2017-03-10 15:05:25****CORRECTIONS****
  
 SAMANTHA HILL
 BUILDING PLANS EXAMINER
 [email protected]
 561-805-6724
  
 FBC = FLORIDA BUILDING CODE, 5TH EDITION (2014)
 FBC B = FBC BUILDING
 FBC EB = FBC EXISTING BUILDING
 FBC A = FBC ACCESSIBILITY
 FBC EC = FBC ENERGY CONSERVATION
  
 1. FBC 1007, FBC A 207, REVISE PLAN TO STATE WHICH
 METHOD OF COMPLIANCE IS ELECTED (IBC 2000 OR IBC 2003).
  
 2. CIRCULATION PATH NOT CLEAR, FBC A 206.3; IN
 PARTICULAR, COMMUNICATION BETWEEN GARAGE AND CLUBHOUSE
 FLOORS. PROVIDE INFORMATION REGARDING THE USE OF THE
 SPACES AND HOW OCCUPANTS, BOTH EMPLOYEES AND GUESTS,
 ACCESS THE SPACES. IT IS RECOMMENDED TO SEND THIS
 INFORMATION VIA EMAIL PRIOR TO RESUBMITTAL IN ORDER TO
 PROVIDE A COMPLETE REVIEW.
  
 PLAN SHOWS A STAIR WHICH APPEARS TO BE AN EMPLOYEE
 STAIR AS IT IS LOCATED IN EMPLOYEE AREAS
 (DELIVERY/DUMPSTER AREA ON 1ST FLOOR, MAINTENANCE AREA
 ON BASEMENT LEVEL). ACCESSIBLE ROUTE, VERTICAL
 ACCESSIBILITY NOT CLEAR BETWEEN LEVELS. IT IS NOT CLEAR
 UNDER WHICH EXEPTION VERTICAL ACCESSIBLITY IS NOT
 PROVIDED. USE OF THE GARAGE AREA AND THE NEED FOR
 EMPLOYEES (OR OTHER OCCUPANTS) TO TRAVEL FROM ONE FLOOR
 TO THE OTHER IS NOT CLEAR.
  
 3. A101, CLARIFY USE OF GOLF CART PARKING FACILITY. WHO
 WILL USE THIS AREA, EMPLOYEES ONLY OR VISITORS? WILL
 GOLF CARTS BE RENTED? WILL CARS BE SELF PARKED OR
 PARKED BY EMPLOYEES? A MAINTENANCE AREA IS SHOWN; IS
 THIS FOR FACILITY OWNED CARTS OR PRIVATELY OWNED CARTS?
 IS THIS GARAGE PARKING (RESIDENTS OR OTHERS SELF PARK
 THEIR CARTS), OR IS THIS STORAGE (FACILITY OWNED CARTS
 BROUGHT OUTSIDE AS NEEDED BY EMPLOYEES)? FBC A
 206.2.15, 1006. THE ACCESSIBLE ROUTE REQUIRED IS NOT
 CLEAR. REVISE PLAN TO ADDRESS ACCESSIBILITY ISSUES.
  
 4. EXIT FROM KITCHEN ROOM 100, SHEET A003, THE EXIT
 DISCHARGE IS NOT CLEAR. THE EXIT OPENS INTO THE
 DELIVERY & DUMPSTER AREA #130, AND A GATE WHICH
 COMPLIES WITH FBC B1008.1.2 IS NOT PROVIDED; SEE ALSO
 1008.1.1 (4 FT MAX), 1008.2 (GATES TO MEET SAME
 REQUIREMENTS AS DOORS), 1003.1 (REQUIREMENTS APPLICABLE
 TO EXIT DISCHARGE). EXIT DISCHARGE IS TO BE CONTINUOUS
 TO THE PUBLIC WAY, 1027.5.
  
 5. A003, FBC B 1014.2, REVISE PLAN TO EXPLAIN RATIONALE
 OF EXITING THROUGH A DUMPSTER AREA, ESPECIALLY FROM THE
 BASEMENT. IT APPEARS THAT EXITING THROUGH A HIGHER
 HAZARD AREA IS PROPOSED. IF EXIT STRATEGY IS NOT
 REVISED, THIS IS TO BE APPROVED VIA EMAIL BY FIRE AND
 BUILDING PRIOR TO RESUBMITTAL.
  
 6. A003, ACCESSIBLE ROUTE NOT CLEAR FOR COVERED OUTDOOR
 DINING FROM RAMP. THE ROUTE IS BLOCKED BY TABLES,
 REVISE OR CLARIFY.
  
 7. A101 SHOWS A 4" ELEVATION CHANGE AT THE DOOR TO THE
 STAIR. FBC A 403.4, 303.2, FBC B 1008.1.5, IT IS NOT
 CLEAR UNDER WHICH EXCEPTION THIS IS PERMITTED. REVISE
 PLAN TO INCLUDE APPLICABLE EXCEPTION, OR REVISE PLAN TO
 COMPLY WITH THESE CODE SECTIONS. VERIFY THAT THERE ARE
 NO OTHER CHANGES IN ELEVATION IN THE MEANS OF EGRESS,
 WITH THE EXCEPTION OF STAIRS AND RAMPS.
  
 8. A101 AT THE BASE OF THE STAIR AT DUMPSTER AREA,
 THERE APPEARS TO BE A DRAIN. REVISE PLAN TO SHOW
 COMPLIANCE WITH FBC A 302.3 (GRATES), 403.3 (SLOPE).
  
 9. A213, THE RAMP DETAIL, TOP LANDING AT DOOR, DOOR
 DOES NOT APPEAR TO HAVE THE 18" MANEUVERING CLEARANCE
 REQUIRED, REVISE, FBC A 404.2.4.1.
  
 10. A003, REVISE OCCUPANT LOAD TO ROUND UP (CANNOT HAVE
 A FRACTION OF AN OCCUPANT), FBC B TABLE 1004.1.2.
  
 11. A001 BUILDING DATA, A/C SPACE IS 7673, BUT A003
 OCCUPANCY LOAD SCHEDULE APPEARS TO SHOW A TOTAL SF AREA
 UNDER AIR OF 6895, REVISE PLAN TO CLARIFY DISCREPANCY.
 OUTDOOR AREAS, OCCUPANCY LOAD SCHEDULE ALSO APPEAR TO
 HAVE A DISCREPANCY. REVISE TO CLARIFY, SUBTOTALS
 SUGGESTED.
  
 12. A003, REVISE PLAN TO CLARIFY PURPOSE OF COVERED
 GOLF TERRACE 126, AND CLARIFY USE OF 100 SF PER PERSON
 FOR THIS AREA WHICH APPEARS TO BE AN AREA WHERE
 OCCUPANTS MAY CONGREGATE. 100 SF PER PERSON IS USED FOR
 OFFICE SPACE WHICH HAS FURNISHINGS; THIS AREA APPEARS
 TO BE OPEN.
  
 13. A003 IS LACKING MANY DOORS, FBC 107. REVISE PLAN TO
 BE CONSISTENT WITH PROPOSED CONSTRUCTION. FOR INSTANCE,
 NO DOORS LEADING FROM BANYAN GRILLE TO COVERED OUTDOOR
 DINING. DOORS ARE SHOWN ON OTHER SHEETS.
  
 14. A SHEETS SPECIFY ELEVATIONS IN NAVD88. CIVIL SHEETS
 UTILIZE NGVD29 VERTICAL DATUM (SEE MASTER PLAN SHEET 2
 WHICH REFERENCES SFWMD BASIN CRITERIA IN NGVD29, COVER
 SHEET WHICH INCLUDES A NOTE THAT ALL ELEVATIONS ARE
 NGVD29). BOTH A SHEETS AND CIVILS SPEC FINISHED FLOOR
 AT 27.50. CLARIFY VERTICAL DATUM; BOTH ARE TO USE THE
 SAME OR TO INCLUDE CONVERSIONS (NOT A CONVERSION
 FACTOR). NOTE THAT THE CITY STANDARD IS NGVD29 UNTIL
 NEW FIRMS ARE ADOPTED. IT IS RECOMMENDED THAT ALL
 ELEVATIONS BE PROVIDED IN NGVD29.
  
 THE VERTICAL DATUM DISCREPANCY RESULTS IN A CONFLICT OF
 APPROXIMATELY 1.55 FEET. REVISE ELEVATIONS TO BE
 CONSISTENT AND VERIFY ELEVATIONS ON OTHER BUILDINGS FOR
 THIS PROJECT AS THIS MAY AFFECT (AMONG OTHER THINGS)
 ACCESSIBILITY AND UTILITIES.
  
 15. PROVIDE A COPY OF THE SURVEY FOR THIS PARCEL, FBC
 107, FBC TABLE 602, 705.8.
  
 16. REVISE PLAN TO SHOW COMPLIANCE WITH FBC B 705,
 TABLES 602, 705.8. DISTANCE TO ASSUMED PROPERTY LINE OR
 PROPERTY LINE NOT CLEAR, COMPLIANCE NOT CLEAR. PROVIDE
 A SITE PLAN, OR REVISE THE SITE PLAN, TO INCLUDE THE
 PROPERTY LINES, ASSUMED PROPERTY LINES, AND DIMENSIONS
 OF THIS BUILDING TO THE PROPERTY LINES, DIMENSION OF
 ADJACENT BUILDING (OR FUTURE ADJACENT BUILDING) TO THE
 ASSUMED PROPERTY LINE OR PROPERTY LINE.
  
 17. A201 SHOWS TWO ARROWS IN THE HALL AT THE BATHROOMS
 WEST OF THE WOMENS LOCKER, REVISE TO CLARIFY WHAT THE
 GRAPHIC DEPICTS.
  
 18. A003 AND OTHER SHEETS, REVISE PLAN TO SHOW
 MANEUVERING CLEARANCE, PULL SIDE, FOR BOTH DOORS AT
 MENS VESTIBULE 116 (MINIMUM 18"), FBC A 404.2.4.1.
  
 19. SHOE DROP 119, FBC B 1008.1.1, THE ENTRY TO THE
 SPACE IS SHOWN AS 2'6", MINIMUM 32" REQUIRED, REVISE.
 CHECK ALL.
  
 20. THE RESTAURANT BAR AREA INCLUDES TABLES AND CHAIRS
 WHICH APPEAR TO RESTRICT THE ACCESSIBLE ROUTE, FBC A
 CHAPTER 4. REVISE TO CLARIFY REQUIREMENTS AND DESIGN
 INTENT.
  
 22. A701, FBC 1008.1.10, PANIC DEVICES OR FIRE EXIT
 HARDWARE IS REQUIRED ON ALL DOORS AND GATES IN THE
 MEANS OF EGRESS SERVING ASSEMBLY OCCUPANCY WITH AN
 OCCUPANT LOAD OVER 50. THE DOOR LOCKSET GROUPS DOES NOT
 INCLUDE PANIC DEVICES OR FIRE EXIT HARDWARE. REVISE THE
 INTERIOR DOOR SCHEDULE, EXTERIOR DOOR SCHEDULE,
 EXTERIOR WINDOW SCHEDULE, ANY OTHER APPLICABLE AREAS.
  
 IF THERE ARE ANY GATES IN THE MEANS OF EGRESS, REVISE
 PLAN TO INCLUDE THE GATE INFORMATION.
  
 23. I WAS UNABLE TO LOCATE SOME OF THE DOORS TYPES IN
 THE SCHEDULE (SUCH AS TYPE P AND TYPE Q). THE DOORS DO
 NOT APPEAR TO COMPLY WITH THE REQUIREMENTS FOR THIS
 OCCUPANCY. REMOVE (OR X OUT) DOORS WHICH ARE NOT FOR
 THIS PROJECT. IF THEY ARE TO BE INCLUDED, PLEASE DIRECT
 TO THE LOCATION.
  
 24. A801, TOILET, THE TOP OF THE SEAT IS TO BE A MAX OF
 19"; THE DETAIL APPEARS TO DEPICT THE LOWER PART OF THE
 TANK, ABOVE THE LID. REVISE DETAIL TO CLEARLY SHOW THAT
 THE SEAT IS TO BE A MAX OF 19", FBC A 604.4.
  
 25. A802 ADA NOTES INCLUDE AN OLD CODE REFERENCE (FBC
 11-4.13.9), REVISE TO REMOVE.
  
 26. WOMENS 107 ADA, SEE FBC A 604.8.1.6 AND 604.8.1.7
 AND ADVISORY, DOOR IS TO BE DIAGONAL TO THE WATER
 CLOSET.
  
 27. LOCKER ROOMS, CHANGING ROOMS, SEE FBC A 803. REVISE
 PLAN TO SHOW COMPLIANCE WITH ALL REQUIREMENTS.
  
 HTTPS://WWW.ACCESS-BOARD.GOV/GUIDELINES-AND-STANDARDS/R
 ECREATION-FACILITIES/GUIDES/SPORTS-FACILITIES/DRESSING,
 -FITTING,-OR-LOCKER-ROOMS
  
 28. FBC A 226, 902, DINING SURFACES, REVISE PLAN TO
 SHOW COMPLIANCE.
  
 29. RECEPTION AREA A201, OTHER SERVICE OR CHECK OUT
 AREAS (FOR EXAMPLE, SHOE DROP, PRO SHOP) PROVIDE A
 DETAIL FOR THE SERVICE (OR CHECK OUT) COUNTERS, FBC A
 227, 904.
  
 30. PROVIDE A DETAIL FOR THE HORIZONTAL 1 HOUR
 ASSEMBLY, EITHER TESTED ASSEMBLY OR CALCULATED, FBC B
 703.2. REVISE PLAN TO INCLUDE DAMPERS REQUIRED, OR
 REVISE PLAN TO INCLUDE EXCEPTION.
  
 31. A ROOF HATCH IS SHOWN ON A904, BUT I WAS UNABLE TO
 LOCATE THIS ITEM ON THE ENERGY CALC INPUT DATA REPORT,
 EITHER INCLUDE OR ADVISE AS TO WHERE THIS CAN BE FOUND,
 FBC 107. IF A ROOF HATCH IS NOT PROPOSED FOR THIS
 PROJECT, REMOVE OR X OUT DETAIL.
  
 32. DETAIL 9-A904, STRUCTURAL INFORMATION NOT INCLUDED.
 EITHER REVISE TO INCLUDE OR, IF NOT LOCATED ELSEWHERE
 ON THE PLAN, THIS WILL BE A PROVISO ITEM - SUBJECT TO
 INSPECTOR'S DISCRETION, A REVISION MAY BE REQUIRED
 PRIOR TO INSTALLATION.
  
 33. S004 NOMINAL C&C WIND PRESSURES STATE THE PORTE
 COCHERE IS OPEN, SEE DEFINITION, DOES NOT APPEAR TO
 MEET THE CRITERIA FOR AN OPEN BUILDING, SEE ASCE7-10
 26.1.2.2 DEFINITION OF OPEN BUILDING IS A BUILDING WITH
 EACH WALL AT LEAST 80% OPEN. THE PORTE COCHERE IS A
 PORTION OF A BUILDING, ONE WALL ENCLOSED. IF ENGINEER
 DISAGREES, PUT RATIONALE IN WRITING AND SEND VIA EMAIL
 FOR CONSIDERATION PRIOR TO RESUBMITTAL.
  
 34. S102, WOOD CONNECTOR SCHEDULE, MARK 5 SPECS LGT, 1
 3/4" TITENS. SEE CATALOG, SEVERAL DIFFERENT LGT, REVISE
 TO SPECIFY WHICH CONNECTOR. IF LGT 2 IS PROPOSED, THE
 FASTENER SPECIFIED ON THE PLAN IS NOT THE SAME AS THE
 ONE SPECIFIED IN THE SIMPSON CATALOG (1 3/4" TITEN
 RATHER THAN 2 1/4" TITEN 2). REVISE OR PROVIDE
 CALCULATIONS OR OTHER DOCUMENTATION TO SUPPORT USE OF A
 SMALLER FASTENER. CHECK ALL.
  
 35. FS471, THE A SHEETS HAVE A TITLE BLOCK FOR RANDALL
 STOFFT AS ARCHITECT, BUT THE DIGITAL SIGNATURE IS FOR
 DON DURANTE. EITHER REVISE THE TITLE BLOCK AND SEAL TO
 SHOW DON DURANTE AS ARCHITECT, OR HAVE THE SHEETS
 SIGNED AND SEALED BY RANDALL STOFFT. IF THIS IS AN
 ERROR IN THE DIGITAL SIGNATURE, PLEASE CONTACT THE
 ISSUER. ISSUER HAS CONFIRMED THAT THIS IS NOT CORRECT;
 THE "SIGNED BY" NAME IS TO MATCH THE NAME OF THE
 INDIVIDUAL SIGNING.
  
 36. THE SEAL FOR RANDALL STOFFT IS NOT CONSISTENT WITH
 THE DESCRIPTION OF SEAL FAC 61G1-16.002. EITHER REVISE
 OR ADVISE VIA EMAIL THAT ARCHITECT OBJECTS TO THE
 COMMENT. AN EMAIL WILL THEN BE SENT TO FLORIDA BOARD OF
 ARCHITECTS TO DETERMINE WHETHER OR NOT THE SEAL ON THE
 PLAN IS ACCEPTABLE.
  
 IF ARCHITECT OBJECTS TO EITHER COMMENT, PLEASE CONTACT
 ME. IT APPEARS THAT ALL A SHEETS NEED TO BE RESUBMITTED
 WITH A CORRECTED SEAL IMAGE AND CORRECT SIGNATURE &
 SEAL. TO AVOID PERMIT ISSUANCE DELAYS, PLEASE DO NOT
 RESUBMIT WITHOUT THESE TWO ITEMS CORRECTED UNLESS WE
 HAVE DISCUSSED THIS IN ADVANCE.
  
 37. CIVIL SHEETS ARE REQUIRED, SEE FIRE COMMENTS.
 DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED FOR
 PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED
 ORIGINALS, FS471. IF THIS DESIGN PROFESSIONAL DOES NOT
 HAVE A DIGITAL OR ELECTRONIC SIGNATURE, PLEASE CONTACT
 ME REGARDING ALTERNATE METHODS OF SUBMITTAL.
  
 38. ENERGY INPUT REPORT HAS THE FOLLOWING ISSUES: NO
 DOORS SHOWN, WATER HEATER NOT INCLUDED. CHECK ALL
 ITEMS.
  
 39. INCORPORATE REQUIREMENT OF 23.2 R VALUE FOR THE
 ROOF (PER ENERGY CALCS) INTO THE PLAN, OR ADVISE WHERE
 THIS INFORMATION CAN BE FOUND, FBC 107.
  
 40. PRODUCT APPROVALS NOT SUBMMITTED. ALL PRODUCT
 APPROVALS ARE TO BE SUBMITTED AND REVIEWED PRIOR TO
 INSTALLATION. PRODUCT APPROVALS ARE TO BE REVIEWED BY
 DESIGNER OF RECORD PRIOR TO SUBMITTAL.
  
 41. FBC B 406, REVISE PLAN TO NOTE THE GOLFCART GARAGE
 AS AN ENCLOSED PARKING GARAGE. 406.6, IT IS NOT CLEAR
 WHERE THE CO2 CENSORS ARE LOCATED, PLEASE ADVISE.
  
 42. REVISE PLAN TO PROVIDE INFORMATION REGARDING WHAT
 WILL BE STORED IN THE STORAGE AREAS, FBC 107. INCLUDE
 BATTERY STORAGE, CHEMICAL STORAGE; AMOUNTS, MSDS SHEETS
 IF APPLICABLE, FUEL AMOUNTS.
  
 43. DETAIL 9-A904 HAS TEXT WHICH IS NOT LEGIBLE;
 REVISE.
  
 44. DETAIL 9-A904 REFERS TO DETAIL MA/FA/BA 115, ADVISE
 AS TO WHERE THIS CAN BE LOCATED, FBC 107.
  
 45. FBC A 209, 503.5, REVISE PLAN TO INCLUDE CLEARANCE
 REQUIRED AT THE PORTE COCHERE (114" MINIMUM).
  
 46. A SEPARATE ROOF PERMIT IS REQUIRED. THE ROOF
 PRODUCT APPROVAL INDICATING THE ASSEMBLY PROPOSED AND
 ENGINEERING, IF APPLICABLE, IS TO BE SUBMITTED. THE
 ROOF PRODUCT APPROVAL IS TO BE REVIEWED BY DESIGNER OF
 RECORD PRIOR TO SUBMITTAL. ROOF PERMIT REQUIRED PRIOR
 TO ROOF WORK COMMENCEMENT.
  
 47. S102 SPECS 5/8" APA SHEATHING, A SHEETS INCLUDE
 DETAILS WITH 19/32", 3/4" IN VARIOUS PLACES (FOR
 INSTANCE, SEE A904), PLEASE CORRELATE.
  
 48. REVISE STRUCTURAL PAGES TO INCLUDE VERTICAL DATUM,
 FBC 107 (FOR INSTANCE, S103). SHEET S201 INCLUDES A TOP
 OF FOOTING EELEVATION IN SECTION 1; 23'2" NAVD. SEE
 OTHER COMMENTS REGARDING VERTICAL DATUM. IF NGVD29 IS
 USED ON OTHER SHEETS, AND NAVD88 IS USED FOR S SHEETS,
 INCLUDE CONVERSION.
  
 49. FP01, NOTE 22, PLEASE COMPLETE INFORMATION.
  
  