ISSUES: NO |
| DOORS SHOWN, WATER HEATER NOT INCLUDED. CHECK ALL |
| ITEMS. |
| |
| 39. INCORPORATE REQUIREMENT OF 23.2 R VALUE FOR THE |
| ROOF (PER ENERGY CALCS) INTO THE PLAN, OR ADVISE WHERE |
| THIS INFORMATION CAN BE FOUND, FBC 107. |
| |
| 40. PRODUCT APPROVALS NOT SUBMMITTED. ALL PRODUCT |
| APPROVALS ARE TO BE SUBMITTED AND REVIEWED PRIOR TO |
| INSTALLATION. PRODUCT APPROVALS ARE TO BE REVIEWED BY |
| DESIGNER OF RECORD PRIOR TO SUBMITTAL. |
| |
| 41. FBC B 406, REVISE PLAN TO NOTE THE GOLFCART GARAGE |
| AS AN ENCLOSED PARKING GARAGE. 406.6, IT IS NOT CLEAR |
| WHERE THE CO2 CENSORS ARE LOCATED, PLEASE ADVISE. |
| |
| 42. REVISE PLAN TO PROVIDE INFORMATION REGARDING WHAT |
| WILL BE STORED IN THE STORAGE AREAS, FBC 107. INCLUDE |
| BATTERY STORAGE, CHEMICAL STORAGE; AMOUNTS, MSDS SHEETS |
| IF APPLICABLE, FUEL AMOUNTS. |
| |
| 43. DETAIL 9-A904 HAS TEXT WHICH IS NOT LEGIBLE; |
| REVISE. |
| |
| 44. DETAIL 9-A904 REFERS TO DETAIL MA/FA/BA 115, ADVISE |
| AS TO WHERE THIS CAN BE LOCATED, FBC 107. |
| |
| 45. FBC A 209, 503.5, REVISE PLAN TO INCLUDE CLEARANCE |
| REQUIRED AT THE PORTE COCHERE (114" MINIMUM). |
| |
| 46. A SEPARATE ROOF PERMIT IS REQUIRED. THE ROOF |
| PRODUCT APPROVAL INDICATING THE ASSEMBLY PROPOSED AND |
| ENGINEERING, IF APPLICABLE, IS TO BE SUBMITTED. THE |
| ROOF PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER OF |
| RECORD PRIOR TO SUBMITTAL. ROOF PERMIT REQUIRED PRIOR |
| TO ROOF WORK COMMENCEMENT. |
| |
| 47. S102 SPECS 5/8" APA SHEATHING, A SHEETS INCLUDE |
| DETAILS WITH 19/32", 3/4" IN VARIOUS PLACES (FOR |
| INSTANCE, SEE A904), PLEASE CORRELATE. |
| |
| 48. REVISE STRUCTURAL PAGES TO INCLUDE VERTICAL DATUM, |
| FBC 107 (FOR INSTANCE, S103). SHEET S201 INCLUDES A TOP |
| OF FOOTING EELEVATION IN SECTION 1; 23'2" NAVD. SEE |
| OTHER COMMENTS REGARDING VERTICAL DATUM. IF NGVD29 IS |
| USED ON OTHER SHEETS, AND NAVD88 IS USED FOR S SHEETS, |
| INCLUDE CONVERSION. |
| |
| 49. FP01, NOTE 22, PLEASE COMPLETE INFORMATION. |
| |
| |